Proposed Text
Part I
Construction
13VAC5-63-10. Chapter 1 Administration; Section 101 General.
A. Section 101.1 Short title. The Virginia Uniform Statewide Building Code, Part I, Construction, may be cited as the Virginia Construction Code or as the VCC. The term "USBC" shall mean the VCC unless the context in which the term is used clearly indicates it to be an abbreviation for the entire Virginia Uniform Statewide Building Code or for a different part of the Virginia Uniform Statewide Building Code.
Note: This code is also known as the 2015 2018
edition of the USBC due to the use of the 2015 2018 editions of
the model codes.
B. Section 101.2 Incorporation by reference. Chapters 2 - 35
of the 2015 2018 International Building Code, published by the
International Code Council, Inc., are adopted and incorporated by reference to
be an enforceable part of the USBC. The term "IBC" means the 2015
2018 International Building Code, published by the International Code
Council, Inc. Any codes and standards referenced in the IBC are also considered
to be part of the incorporation by reference, except that such codes and
standards are used only to the prescribed extent of each such reference. In
addition, any provisions of the appendices of the IBC specifically identified
to be part of the USBC are also considered to be part of the incorporation by
reference.
Note 1: The IBC references other International Codes and standards including the following major codes:
2015 2018 International Plumbing Code (IPC)
2015 2018 International Mechanical Code (IMC)
2014 2017 NFPA 70
2015 2018 International Fuel Gas Code (IFGC)
2015 2018 International Energy Conservation Code
(IECC)
2015 2018 International Residential Code (IRC)
Note 2: The IRC is applicable to the construction of detached one-family and two-family dwellings and townhouses as set out in Section 310.
C. Section 101.3 Numbering system. A dual numbering system is used in the USBC to correlate the numbering system of the Virginia Administrative Code with the numbering system of the IBC. IBC numbering system designations are provided in the catchlines of the Virginia Administrative Code sections. Cross references between sections or chapters of the USBC use only the IBC numbering system designations. The term "chapter" is used in the context of the numbering system of the IBC and may mean a chapter in the USBC, a chapter in the IBC or a chapter in a referenced code or standard, depending on the context of the use of the term. The term "chapter" is not used to designate a chapter of the Virginia Administrative Code, unless clearly indicated.
D. Section 101.4 Arrangement of code provisions. The USBC is comprised of the combination of (i) the provisions of Chapter 1, Administration, which are established herein, (ii) Chapters 2 - 35 of the IBC, which are incorporated by reference in Section 101.2, and (iii) the changes to the text of the incorporated chapters of the IBC that are specifically identified. The terminology "changes to the text of the incorporated chapters of the IBC that are specifically identified" shall also be referred to as the "state amendments to the IBC." Such state amendments to the IBC are set out using corresponding chapter and section numbers of the IBC numbering system. In addition, since Chapter 1 of the IBC is not incorporated as part of the USBC, any reference to a provision of Chapter 1 of the IBC in the provisions of Chapters 2 - 35 of the IBC is generally invalid. However, where the purpose of such a reference would clearly correspond to a provision of Chapter 1 established herein, then the reference may be construed to be a valid reference to such corresponding Chapter 1 provision.
E. Section 101.5 Use of terminology and notes. The provisions of this code shall be used as follows:
1. The term "this code," or "the code," where used in the provisions of Chapter 1, in Chapters 2 - 35 of the IBC or in the state amendments to the IBC means the USBC, unless the context clearly indicates otherwise.
2. The term "this code," or "the code," where used in a code or standard referenced in the IBC means that code or standard, unless the context clearly indicates otherwise.
3. The use of notes in Chapter 1 is to provide information only and shall not be construed as changing the meaning of any code provision.
4. Notes in the IBC, in the codes and standards referenced in the IBC and in the state amendments to the IBC may modify the content of a related provision and shall be considered to be a valid part of the provision, unless the context clearly indicates otherwise.
F. Section 101.6 Order of precedence. The provisions of this code shall be used as follows:
1. The provisions of Chapter 1 of this code supersede any provisions of Chapters 2 - 35 of the IBC that address the same subject matter and impose differing requirements.
2. The provisions of Chapter 1 of this code supersede any provisions of the codes and standards referenced in the IBC that address the same subject matter and impose differing requirements.
3. The state amendments to the IBC supersede any provisions of Chapters 2 - 35 of the IBC that address the same subject matter and impose differing requirements.
4. The state amendments to the IBC supersede any provisions of the codes and standards referenced in the IBC that address the same subject matter and impose differing requirements.
5. The provisions of Chapters 2 - 35 of the IBC supersede any provisions of the codes and standards referenced in the IBC that address the same subject matter and impose differing requirements.
G. Section 101.7 Administrative provisions. The provisions of
Chapter 1 establish administrative requirements, which include but are not
limited to provisions relating to the scope of the code, enforcement, fees,
permits, inspections and disputes. Any provisions of Chapters 2 - 35 of the IBC
or any provisions of the codes and standards referenced in the IBC that address
the same subject matter and impose differing requirements are deleted and
replaced by the provisions of Chapter 1. Further, any administrative
requirements contained in the state amendments to the IBC shall be given the
same precedence as the provisions of Chapter 1. Notwithstanding the above,
where administrative requirements of Chapters 2 - 35 of the IBC or of the codes
and standards referenced in the IBC are specifically identified as valid
administrative requirements in Chapter 1 of this code or in the state
amendments to the IBC, then such requirements are not deleted and replaced.
Note: The purpose of this provision is to eliminate overlap, conflicts and duplication by providing a single standard for administrative, procedural and enforcement requirements of this code.
H. Section 101.8 Definitions. The definitions of terms used in this code are contained in Chapter 2 along with specific provisions addressing the use of definitions. Terms may be defined in other chapters or provisions of the code and such definitions are also valid.
Note: The order of precedence outlined in Section 101.6 may be determinative in establishing how to apply the definitions in the IBC and in the referenced codes and standards.
13VAC5-63-20. Section 102 Purpose and scope.
A. Section 102.1 Purpose. In accordance with § 36-99 of the Code of Virginia, the purpose of the USBC is to protect the health, safety and welfare of the residents of the Commonwealth of Virginia, provided that buildings and structures should be permitted to be constructed at the least possible cost consistent with recognized standards of health, safety, energy conservation and water conservation, including provisions necessary to prevent overcrowding, rodent or insect infestation, and garbage accumulation; and barrier-free provisions for the physically handicapped and aged.
B. Section 102.2 Scope. This section establishes the scope of the USBC in accordance with § 36-98 of the Code of Virginia. The USBC shall supersede the building codes and regulations of the counties, municipalities and other political subdivisions and state agencies. This code also shall supersede the provisions of local ordinances applicable to single-family residential construction that (i) regulate dwelling foundations or crawl spaces, (ii) require the use of specific building materials or finishes in construction, or (iii) require minimum surface area or numbers of windows; however, this code shall not supersede proffered conditions accepted as a part of a rezoning application, conditions imposed upon the grant of special exceptions, special or conditional use permits or variances, conditions imposed upon a clustering of single-family homes and preservation of open space development through standards, conditions, and criteria established by a locality pursuant to subdivision 8 of § 15.2-2242 of the Code of Virginia or § 15.2-2286.1 of the Code of Virginia, or land use requirements in airport or highway overlay districts, or historic districts created pursuant to § 15.2-2306 of the Code of Virginia, or local flood plain regulations adopted as a condition of participation in the National Flood Insurance Program.
Note: Requirements relating to functional design are contained
in Section 103.10 103.5 of this code.
C. Section 102.2.1 Invalidity of provisions. To the extent that any provisions of this code are in conflict with Chapter 6 (§ 36-97 et seq.) of Title 36 of the Code of Virginia or in conflict with the scope of the USBC, those provisions are considered to be invalid to the extent of such conflict.
D. Section 102.3 Exemptions. The following are exempt from this code:
1. Equipment and wiring used for providing utility, communications, information, cable television, broadcast or radio service in accordance with all of the following conditions:
1.1. The equipment and wiring, are located on either
rights-of-way or property for which the service provider has rights of
occupancy and entry.
1.2. Buildings housing exempt equipment and wiring shall be subject to the USBC.
1.3. The equipment and wiring exempted by this section shall not create an unsafe condition prohibited by the USBC.
2. Support structures owned or controlled by a provider of publicly regulated utility service or its affiliates for the transmission and distribution of electric service in accordance with all of the following conditions:
2.1. The support structures are located on either rights-of-way or property for which the service provider has rights of occupancy and entry.
2.2. The support structures exempted by this section shall not create an unsafe condition prohibited by the USBC.
3. Direct burial poles used to support equipment or wiring providing communications, information or cable television services. The poles exempted by this section shall not create an unsafe condition prohibited by the USBC.
4. Electrical equipment, transmission equipment, and related wiring used for wireless transmission of radio, broadcast, telecommunications, or information service in accordance with all of the following conditions:
4.1. Buildings housing exempt equipment and wiring and structures supporting exempt equipment and wiring shall be subject to the USBC.
4.2. The equipment and wiring exempted by this section shall not create an unsafe condition prohibited by the USBC.
5. Manufacturing, processing, and product handling machines and equipment that do not produce or process hazardous materials regulated by this code, including those portions of conveyor systems used exclusively for the transport of associated materials or products, and all of the following service equipment:
5.1. Electrical equipment connected after the last disconnecting means.
5.2. Plumbing piping and equipment connected after the last shutoff valve or backflow device and before the equipment drain trap.
5.3. Gas piping and equipment connected after the outlet shutoff valve.
Manufacturing and processing machines that produce or process hazardous materials regulated by this code are only required to comply with the code provisions regulating the hazardous materials.
6. Parking lots and sidewalks that are not part of an accessible route.
7. Nonmechanized playground or recreational equipment such as swing sets, sliding boards, climbing bars, jungle gyms, skateboard ramps, and similar equipment where no admission fee is charged for its use or for admittance to areas where the equipment is located.
8. Industrialized buildings subject to the Virginia Industrialized Building Safety Regulations (13VAC5-91) and manufactured homes subject to the Virginia Manufactured Home Safety Regulations (13VAC5-95); except as provided for in Section 427 and in the case of demolition of such industrialized buildings or manufactured homes.
9. Farm buildings and structures, except for a building or a portion of a building located on a farm that is operated as a restaurant as defined in § 35.1-1 of the Code of Virginia and licensed as such by the Virginia Board of Health pursuant to Chapter 2 (§ 35.1-11 et seq.) of Title 35.1 of the Code of Virginia. However, farm buildings and structures lying within a flood plain or in a mudslide-prone area shall be subject to flood-proofing regulations or mudslide regulations, as applicable.
10. Federally owned buildings and structures unless federal law specifically requires a permit from the locality. Underground storage tank installations, modifications and removals shall comply with this code in accordance with federal law.
11. Off-site manufactured intermodal freight containers, moving containers, and storage containers placed on site temporarily or permanently for use as a storage container.
12. Automotive lifts.
13VAC5-63-30. Section 103 Application of code.
A. Section 103.1 General. In accordance with § 36-99 of the Code of Virginia, the USBC shall prescribe building regulations to be complied with in the construction and rehabilitation of buildings and structures, and the equipment therein.
B. Section 103.1.1 Virginia Existing Building Code. Part II of the Virginia Uniform Statewide Building Code, also known as the "Virginia Existing Building Code," or the "VEBC" is applicable to construction and rehabilitation activities in existing buildings and structures, as those terms are defined in the VEBC, except where specifically addressed in the VCC.
C. Section 103.2 When applicable to new construction.
Construction for which a permit application is submitted to the local building
department on or after the effective date of the 2015 2018
edition of the code shall comply with the provisions of this code, except for
permit applications submitted during a one-year period beginning on the
effective date of the 2015 2018 edition of the code. The
applicant for a permit during such one-year period shall be permitted to choose
whether to comply with the provisions of this code or the provisions of the
edition of the code in effect immediately prior to the 2015 2018
edition. This provision shall also apply to subsequent amendments to this code
based on the effective date of such amendments. In addition, when a permit has
been properly issued under a previous edition of this code, this code shall not
require changes to the approved construction documents, design or construction
of such a building or structure, provided the permit has not been suspended or
revoked.
D. Section 103.3 Nonrequired equipment. The following criteria for nonrequired equipment is in accordance with § 36-103 of the Code of Virginia. Building owners may elect to install partial or full fire alarms or other safety equipment that was not required by the edition of the USBC in effect at the time a building was constructed without meeting current requirements of the code, provided the installation does not create a hazardous condition. Permits for installation shall be obtained in accordance with this code. In addition, as a requirement of this code, when such nonrequired equipment is to be installed, the building official shall notify the appropriate fire official or fire chief.
E. Section 103.3.1 Reduction in function or discontinuance of nonrequired fire protection systems. When a nonrequired fire protection system is to be reduced in function or discontinued, it shall be done in such a manner so as not to create a false sense of protection. Generally, in such cases, any features visible from interior areas shall be removed, such as sprinkler heads, smoke detectors or alarm panels or devices, but any wiring or piping hidden within the construction of the building may remain. Approval of the proposed method of reduction or discontinuance shall be obtained from the building official.
F. Section 103.4 Use of certain provisions of referenced codes. The following provisions of the IBC and of other indicated codes or standards are to be considered valid provisions of this code. Where any such provisions have been modified by the state amendments to the IBC, then the modified provisions apply.
1. Special inspection requirements in Chapters 2 - 35.
2. Testing requirements and requirements for the submittal of construction documents in any of the ICC codes referenced in Chapter 35 and in the IRC.
3. Section R301.2 of the IRC authorizing localities to determine climatic and geographic design criteria.
4. Flood load or flood-resistant construction requirements in
the IBC or the IRC, including, but not limited to, any such provisions
pertaining to flood elevation certificates that are located in Chapter 1 of
those codes. Any required flood elevation certificate pursuant to such
provisions shall be prepared by a land surveyor licensed in Virginia or an
RDP a registered design professional (RDP).
5. Section R101.2 of the IRC.
6. Section N1102.1 of the IRC and Sections C402.1.1 and R402.1 of the IECC.
G. Section 103.5 Functional design. The following criteria for
functional design is in accordance with § 36-98 of the Code of Virginia. The
USBC shall not supersede the regulations of other state agencies that require
and govern the functional design and operation of building related activities
not covered by the USBC, including but not limited to (i) public water
supply systems, (ii) waste water treatment and disposal systems, and (iii)
solid waste facilities. Nor shall state agencies be prohibited from requiring,
pursuant to other state law, that buildings and equipment be maintained in
accordance with provisions of this code. In addition, as established by this
code, the building official may refuse to issue a permit until the applicant
has supplied certificates of functional design approval from the appropriate
state agency or agencies. For purposes of coordination, the locality may
require reports to the building official by other departments or agencies
indicating compliance with their regulations applicable to the functional
design of a building or structure as a condition for issuance of a building
permit or certificate of occupancy. Such reports shall be based upon review of
the plans or inspection of the project as determined by the locality. All
enforcement of these conditions shall not be the responsibility of the building
official, but rather the agency imposing the condition.
Note: Identified state agencies with functional design approval are listed in the "Related Laws Package," which is available from DHCD.
H. Section 103.6 Amusement devices and inspections. In accordance with § 36-98.3 of the Code of Virginia, to the extent they are not superseded by the provisions of § 36-98.3 of the Code of Virginia and the VADR, the provisions of the USBC shall apply to amusement devices. In addition, as a requirement of this code, inspections for compliance with the VADR shall be conducted either by local building department personnel or private inspectors provided such persons are certified as amusement device inspectors under the VCS.
I. Section 103.7 State buildings and structures. This section establishes the application of the USBC to state-owned buildings and structures in accordance with § 36-98.1 of the Code of Virginia. The USBC shall be applicable to all state-owned buildings and structures, with the exception that §§ 2.2-1159 through 2.2-1161 of the Code of Virginia shall provide the standards for ready access to and use of state-owned buildings by the physically handicapped.
Any state-owned building or structure or building built on state-owned property for which preliminary plans were prepared or on which construction commenced after the initial effective date of the USBC, shall remain subject to the provisions of the USBC that were in effect at the time such plans were completed or such construction commenced. Subsequent reconstruction, renovation or demolition of such building or structure shall be subject to the pertinent provisions of this code.
Acting through the Division of Engineering and Buildings, the Virginia Department of General Services shall function as the building official for state-owned buildings. The department shall review and approve plans and specifications, grant modifications, and establish such rules and regulations as may be necessary to implement this section. It shall provide for the inspection of state-owned buildings and enforcement of the USBC and standards for access by the physically handicapped by delegating inspection and USBC enforcement duties to the State Fire Marshal's Office, to other appropriate state agencies having needed expertise, and to local building departments, all of which shall provide such assistance within a reasonable time and in the manner requested. State agencies and institutions occupying buildings shall pay to the local building department the same fees as would be paid by a private citizen for the services rendered when such services are requested by the department. The department may alter or overrule any decision of the local building department after having first considered the local building department's report or other rationale given for its decision. When altering or overruling any decision of a local building department, the department shall provide the local building department with a written summary of its reasons for doing so.
Notwithstanding any provision of this code to the contrary, roadway tunnels and bridges owned by the Virginia Department of Transportation shall be exempt from this code. The Virginia Department of General Services shall not have jurisdiction over such roadway tunnels, bridges and other limited access highways; provided, however, that the Department of General Services shall have jurisdiction over any occupied buildings within any Department of Transportation rights-of-way that are subject to this code.
Except as provided in subsection E of § 23.1-1016 of the Code of Virginia, and notwithstanding any provision of this code to the contrary, at the request of a public institution of higher education, the Virginia Department of General Services, as further set forth in this provision, shall authorize that institution of higher education to contract with a building official of the locality in which the construction is taking place to perform any inspection and certifications required for the purpose of complying with this code. The department shall publish administrative procedures that shall be followed in contracting with a building official of the locality. The authority granted to a public institution of higher education under this provision to contract with a building official of the locality shall be subject to the institution meeting the conditions prescribed in subsection A of § 23.1-1002 of the Code of Virginia.
Note: In accordance with § 36-98.1 of the Code of Virginia, roadway tunnels and bridges shall be designed, constructed and operated to comply with fire safety standards based on nationally recognized model codes and standards to be developed by the Virginia Department of Transportation in consultation with the State Fire Marshal. Emergency response planning and activities related to the standards shall be developed by the Department of Transportation and coordinated with the appropriate local officials and emergency service providers. On an annual basis, the Department of Transportation shall provide a report on the maintenance and operability of installed fire protection and detection systems in roadway tunnels and bridges to the State Fire Marshal.
J. Section 103.7.1 Certification of state enforcement personnel. State enforcement personnel shall comply with the applicable requirements of Section 105 for certification.
13VAC5-63-50. Section 105 Local building department.
A. Section 105.1 Appointment of building official. Every local building department shall have a building official as the executive official in charge of the department. The building official shall be appointed in a manner selected by the local governing body. After permanent appointment, the building official shall not be removed from office except for cause after having been afforded a full opportunity to be heard on specific and relevant charges by and before the appointing authority. DHCD shall be notified by the appointing authority within 30 days of the appointment or release of a permanent or acting building official.
Note: Building officials are subject to sanctions in accordance with the VCS.
B. Section 105.1.1 Qualifications of building official. The building official shall have at least five years of building experience as a licensed professional engineer or architect, building, fire or trade inspector, contractor, housing inspector or superintendent of building, fire or trade construction or at least five years of building experience after obtaining a degree in architecture or engineering, with at least three years in responsible charge of work. Any combination of education and experience that would confer equivalent knowledge and ability shall be deemed to satisfy this requirement. The building official shall have general knowledge of sound engineering practice in respect to the design and construction of structures, the basic principles of fire prevention, the accepted requirements for means of egress and the installation of elevators and other service equipment necessary for the health, safety and general welfare of the occupants and the public. The local governing body may establish additional qualification requirements.
C. Section 105.1.2 Certification of building official. An acting or permanent building official shall be certified as a building official in accordance with the VCS within one year after being appointed as acting or permanent building official.
Exception: A building official in place prior to April 1, 1983, shall not be required to meet the certification requirements in this section while continuing to serve in the same capacity in the same locality.
D. Section 105.1.3 Noncertified building official. Except for a building official exempt from certification under the exception to Section 105.1.2, any acting or permanent building official who is not certified as a building official in accordance with the VCS shall attend the core module of the Virginia Building Code Academy or an equivalent course in an individual or regional code academy accredited by DHCD within 180 days of appointment. This requirement is in addition to meeting the certification requirement in Section 105.1.2.
Note: Continuing education and periodic training requirements for DHCD certifications are set out in the VCS.
E. Section 105.2 Technical assistants. The building official, subject to any limitations imposed by the locality, shall be permitted to utilize technical assistants to assist the building official in the enforcement of the USBC. DHCD shall be notified by the building official within 60 days of the employment of, contracting with or termination of all technical assistants.
Note: Technical assistants are subject to sanctions in accordance with the VCS.
F. Section 105.2.1 Qualifications of technical assistants. A technical assistant shall have at least three years of experience and general knowledge in at least one of the following areas: building construction; building construction conceptual and administrative processes; building, fire or housing inspections; plumbing, electrical or mechanical trades; or fire protection, elevator or property maintenance work. Any combination of education and experience that would confer equivalent knowledge and ability, including high school technical training programs or college engineering, architecture, or construction degree programs, shall be deemed to satisfy this requirement. The locality may establish additional qualification requirements.
G. Section 105.2.2 Certification of technical assistants. A technical assistant shall be certified in the appropriate subject area within 18 months after becoming a technical assistant. When required by local policy to have two or more certifications, a technical assistant shall obtain the additional certifications within three years from the date of such requirement.
Exceptions:
1. A technical assistant in place prior to March 1, 1988, shall not be required to meet the certification requirements in this section while continuing to serve in the same capacity in the same locality.
2. A permit technician in place prior to the effective date of the 2015 edition of the code shall not be required to meet the certification requirements in this section while continuing to serve in the same capacity in the same locality.
Note: Continuing education and periodic training requirements for DHCD certifications are set out in the VCS.
H. Section 105.3 Conflict of interest. The standards of conduct for building officials and technical assistants shall be in accordance with the provisions of the State and Local Government Conflict of Interests Act, Chapter 31 (§ 2.2-3100 et seq.) of Title 2.2 of the Code of Virginia.
I. Section 105.4 Records. The local building department shall retain a record of applications received, permits, certificates, notices and orders issued, fees collected and reports of inspection in accordance with The Library of Virginia's General Schedule Number Six.
13VAC5-63-60. Section 106 Powers and duties of the building official.
A. Section 106.1 Powers and duties, generally. The building official shall enforce this code as set out herein and as interpreted by the State Review Board.
B. Section 106.2 Delegation of authority. The building official may delegate powers and duties except where such authority is limited by the local government. However, such limitations of authority by the local government are not applicable to the third-party inspector policy required by Section 113.7.1 nor shall such limitations of authority by the local government have the effect of altering the provisions of this code or creating building regulations. When such delegations are made, the building official shall be responsible for assuring that they are carried out in accordance with the provisions of this code.
C. Section 106.3 Issuance of modifications. Upon written application by an owner or an owner's agent, the building official may approve a modification of any provision of the USBC provided the spirit and functional intent of the code are observed and public health, welfare and safety are assured. The decision of the building official concerning a modification shall be made in writing and the application for a modification and the decision of the building official concerning such modification shall be retained in the permanent records of the local building department.
Note: The USBC references nationally recognized model codes and standards. Future amendments to such codes and standards are not automatically included in the USBC; however the building official should give them due consideration in deciding whether to approve a modification.
D. Section 106.3.1 Substantiation of modification. The building
official may require or may consider a statement from an RDP a
registered design professional (RDP) or other person competent in the
subject area of the application as to the equivalency of the proposed
modification. In addition, the building official may require the application to
include construction documents sealed by an RDP. The building official may
also consider nationally recognized guidelines in deciding whether to approve a
modification.
E. Section 106.3.2 Use of performance code. Compliance with the provisions of a nationally recognized performance code when approved as a modification shall be considered to constitute compliance with this code. All documents submitted as part of such consideration shall be retained in the permanent records of the local building department.
13VAC5-63-80. Section 108 Application for permit.
A. Section 108.1 When applications are required. Application for a permit shall be made to the building official and a permit shall be obtained prior to the commencement of any of the following activities, except that applications for emergency construction, alterations or equipment replacement shall be submitted by the end of the first working day that follows the day such work commences. In addition, the building official may authorize work to commence pending the receipt of an application or the issuance of a permit.
1. Construction or demolition of a building or structure. Installations or alterations involving (i) the removal or addition of any wall, partition or portion thereof, (ii) any structural component, (iii) the repair or replacement of any required component of a fire or smoke rated assembly, (iv) the alteration of any required means of egress system, including the addition of emergency supplemental hardware, (v) water supply and distribution system, sanitary drainage system or vent system, (vi) electric wiring, (vii) fire protection system, mechanical systems, or fuel supply systems, or (viii) any equipment regulated by the USBC.
2. For change of occupancy, application for a permit shall be made when a new certificate of occupancy is required by the VEBC.
3. Movement of a lot line that increases the hazard to or decreases the level of safety of an existing building or structure in comparison to the building code under which such building or structure was constructed.
4. Removal or disturbing of any asbestos containing materials during the construction or demolition of a building or structure, including additions.
B. Section 108.2 Exemptions from application for permit. Notwithstanding the requirements of Section 108.1, application for a permit and any related inspections shall not be required for the following; however, this section shall not be construed to exempt such activities from other applicable requirements of this code. In addition, when an owner or an owner's agent requests that a permit be issued for any of the following, then a permit shall be issued and any related inspections shall be required.
1. Installation of wiring and equipment that (i) operates at less than 50 volts, (ii) is for broadband communications systems, (iii) is exempt under Section 102.3(1) or 102.3(4), or (iv) is for monitoring or automation systems in dwelling units, except when any such installations are located in a plenum, penetrate fire rated or smoke protected construction or are a component of any of the following:
1.1. Fire alarm system.
1.2. Fire detection system.
1.3. Fire suppression system.
1.4. Smoke control system.
1.5. Fire protection supervisory system.
1.6. Elevator fire safety control system.
1.7. Access or egress control system or delayed egress locking or latching system.
1.8. Fire damper.
1.9. Door control system.
2. One story detached structures used as tool and storage sheds, playhouses or similar uses, provided the building area does not exceed 256 square feet (23.78 m2) and the structures are not classified as a Group F-1 or H occupancy.
3. Detached prefabricated buildings housing the equipment of a publicly regulated utility service, provided the floor area does not exceed 150 square feet (14 m2).
4. Tents or air-supported structures, or both, that cover an area of 900 square feet (84 m2) or less, including within that area all connecting areas or spaces with a common means of egress or entrance, provided such tents or structures have an occupant load of 50 or less persons.
5. Fences of any height unless required for pedestrian safety as provided for by Section 3306, or used for the barrier for a swimming pool.
6. Concrete or masonry walls, provided such walls do not exceed six feet in height above the finished grade. Ornamental column caps shall not be considered to contribute to the height of the wall and shall be permitted to extend above the six feet height measurement.
7. Retaining walls supporting less than three feet of unbalanced fill that are not constructed for the purpose of impounding Class I, II or III-A liquids or supporting a surcharge other than ordinary unbalanced fill.
8. Swimming pools that have a surface area not greater than 150
square feet (13.95 m2), do not exceed 5,000 gallons (19 000 (19,000
L) and are less than 24 inches (610 mm) deep.
9. Signs under the conditions in Section H101.2 of Appendix H.
10. Replacement of above-ground existing LP-gas containers of the same capacity in the same location and associated regulators when installed by the serving gas supplier.
11. Flagpoles 30 feet (9144 mm) or less in height.
12. Temporary ramps serving dwelling units in Group Groups
R-3 and R-5 occupancies where the height of the entrance served by the ramp is
no more than 30 inches (762 mm) above grade.
13. Construction work deemed by the building official to be minor and ordinary and which does not adversely affect public health or general safety.
14. Ordinary repairs that include the following:
14.1. Replacement of windows and doors with windows and doors of similar operation and opening dimensions that do not require changes to the existing framed opening and that are not required to be fire rated in Group R-2 where serving a single dwelling unit and in Groups R-3, R-4 and R-5.
14.2. Replacement of plumbing fixtures and well pumps in all groups without alteration of the water supply and distribution systems, sanitary drainage systems or vent systems.
14.3. Replacement of general use snap switches, dimmer and control switches, 125 volt-15 or 20 ampere receptacles, luminaires (lighting fixtures) and ceiling (paddle) fans in Group R-2 where serving a single dwelling unit and in Groups R-3, R-4 and R-5.
14.4. Replacement of mechanical appliances provided such equipment is not fueled by gas or oil in Group R-2 where serving a single-family dwelling and in Groups R-3, R-4 and R-5.
14.5. Replacement of an unlimited amount of roof covering or
siding in Groups Group R-3, R-4 or R-5 provided the building or
structure is not in an area where the nominal design wind speed is greater than
100 miles per hour (44.7 meters per second) and replacement of 100 square feet
(9.29 m2) or less of roof covering in all groups and all wind zones.
14.6. Replacement of 256 square feet 23.78 m2
(23.78 m2) or less of roof decking in Groups Group
R-3, R-4 or R-5 unless the decking to be replaced was required at the time of
original construction to be fire-retardant-treated or protected in some other
way to form a fire-rated wall termination.
14.7. Installation or replacement of floor finishes in all occupancies.
14.8. Replacement of Class C interior wall or ceiling finishes installed in Groups A, E and I and replacement of all classes of interior wall or ceiling finishes in other groups.
14.9. Installation or replacement of cabinetry or trim.
14.10. Application of paint or wallpaper.
14.11. Other repair work deemed by the building official to be minor and ordinary which does not adversely affect public health or general safety.
15. Crypts, mausoleums, and columbaria structures not exceeding
1500 1,500 square feet (139.35 m2) in area if the
building or structure is not for occupancy and used solely for the interment of
human or animal remains and is not subject to special inspections.
16. Billboard safety upgrades to add or replace steel catwalks, steel ladders, or steel safety cable.
Exceptions:
1. Application for a permit may be required by the building official for the installation of replacement siding, roofing and windows in buildings within a historic district designated by a locality pursuant to § 15.2-2306 of the Code of Virginia.
2. Application for a permit may be required by the building official for any items exempted in this section that are located in a special flood hazard area.
C. Section 108.3 Applicant information, processing by mail. Application for a permit shall be made by the owner or lessee of the relevant property or the agent of either or by the RDP, contractor or subcontractor associated with the work or any of their agents. The full name and address of the owner, lessee and applicant shall be provided in the application. If the owner or lessee is a corporate body, when and to the extent determined necessary by the building official, the full name and address of the responsible officers shall also be provided.
A permit application may be submitted by mail and such permit applications shall be processed by mail, unless the permit applicant voluntarily chooses otherwise. In no case shall an applicant be required to appear in person.
The building official may accept applications for a permit through electronic submissions provided the information required by this section is obtained.
D. Section 108.4 Prerequisites to obtaining permit. In
accordance with § 54.1-1111 of the Code of Virginia, any person applying to the
building department for the construction, removal or improvement of any
structure shall furnish prior to the issuance of the permit either (i)
satisfactory proof to the building official that he is duly licensed or
certified under the terms or Chapter 11 (§ 54.1-1000 et seq.) of Title
54.1 of the Code of Virginia to carry out or superintend the same or (ii) file
a written statement, supported by an affidavit, that he is not subject
to licensure or certification as a contractor or subcontractor pursuant to
Chapter 11 of Title 54.1 of the Code of Virginia. The applicant shall also
furnish satisfactory proof that the taxes or license fees required by any
county, city, or town have been paid so as to be qualified to bid upon or
contract for the work for which the permit has been applied.
E. Section 108.5 Mechanics' lien agent designation. In accordance with § 36-98.01 of the Code of Virginia, a building permit issued for any one-family or two-family residential dwelling shall at the time of issuance contain, at the request of the applicant, the name, mailing address, and telephone number of the mechanics' lien agent as defined in § 43-1 of the Code of Virginia. If the designation of a mechanics' lien agent is not so requested by the applicant, the building permit shall at the time of issuance state that none has been designated with the words "None Designated."
Note: In accordance with § 43-4.01A of the Code of Virginia, a permit may be amended after it has been initially issued to name a mechanics' lien agent or a new mechanics' lien agent.
F. Section 108.6 Application form, description of work. The
application for a permit shall be submitted on a form or forms supplied
by the local building department. The application shall contain a general
description and location of the proposed work and such other information as
determined necessary by the building official.
G. Section 108.7 Amendments to application. An application for a permit may be amended at any time prior to the completion of the work governed by the permit. Additional construction documents or other records may also be submitted in a like manner. All such submittals shall have the same effect as if filed with the original application for a permit and shall be retained in a like manner as the original filings.
H. Section 108.8 Time limitation of application. An application for a permit for any proposed work shall be deemed to have been abandoned six months after the date of filing unless such application has been pursued in good faith or a permit has been issued, except that the building official is authorized to grant one or more extensions of time if a justifiable cause is demonstrated.
13VAC5-63-100. Section 110 Permits.
A. Section 110.1 Approval and issuance of permits. The building official shall examine or cause to be examined all applications for permits or amendments to such applications within a reasonable time after filing. If the applications or amendments do not comply with the provisions of this code or all pertinent laws and ordinances, the permit shall not be issued and the permit applicant shall be notified in writing of the reasons for not issuing the permit. If the application complies with the applicable requirements of this code, a permit shall be issued as soon as practicable. The issuance of permits shall not be delayed in an effort to control the pace of construction of new detached one- or two-family dwellings.
B. Section 110.1.1 Consultation and notification. Prior to approval of emergency supplemental hardware, the building code official shall consult with the local fire code official, or state fire code official if no local fire code official exists, and head of the local law-enforcement agency. The local fire code official; the state fire code official; and the local fire, EMS, and law-enforcement first responders shall be notified of such approval. After approval of such emergency supplemental hardware by the building code official.
C. Section 110.2 Types of permits. Separate or combined permits may be required for different areas of construction such as building construction, plumbing, electrical, and mechanical work, or for special construction as determined appropriate by the locality. In addition, permits for two or more buildings or structures on the same lot may be combined. Annual permits may also be issued for any construction regulated by this code. The annual permit holder shall maintain a detailed record of all alterations made under the annual permit. Such record shall be available to the building official and shall be submitted to the local building department if requested by the building official.
C. D. Section 110.3 Asbestos inspection in
buildings to be renovated or demolished; exceptions. In accordance with §
36-99.7 of the Code of Virginia, the local building department shall not issue
a building permit allowing a building for which an initial building permit was
issued before January 1, 1985, to be renovated or demolished until the local
building department receives certification from the owner or his agent that the
affected portions of the building have been inspected for the presence of
asbestos by an individual licensed to perform such inspections pursuant to §
54.1-503 of the Code of Virginia and that no asbestos-containing materials were
found or that appropriate response actions will be undertaken in accordance
with the requirements of the Clean Air Act National Emission Standard for the Hazardous
Air Pollutant (NESHAPS) (40 CFR Part 61, Subpart M), and the asbestos worker
protection requirements established by the U.S. Occupational Safety and Health
Administration for construction workers (29 CFR 1926.1101). Local educational
agencies that are subject to the requirements established by the Environmental
Protection Agency under the Asbestos Hazard Emergency Response Act (AHERA)
shall also certify compliance with 40 CFR Part 763 and subsequent amendments
thereto.
To meet the inspection requirements above, except with respect to schools, asbestos inspection of renovation projects consisting only of repair or replacement of roofing, floorcovering, or siding materials may be satisfied by a statement that the materials to be repaired or replaced are assumed to contain friable asbestos and that asbestos installation, removal, or encapsulation will be accomplished by a licensed asbestos contractor.
The provisions of this section shall not apply to single-family dwellings or residential housing with four or fewer units unless the renovation or demolition of such buildings is for commercial or public development purposes. The provisions of this section shall not apply if the combined amount of regulated asbestos-containing material involved in the renovation or demolition is less than 260 linear feet on pipes or less than 160 square feet on other facility components or less than 35 cubic feet off facility components where the length or area could not be measured previously.
An abatement area shall not be reoccupied until the building official receives certification from the owner that the response actions have been completed and final clearances have been measured. The final clearance levels for reoccupancy of the abatement area shall be 0.01 or fewer asbestos fibers per cubic centimeter if determined by Phase Contrast Microscopy analysis (PCM) or 70 or fewer structures per square millimeter if determined by Transmission Electron Microscopy analysis (TEM).
D. E. Section 110.4 Fire apparatus access road
requirements. The permit applicant shall be informed of any requirements for
providing or maintaining fire apparatus access roads prior to the issuance of a
building permit.
E. F. Section 110.5 Signature on and posting
Posting of permits; limitation of approval. The signature of the
building official or authorized representative shall be on or affixed to every
permit. A copy of the permit shall be posted on the construction site for
public inspection until the work is completed. Such posting shall include the
street or lot number, if one has been assigned, to be readable from a
public way. In addition, each building or structure to which a street number
has been assigned shall, upon completion, have the number displayed so as to be
readable from the public way.
A permit shall be considered authority to proceed with construction in accordance with this code, the approved construction documents, the permit application and any approved amendments or modifications. The permit shall not be construed to otherwise authorize the omission or amendment of any provision of this code.
F. G. Section 110.6 Abandonment of work. A
building official shall be permitted to revoke a permit if work on the site
authorized by the permit is not commenced within six months after issuance of
the permit, or if the authorized work on the site is suspended or abandoned for
a period of six months after the permit is issued; however, permits issued for
plumbing, electrical and mechanical work shall not be revoked if the building
permit is still in effect. It shall be the responsibility of the permit
applicant to prove to the building official that authorized work includes
substantive progress, characterized by approved inspections as specified in
Section 113.3 of at least one inspection within a period of six months or other
evidence that would indicate substantial work has been performed. Upon written
request, the building official may grant one or more extensions of time, not to
exceed one year per extension.
G. H. Section 110.7 Single-family dwelling
permits. The building official shall be permitted to require a three year time
limit to complete construction of new detached single-family dwellings,
additions to detached single-family dwellings and residential accessory
structures. The time limit shall begin from the issuance date of the permit.
The building official may grant extensions of time if the applicant can
demonstrate substantive progress, characterized by approved inspections as
specified in Section 113.3 of at least one inspection within a period of six
months or other evidence that would indicate substantial work has been
performed.
H. I. Section 110.8 Revocation of a permit. The
building official may revoke a permit or approval issued under this code in the
case of any false statement, misrepresentation of fact, abandonment of work,
failure to complete construction as required by Section 110.7, noncompliance
with provisions of this code and pertinent laws and ordinances, or
incorrect information supplied by the applicant in the application or
construction documents on which the permit or approval was based.
13VAC5-63-120. Section 112 Workmanship, materials and equipment.
A. Section 112.1 General. It shall be the duty of any person performing work covered by this code to comply with all applicable provisions of this code and to perform and complete such work so as to secure the results intended by the USBC. Damage to regulated building components caused by violations of this code or by the use of faulty materials or installations shall be considered as separate violations of this code and shall be subject to the applicable provisions of Section 115.
B. Section 112.2 Alternative methods or materials. In accordance with § 36-99 of the Code of Virginia, where practical, the provisions of this code are stated in terms of required level of performance so as to facilitate the prompt acceptance of new building materials and methods. When generally recognized standards of performance are not available, this section and other applicable requirements of this code provide for acceptance of materials and methods whose performance is substantially equal in safety to those specified on the basis of reliable test and evaluation data presented by the proponent. In addition, as a requirement of this code, the building official shall require that sufficient technical data be submitted to substantiate the proposed use of any material, equipment, device, assembly or method of construction. The building official may consider nationally recognized guidelines in making a determination.
C. Section 112.3 Documentation and approval. In determining whether any material, equipment, device, assembly or method of construction complies with this code, the building official shall approve items listed by nationally recognized testing laboratories, when such items are listed for the intended use and application, and in addition, may consider the recommendations of RDPs. Approval shall be issued when the building official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code and that the material, equipment, device, assembly or method of construction offered is, for the purpose intended, at least the equivalent of that prescribed by the code. Such approval is subject to all applicable requirements of this code and the material, equipment, device, assembly or method of construction shall be installed in accordance with the conditions of the approval and their listings. In addition, the building official may revoke such approval whenever it is discovered that such approval was issued in error or on the basis of incorrect information, or where there are repeated violations of the USBC.
D. Section 112.3.1 Conditions of listings. Where conflicts between this code and conditions of the listing or the manufacturer's installation instructions occur, the provisions of this code shall apply.
Exception: Where a code provision is less restrictive than the conditions of the listing of the equipment or appliance or the manufacturer's installation instructions, the conditions of the listing and the manufacturer's installation instructions shall apply.
E. Section 112.4 Used material and equipment. Used materials, equipment and devices may be approved provided they have been reconditioned, tested or examined and found to be in good and proper working condition and acceptable for use by the building official.
F. Section 112.5 Defective materials. Notwithstanding any provision of this code to the contrary, where action has been taken and completed by the BHCD under subsection D of § 36-99 of the Code of Virginia establishing new performance standards for identified defective materials, this section sets forth the new performance standards addressing the prospective use of such materials and establishes remediation standards for the removal of any defective materials already installed, which when complied with enables the building official to certify that the building is deemed to comply with the edition of the USBC under which the building was originally constructed with respect to the remediation of the defective materials.
G. Section 112.5.1 Drywall, performance standard. All newly installed gypsum wallboard shall not be defective drywall as defined in Section 112.5.1.1.1.
H. Section 112.5.1.1 Remediation standards. The following provisions establish remediation standards where defective drywall was installed in buildings.
I. Section 112.5.1.1.1 Definition. For the purposes of this section the term "defective drywall" means gypsum wallboard that (i) contains elemental sulfur exceeding 10 parts per million that when exposed to heat or humidity, or both, emits volatile sulfur compounds in quantities that cause observable corrosion on electrical wiring, plumbing pipes, fuel gas lines, or HVAC equipment, or any components of the foregoing or (ii) has been designated by the U.S. Consumer Product Safety Commission as a product with a product defect that constitutes a substantial product hazard within the meaning of § 15(a)(2) of the Consumer Product Safety Act (15 USC § 2064(a)(2)).
J. Section 112.5.1.1.2 Permit. Application for a permit shall be made to the building official, and a permit shall be obtained prior to the commencement of remediation work undertaken to remove defective drywall from a building and for the removal, replacement, or repair of corroded electrical, plumbing, mechanical, or fuel gas equipment and components.
K. Section 112.5.1.1.3 Protocol. Where remediation of defective drywall is undertaken, the following standards shall be met. The building official shall be permitted to consider and approve modifications to these standards in accordance with Section 106.3.
L. Section 112.5.1.1.3.1 Drywall. Drywall in the building, whether defective or nondefective, shall be removed and discarded, including fasteners that held any defective drywall to prevent small pieces of drywall from remaining under fasteners.
Exceptions:
1. Nondefective drywall not subject to the corrosive effects of any defective drywall shall be permitted to be left in place in buildings where the defective drywall is limited to a defined room or space or isolated from the rest of the building and the defective drywall can be positively identified. If the room or space containing the defective drywall also contains any nondefective drywall, the nondefective drywall in that room or space shall also be removed.
2. In multifamily buildings where defective drywall was not used in the firewalls between units and there are no affected building systems behind the firewalls, the firewalls shall be permitted to be left in place.
M. Section 112.5.1.1.3.2 Insulation and other building components. Insulation in walls and ceilings shall be removed and discarded. Carpet and vinyl flooring shall be removed and discarded. Woodwork, trim, cabinets, and tile or wood floors may be left in place or may be reused.
Exceptions:
1. Closed-cell foam insulation is permitted to be left in place if testing for off-gassing from defective drywall is negative, unless its removal is required to gain access.
2. Insulation, carpet, or vinyl flooring in areas not exposed to defective drywall or to the effects of defective drywall, may be left in place or reused.
N. Section 112.5.1.1.3.3 Electrical wiring, equipment, devices, and components. All electrical wiring regulated by this code shall be permitted to be left in place, but removal or cleaning of exposed ends of the wiring to reveal clean or uncorroded surfaces is required. All electrical equipment, devices, and components of the electrical system of the building regulated by this code shall be removed and discarded. This shall include all smoke detectors.
Exceptions:
1. Electrical equipment, devices, or components in areas not exposed to the corrosive effects of defective drywall shall be permitted to be left in place or reused. Electrical equipment, devices, or components in areas exposed to the corrosive effects of defective drywall shall be cleaned, repaired, or replaced.
2. Cord and plug connected appliances are not subject to this code and, therefore, cannot be required to be removed or replaced.
Note: All low-voltage wiring associated with security systems, door bells, elevator controls, and other such components shall be removed and replaced or repaired.
O. Section 112.5.1.1.3.4 Plumbing and fuel gas piping, fittings, fixtures, and equipment. All copper fuel gas piping and all equipment utilizing fuel gas with copper, silver, or aluminum components shall be removed and discarded. All copper plumbing pipes and fittings shall be removed and discarded. Plumbing fixtures with copper, silver, or aluminum components shall be removed and discarded.
Exception: Plumbing or fuel gas piping, fittings, fixtures, equipment, or components in areas not exposed to the corrosive effects of defective drywall shall be permitted to be left in place or reused.
P. Section 112.5.1.1.3.5 Mechanical systems. All heating,
air-conditioning, and ventilation system components, including but not
limited to ductwork, air-handling units, furnaces, heat pumps, refrigerant lines,
and thermostats and associated wiring, shall be removed and discarded.
Exception: Mechanical system components in areas not exposed to the corrosive effects of defective drywall shall be permitted to be left in place or reused.
Q. Section 112.5.1.1.3.6 Cleaning. Following the removal of all materials and components in accordance with Sections 112.5.1.1.3.1 through 112.5.1.1.3.5, the building shall be thoroughly cleaned to remove any particulate matter and dust.
R. Section 112.5.1.1.3.7 Airing out. Following cleaning in accordance with Section 112.5.1.1.3.6, the building shall be thoroughly aired out with the use of open windows and doors and fans.
S. Section 112.5.1.1.3.8 Pre-rebuilding clearance testing. Following the steps outlined above for removal of all materials and components, cleaning and airing out, a pre-rebuilding clearance test shall be conducted with the use of copper or silver coupons and the methodology outlined in the April 2, 2010, joint report by the Consumer Products Safety Commission and the Department of Housing and Urban Development "Interim Remediation Guidance for Homes with Corrosion from Problem Drywall" or with the use of a copper probe and dosimeter. The clearance testing shall confirm that all airborne compounds associated with the defective drywall are at usual environmental background levels. The clearance testing report, certifying compliance, shall be submitted to the building official.
Notes:
1. Where the building is served by a well and prior to conducting clearance tests, all outlets in piping served by the well should be capped or otherwise plugged to prevent contamination of the air sample.
2. To prevent siphoning and evaporation of the trap seals, fixtures should be capped or otherwise plugged to prevent sewer gases from contaminating the air sample.
T. Section 112.5.1.1.3.9 Testing agencies and personnel. Agencies and personnel performing pre-rebuilding or post-rebuilding clearance testing shall be independent of those responsible for all other remediation work and the agencies and personnel shall be appropriately certified or accredited by the Council of Engineering and Scientific Specialty Boards, the American Indoor Air Quality Council, or the World Safety Organization.
Exception: Testing agencies and personnel shall be accepted if certified by an RDP or if the agency employs an RDP to be in responsible charge of the work.
U. Section 112.5.1.1.3.10 Rebuilding standards. The rebuilding of the building shall comply with the edition of the USBC that was in effect when the building was originally built.
V. Section 112.5.1.1.3.11 Post-rebuilding clearance testing. A post-rebuilding clearance test prior to reoccupancy of the building or structure shall be conducted with the use of copper or silver coupons and the methodology outlined in the April 2, 2010, joint report by the U.S. Consumer Products Safety Commission and by the Department of Housing and Urban Development "Interim Remediation Guidance for Homes with Corrosion from Problem Drywall" or with the use of a copper probe and dosimeter. The clearance testing shall confirm that all airborne compounds associated with the defective drywall are at usual environmental background levels. The clearance testing report certifying compliance shall be submitted to the building official.
Notes:
1. Where the building is served by a well and prior to conducting clearance tests, all outlets in piping served by the well should be capped or otherwise plugged to prevent contamination of the air sample.
2. To prevent siphoning and evaporation of the trap seals, fixtures should be capped or otherwise plugged to prevent sewer gases from contaminating the air sample.
W. Section 112.5.1.1.4 Final approval by the building official. Once remediation has been completed in accordance with this section, a certificate or letter of approval shall be issued by the building official. The certificate or letter shall state that the remediation and rebuilding is deemed to comply with this code.
X. Section 112.5.1.1.4.1 Approval of remediation occurring prior to these standards. The building official shall issue a certificate or letter of approval for remediation of defective drywall that occurred prior to the effective date of these standards provided post-rebuilding clearance testing has been performed in accordance with Section 112.5.1.1.3.11, by agencies and personnel complying with Section 112.5.1.1.3.9, and the clearance testing confirms that all airborne compounds associated with the defective drywall are at usual environmental background levels. The clearance testing report certifying compliance shall be submitted to the building official.
13VAC5-63-130. Section 113 Inspections.
A. Section 113.1 General. In accordance with § 36-105 of the Code of Virginia, any building or structure may be inspected at any time before completion, and shall not be deemed in compliance until approved by the inspecting authority. Where the construction cost is less than $2,500, however, the inspection may, in the discretion of the inspecting authority, be waived. The building official shall coordinate all reports of inspections for compliance with the USBC, with inspections of fire and health officials delegated such authority, prior to the issuance of an occupancy permit.
B. Section 113.1.1 Equipment required. Any ladder, scaffolding or test equipment necessary to conduct or witness a requested inspection shall be provided by the permit holder.
C. Section 113.1.2 Duty to notify. When construction reaches a stage of completion that requires an inspection, the permit holder shall notify the building official.
D. Section 113.1.3 Duty to inspect. Except as provided for in Section 113.7, the building official shall perform the requested inspection in accordance with Section 113.6 when notified in accordance with Section 113.1.2.
E. Section 113.2 Prerequisites. The building official may conduct a site inspection prior to issuing a permit. When conducting inspections pursuant to this code, all personnel shall carry proper credentials.
F. Section 113.3 Minimum inspections. The following minimum inspections shall be conducted by the building official when applicable to the construction or permit:
1. Inspection of footing excavations and reinforcement material for concrete footings prior to the placement of concrete.
2. Inspection of foundation systems during phases of construction necessary to assure compliance with this code.
3. Inspection of preparatory work prior to the placement of concrete.
4. Inspection of structural members and fasteners prior to concealment.
5. Inspection of electrical, mechanical and plumbing materials, equipment and systems prior to concealment.
6. Inspection of energy conservation material prior to concealment.
7. Final inspection.
G. 113.3.1 Equipment changes. Upon the replacement or new installation of any fuel-burning appliances or equipment in existing Group R-5 occupancies, an inspection or inspections shall be conducted to ensure that the connected vent or chimney systems comply with the following:
1. Vent or chimney systems are sized in accordance with the IRC.
2. Vent or chimney systems are clean, free of any obstruction or blockages, defects, or deterioration, and are in operable condition. Where not inspected by the local building department, persons performing such changes or installations shall certify to the building official that the requirements of Items 1 and 2 of this section are met.
H. Section 113.4 Additional inspections. The building official may designate additional inspections and tests to be conducted during the construction of a building or structure and shall so notify the permit holder.
I. Section 113.5 In-plant and factory inspections. When required by the provisions of this code, materials, equipment or assemblies shall be inspected at the point of manufacture or fabrication. The building official shall require the submittal of an evaluation report of such materials, equipment or assemblies. The evaluation report shall indicate the complete details of the assembly including a description of the assembly and its components, and describe the basis upon which the assembly is being evaluated. In addition, test results and other data as necessary for the building official to determine conformance with the USBC shall be submitted. For factory inspections, an identifying label or stamp permanently affixed to materials, equipment or assemblies indicating that a factory inspection has been made shall be acceptable instead of a written inspection report, provided the intent or meaning of such identifying label or stamp is properly substantiated.
J. Section 113.6 Approval or notice of defective work. The building official shall either approve the work in writing or give written notice of defective work to the permit holder. Upon request of the permit holder, the notice shall reference the USBC section that serves as the basis for the defects and such defects shall be corrected and reinspected before any work proceeds that would conceal such defects. A record of all reports of inspections, tests, examinations, discrepancies and approvals issued shall be maintained by the building official and shall be communicated promptly in writing to the permit holder. Approval issued under this section may be revoked whenever it is discovered that such approval was issued in error or on the basis of incorrect information, or where there are repeated violations of the USBC. Notices issued pursuant to this section shall be permitted to be communicated electronically, provided the notice is reasonably calculated to get to the permit holder.
K. Section 113.7 Approved inspection agencies. The building official may accept reports of inspections and tests from individuals or inspection agencies approved in accordance with the building official's written policy required by Section 113.7.1. The individual or inspection agency shall meet the qualifications and reliability requirements established by the written policy. Under circumstances where the building official is unable to make the inspection or test required by Section 113.3 or 113.4 within two working days of a request or an agreed upon date or if authorized for other circumstances in the building official's written policy, the building official shall accept reports for review. The building official shall approve the report from such approved individuals or agencies unless there is cause to reject it. Failure to approve a report shall be in writing within two working days of receiving it stating the reason for the rejection. Reports of inspections conducted by approved third-party inspectors or agencies shall be in writing, shall indicate if compliance with the applicable provisions of the USBC have been met and shall be certified by the individual inspector or by the responsible officer when the report is from an agency. Reports of inspections conducted for the purpose of verifying compliance with the requirements of the USBC for elevators, escalators, and related conveyances shall include the name and certification number of the elevator mechanic performing the tests witnessed by the third-party inspector or agency.
Exception: The licensed mechanical contractor installing the mechanical system shall be permitted to perform duct tests required by Section R403.3.3 of the IECC or Section N1103.3.3 of the IRC. The contractor shall have been trained on the equipment used to perform the test.
Note: Photographs, videotapes or other sources of pertinent data or information may be considered as constituting such reports and tests.
L. Section 113.7.1 Third-party inspectors. Each building official charged with the enforcement of the USBC shall have a written policy establishing the minimum acceptable qualifications for third-party inspectors. The policy shall include the format and time frame required for submission of reports, any prequalification or preapproval requirements before conducting a third-party inspection and any other requirements and procedures established by the building official.
M. Section 113.7.2 Qualifications. In determining third-party inspector qualifications, the building official may consider such items as DHCD inspector certification, other state or national certifications, state professional registrations, related experience, education and any other factors that would demonstrate competency and reliability to conduct inspections.
N. Section 113.8 Final inspection. Upon completion of a
building or structure and before the issuance of a certificate of occupancy
construction for which a permit was issued, a final inspection shall be
conducted to ensure that any defective work has been corrected and that all work
complies with the USBC and has been approved, including any work associated
with modifications under Section 106.3. The building official shall be
permitted to require the electrical service to a building or structure to be
energized prior to conducting the final inspection. The approval Approval
of a the final inspection shall be permitted to serve as the
new certificate of occupancy required by Section 116.1 in the case of additions
or alterations to existing buildings or structures that already have a certificate
of indicates that all work associated with the permit complies with this
code and the permit is complete. Prior to occupancy or change of
occupancy of a building or structure, a certificate of occupancy shall be
issued in accordance with Section 116.
13VAC5-63-150. Section 115 Violations.
A. Section 115.1 Violation a misdemeanor; civil penalty. In accordance with § 36-106 of the Code of Virginia, it shall be unlawful for any owner or any other person, firm or corporation, on or after the effective date of any code provisions, to violate any such provisions. Any locality may adopt an ordinance that establishes a uniform schedule of civil penalties for violations of specified provisions of the code that are not abated or remedied promptly after receipt of a notice of violation from the local enforcement officer.
Note: See the full text of § 36-106 of the Code of Virginia for additional requirements and criteria pertaining to legal action relative to violations of the code.
B. Section 115.2 Notice of violation. The building official
shall issue a written notice of violation to the responsible party permit
holder if any violations of this code or any directives or orders of the
building official have not been corrected or complied with in within
a reasonable time. The building official may also issue a notice of
violation to other persons found to be responsible in addition to the permit
holder. If the violations, directives, or orders involve work without a permit,
the notice of violation shall be issued to the responsible party. The
notice shall reference the code section upon which the notice is based and
direct the correction of the violation or the compliance with such directive or
order and specify a reasonable time period within which the corrections or
compliance must occur. The notice shall be issued by either delivering a copy to
the responsible party by mail to the last known address of the permit
holder or responsible party, by delivering the notice in person or,
by leaving it in the possession of any person in charge of the premises, or by
posting the notice in a conspicuous place if the person in charge of the
premises cannot be found. The notice of violation shall indicate the right of
appeal by referencing the appeals section. When the owner of the building or
structure, or the permit holder for the construction in question, or
the tenants of such building or structure, are not the responsible
party to whom the notice of violation is issued, then a copy of the notice
shall also be delivered to the such owner, permit holder or
tenants.
Note: A notice of unsafe building or structure for structures that become unsafe during the construction process are issued in accordance with Section 118.
C. Section 115.2.1 Notice not to be issued under certain circumstances. When violations are discovered more than two years after the certificate of occupancy is issued or the date of initial occupancy, whichever occurred later, or more than two years after the approved final inspection for an alteration or renovation, a notice of violation shall only be issued upon advice from the legal counsel of the locality that action may be taken to compel correction of the violation. When compliance can no longer be compelled by prosecution under § 36-106 of the Code of Virginia, the building official, when requested by the building owner, shall document in writing the existence of the violation noting the edition of the USBC the violation is under.
D. Section 115.3 Further action when violation not corrected. If
the responsible party has not complied with the Upon failure to comply
with the notice of violation, the building official may initiate legal
proceedings by requesting the legal counsel of the locality to institute the
appropriate legal proceedings to restrain, correct or abate the violation or to
require the removal or termination of the use of the building or structure
involved. In cases where the locality so authorizes, the building official may
issue or obtain a summons or warrant. Compliance with a notice of violation
notwithstanding, the building official may request legal proceedings be
instituted for prosecution when a person, firm or corporation is served with
three or more notices of violation within one calendar year for failure to
obtain a required construction permit prior to commencement of work subject to
this code.
Note: See § 19.2-8 of the Code of Virginia concerning the statute of limitations for building code prosecutions.
E. Section 115.4 Penalties and abatement. Penalties for violations of the USBC shall be as set out in § 36-106 of the Code of Virginia. The successful prosecution of a violation of the USBC shall not preclude the institution of appropriate legal action to require correction or abatement of a violation.
F. Section 115.5 Transfer of ownership. In accordance with § 36-105 of the Code of Virginia, if the local building department has initiated an enforcement action against the owner of a building or structure and such owner subsequently transfers the ownership of the building or structure to an entity in which the owner holds an ownership interest greater than 50%, the pending enforcement action shall continue to be enforced against the owner.
13VAC5-63-160. Section 116 Certificates of occupancy.
A. Section 116.1 General; when to be issued. A certificate
Prior to occupancy or change of occupancy indicating completion
of the work for which a permit was issued shall be obtained prior to the
occupancy of any building or structure, except as provided for in this
section generally and as specifically provided for in Section 113.8 for
additions or alterations. The certificate shall be issued after completion a
certificate of occupancy shall be obtained in accordance with this section. The
building official shall issue the certificate of occupancy within five working
days after approval of the final inspection and when the building or
structure is in or portion thereof is determined to be in compliance
with this code and any pertinent laws or ordinances, or when otherwise
entitled. The building official shall, however, issue a certificate of
occupancy within five working days after being requested to do so, provided the
building or structure meets all of the requirements for a certificate.
Exception Exceptions:
1. A certificate of occupancy is not required for an accessory structure as defined in the IRC.
2. A new certificate of occupancy is not required for an addition to an existing Group R-5 building that already has a certificate of occupancy.
B. Section 116.1.1 Temporary certificate of occupancy. Upon the request of a permit holder, a temporary certificate of occupancy may be issued before the completion of the work covered by a permit, provided that such portion or portions of a building of structure may be occupied safely prior to full completion of the building or structure without endangering life or public safety.
C. Section 116.2 Contents of certificate. A certificate of occupancy shall specify the following:
1. The edition of the USBC under which the permit is issued.
2. The group classification and occupancy in accordance with the provisions of Chapter 3.
3. The type of construction as defined in Chapter 6.
4. If an automatic sprinkler system is provided and whether or not such system was required.
5. Any special stipulations and conditions of the building permit and if any modifications were issued under the permit, there shall be a notation on the certificate that modifications were issued.
6. Group R-5 occupancies complying with Section R320.2 of the IRC shall have a notation of compliance with that section on the certificate.
D. Section 116.3 Suspension or revocation of certificate. A
certificate of occupancy may be revoked or suspended whenever the building
official discovers that such certificate was issued in error or on the basis of
incorrect information, or where there are repeated violations of the USBC after
the certificate has been issued or when requested by the code official under
Section 105.7 106.6 of the VMC. The revocation or suspension
shall be in writing and shall state the necessary corrections or conditions for
the certificate to be reissued or reinstated in accordance with Section
116.3.1.
E. Section 116.3.1 Reissuance or reinstatement of certificate of occupancy. When a certificate of occupancy has been revoked or suspended, it shall be reissued or reinstated upon correction of the specific condition or conditions cited as the cause of the revocation or suspension and the revocation or suspension of a certificate of occupancy shall not be used as justification for requiring a building or structure to be subject to a later edition of the code than that under which such building or structure was initially constructed.
F. Section 116.4 Issuance of certificate for pre-USBC
buildings or structures When no certificate exists. When a
building or structure was constructed prior to being subject to the initial
edition of the USBC and the local building department does not have a
certificate of occupancy for the a building or structure, the
owner or owner's agent may submit a written request for a certificate to be
created. The building official, after receipt of the request, shall issue a
certificate provided a determination is made that there are no current
violations of the VMC or the Virginia Statewide Fire Prevention Code
(13VAC5-51) and the occupancy classification of the building or structure has
not changed. Such buildings and structures shall not be prevented from
continued use.
Exception: When no certificate exists, but the
local building department has records indicating that a certificate did exist,
then the but does not have a copy of the certificate itself, then the
building official may either verify in writing that a certificate did exist or
issue a certificate based upon the records.
13VAC5-63-190. Section 119 Appeals.
A. Section 119.1 Establishment of appeals board. In accordance with § 36-105 of the Code of Virginia, there shall be established within each local building department a LBBCA. Whenever a county or a municipality does not have such a LBBCA, the local governing body shall enter into an agreement with the local governing body of another county or municipality or with some other agency, or a state agency approved by DHCD for such appeals resulting therefrom. Fees may be levied by the local governing body in order to defray the cost of such appeals. In addition, as an authorization in this code, separate LBBCAs may be established to hear appeals of different enforcement areas such as electrical, plumbing or mechanical requirements. Each such LBBCA shall comply with the requirements of this section. The locality is responsible for maintaining a duly constituted LBBCA prepared to hear appeals within the time limits established in this section. The LBBCA shall meet as necessary to assure a duly constituted board, appoint officers as necessary, and receive such training on the code as may be appropriate or necessary from staff of the locality.
B. Section 119.2 Membership of board. The LBBCA shall consist of at least five members appointed by the locality for a specific term of office established by written policy. Alternate members may be appointed to serve in the absence of any regular members and as such, shall have the full power and authority of the regular members. Regular and alternate members may be reappointed. Written records of current membership, including a record of the current chairman and secretary shall be maintained in the office of the locality. In order to provide continuity, the terms of the members may be of different length so that less than half will expire in any one-year period.
C. Section 119.3 Officers and qualifications of members. The LBBCA shall annually select one of its regular members to serve as chairman. When the chairman is not present at an appeal hearing, the members present shall select an acting chairman. The locality or the chief executive officer of the locality shall appoint a secretary to the LBBCA to maintain a detailed record of all proceedings. Members of the LBBCA shall be selected by the locality on the basis of their ability to render fair and competent decisions regarding application of the USBC and shall to the extent possible, represent different occupational or professional fields relating to the construction industry. At least one member should be an experienced builder; at least one member should be an RDP, and at least one member should be an experienced property manager. Employees or officials of the locality shall not serve as members of the LBBCA.
D. Section 119.4 Conduct of members. No member shall hear an appeal in which that member has a conflict of interest in accordance with the State and Local Government Conflict of Interests Act (§ 2.2-3100 et seq. of the Code of Virginia). Members shall not discuss the substance of an appeal with any other party or their representatives prior to any hearings.
E. Section 119.5 Right of appeal; filing of appeal application. Any person aggrieved by the local building department's application of the USBC or the refusal to grant a modification to the provisions of the USBC may appeal to the LBBCA. The applicant shall submit a written request for appeal to the LBBCA within 30 calendar days of the receipt of the decision being appealed. The application shall contain the name and address of the owner of the building or structure and in addition, the name and address of the person appealing, when the applicant is not the owner. A copy of the building official's decision shall be submitted along with the application for appeal and maintained as part of the record. The application shall be marked by the LBBCA to indicate the date received. Failure to submit an application for appeal within the time limit established by this section shall constitute acceptance of a building official's decision.
Note: To the extent that a decision of a building official pertains to amusement devices there may be a right of appeal under the VADR.
F. Section 119.6 Meetings and postponements. The LBBCA shall
meet within 30 calendar days after the date of receipt of the application for
appeal, except that a period of up to 45 calendar days shall be permitted where
the LBBCA has regularly scheduled monthly meetings. A longer time period shall
be permitted if agreed to by all the parties involved in the appeal. A
notice Notice indicating the time and place of the hearing shall be
sent to the parties in writing to the addresses listed on the application if
requested or by electronic means at least 14 calendar days prior to the
date of the hearing, except that unless a lesser time period shall
be permitted if is agreed to by all the parties involved in the
appeal. When a quorum of the LBBCA is not present at a hearing to hear an
appeal, any party involved in the appeal shall have the right to request a
postponement of the hearing. The LBBCA shall reschedule the appeal within 30
calendar days of the postponement, except that a longer time period shall be
permitted if agreed to by all the parties involved in the appeal.
G. Section 119.7 Hearings and decision. All hearings before the LBBCA shall be open meetings and the appellant, the appellant's representative, the locality's representative and any person whose interests are affected by the building official's decision in question shall be given an opportunity to be heard. The chairman shall have the power and duty to direct the hearing, rule upon the acceptance of evidence and oversee the record of all proceedings. The LBBCA shall have the power to uphold, reverse or modify the decision of the official by a concurring vote of a majority of those present. Decisions of the LBBCA shall be final if no further appeal is made. The decision of the LBBCA shall be explained in writing, signed by the chairman and retained as part of the record of the appeal. Copies of the written decision shall be sent to all parties by certified mail. In addition, the written decision shall contain the following wording:
"Any person who was a party to the appeal may appeal to the State Review Board by submitting an application to such Board within 21 calendar days upon receipt by certified mail of this decision. Application forms are available from the Office of the State Review Board, 600 East Main Street, Richmond, Virginia 23219, (804) 371-7150."
H. Section 119.8 Appeals to the State Review Board. After final determination by the LBBCA in an appeal, any person who was a party to the appeal may further appeal to the State Review Board. In accordance with § 36-98.2 of the Code of Virginia for state-owned buildings and structures, appeals by an involved state agency from the decision of the building official for state-owned buildings or structures shall be made directly to the State Review Board. The application for appeal shall be made to the State Review Board within 21 calendar days of the receipt of the decision to be appealed. Failure to submit an application within that time limit shall constitute an acceptance of the building official's decision. For appeals from a LBBCA, a copy of the building official's decision and the written decision of the LBBCA shall be submitted with the application for appeal to the State Review Board. Upon request by the office of the State Review Board, the LBBCA shall submit a copy of all pertinent information from the record of the appeal. In the case of appeals involving state-owned buildings or structures, the involved state agency shall submit a copy of the building official's decision and other relevant information with the application for appeal to the State Review Board. Procedures of the State Review Board are in accordance with Article 2 (§ 36-108 et seq.) of Chapter 6 of Title 36 of the Code of Virginia. Decisions of the State Review Board shall be final if no further appeal is made.
13VAC5-63-200. Chapter 2 Definitions.
A. Add the following definitions to Section 202 of the IBC to read:
Aboveground liquid fertilizer storage tank (ALFST). A device
that contains an accumulation of liquid fertilizer (i) constructed of
nonearthen materials, such as concrete, steel or plastic, that provide
structural support; (ii) having a capacity of 100,000 gallons (378 500 (378,500
L) or greater; and (iii) the volume of which is more than 90% above the surface
of the ground. The term does not include any wastewater treatment or wastewater
storage tank, utility or industry pollution control equipment.
Building regulations. Any law, rule, resolution, regulation, ordinance or code, general or special, or compilation thereof, heretofore or hereafter enacted or adopted by the Commonwealth or any county or municipality, including departments, boards, bureaus, commissions, or other agencies thereof, relating to construction, reconstruction, alteration, conversion, repair, maintenance, or use of structures and buildings and installation of equipment therein. The term does not include zoning ordinances or other land use controls that do not affect the manner of construction or materials to be used in the erection, alteration or repair of a building or structure.
Chemical fume hood. A ventilated enclosure designed to contain and exhaust fumes, gases, vapors, mists, and particulate matter generated within the hood.
Construction. The construction, reconstruction, alteration, repair, or conversion of buildings and structures.
Day-night average sound level (Ldn). A 24-hour energy average sound level expressed in dBA, with a 10 decibel penalty applied to noise occurring between 10 p.m. and 7 a.m.
DHCD. The Virginia Department of Housing and Community Development.
Emergency communication equipment. Emergency communication
equipment, includes but is not limited to two-way radio communications,
signal booster, bi-directional amplifiers, radiating cable systems, or internal
multiple antenna, or a combination of the foregoing.
Emergency public safety personnel. Emergency public safety
personnel includes firefighters, emergency medical personnel, law-enforcement
officers, and other emergency public safety personnel routinely called upon to
provide emergency assistance to members of the public in a wide variety of
emergency situations, including but not limited to fires, medical
emergencies, violent crimes, and terrorist attacks.
Emergency supplemental hardware. Any approved hardware used only for emergency events or drills to keep intruders from entering the room during an active shooter or hostile threat event or drill.
Equipment. Plumbing, heating, electrical, ventilating, air-conditioning and refrigeration equipment, elevators, dumbwaiters, escalators, and other mechanical additions or installations.
Farm building or structure. A building or structure not used for residential purposes, located on property where farming operations take place, and used primarily for any of the following uses or combination thereof:
1. Storage, handling, production, display, sampling or sale of agricultural, horticultural, floricultural or silvicultural products produced in the farm.
2. Sheltering, raising, handling, processing or sale of agricultural animals or agricultural animal products.
3. Business or office uses relating to the farm operations.
4. Use of farm machinery or equipment or maintenance or storage of vehicles, machinery or equipment on the farm.
5. Storage or use of supplies and materials used on the farm.
6. Implementation of best management practices associated with farm operations.
Hospice facility. An institution, place, or building owned or operated by a hospice provider and licensed by the Virginia Department of Health as a hospice facility to provide room, board, and palliative and supportive medical and other health services to terminally ill patients and their families, including respite and symptom management, on a 24-hour basis to individuals requiring such care pursuant to the orders of a physician.
Industrialized building. A combination of one or more sections or modules, subject to state regulations and including the necessary electrical, plumbing, heating, ventilating and other service systems, manufactured off-site and transported to the point of use for installation or erection, with or without other specified components, to comprise a finished building. Manufactured homes shall not be considered industrialized buildings for the purpose of this code.
Laboratory suite. A fire-rated enclosed laboratory area that will provide one or more laboratory spaces, within a Group B educational occupancy, that are permitted to include ancillary uses such as offices, bathrooms, and corridors that are contiguous with the laboratory area and are constructed in accordance with Section 430.3.
LBBCA. Local board of building code appeals.
Liquid fertilizer. A fluid in which a fertilizer is in true solution. This term does not include anhydrous ammonia or a solution used in pollution control.
Local building department. The agency or agencies of any local governing body charged with the administration, supervision, or enforcement of this code, approval of construction documents, inspection of buildings or structures, or issuance of permits, licenses, certificates or similar documents.
Local governing body. The governing body of any city, county or town in this Commonwealth.
Locality. A city, county or town in this Commonwealth.
Manufactured home. A structure subject to federal regulation, which is transportable in one or more sections; is eight body feet or more in width and 40 body feet or more in length in the traveling mode, or is 320 or more square feet when erected on site; is built on a permanent chassis; is designed to be used as a single-family dwelling, with or without a permanent foundation, when connected to the required utilities; and includes the plumbing, heating, air-conditioning, and electrical systems contained in the structure.
Marina. Any installation, operating under public or private ownership, that has a structure providing dockage or moorage for boats, other than paddleboats or rowboats, and provides, through sale, rental, fee, or on a free basis, any equipment, supply, or service, including fuel, electricity, or water, for the convenience of the public or its lessees, renters, or users of its facilities. A dock or pier with or without slips that exclusively serves a single-family residential lot for the use of the owner of the lot is not a marina.
Night club. Any building in which the main use is a place of public assembly that provides exhibition, performance or other forms of entertainment; serves alcoholic beverages; and provides music and space for dancing.
Permissible fireworks. Any sparklers, fountains, Pharaoh's serpents, caps for pistols, or pinwheels commonly known as whirligigs or spinning jennies.
Short-term holding area. An area containing a holding cell or
cells, or a holding room or rooms, including associated rooms or
spaces where the occupants are restrained or detained by the use of security
measures not under the occupant's control for less than 24 hours.
Skirting. A weather-resistant material used to enclose the space from the bottom of the manufactured home to grade.
Slip. A berth or space where a boat may be secured to a fixed or floating structure, including a dock, finger pier, boat lift, or mooring buoy.
Sound transmission class (STC) rating. A single number characterizing the sound reduction performance of a material tested in accordance with ASTM E90-90, "Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions."
State regulated care facility (SRCF). A building with an occupancy in Group R-2, R-3, R-4 or R-5 occupied by persons in the care of others where program oversight is provided by the Virginia Department of Social Services, the Virginia Department of Behavioral Health and Developmental Services, the Virginia Department of Education or the Virginia Department of Juvenile Justice.
State Review Board. The Virginia State Building Code Technical Review Board as established under § 36-108 of the Code of Virginia.
Teaching and research laboratory. A building or portion of a building where hazardous materials are stored, used, and handled for the purpose of testing, analysis, teaching, research, or developmental activities on a nonproduction basis rather than in a manufacturing process.
Technical assistant. Any person employed by or under an
extended contract to a local building department or local enforcing agency for
enforcing the USBC, including but not limited to inspectors, plans
reviewers, and permit technicians. For the purpose of this definition, an
extended contract shall be a contract with an aggregate term of 18 months or
longer.
Tenable environmental. An environment in which the products of combustion, including smoke, toxic gases, particulates, and heat, are limited or otherwise restricted in order to maintain the impact on occupants, including those in the area of fire origin, to a level that is not life threatening and permits the rescue of occupants for a limited time.
Unsafe building or structure. Any building or structure that is under construction and has not received a permanent certificate of occupancy, final inspection, or for which a permit was never issued or has expired and has been determined by the building official to be of faulty construction that is so damaged, decayed, dilapidated, structurally unsafe, or of such faulty construction or unstable foundation that partial or complete collapse is likely, or any unfinished construction that does not have a valid permit, or the permit has been revoked, and the condition of the unfinished construction presents an immediate serious and imminent threat to the life and safety of the occupants or the public.
VADR. The Virginia Amusement Device Regulations (13VAC5-31).
VCS. The Virginia Certification Standards (13VAC5-21).
Working day. A day other than Saturday, Sunday or a legal local, state or national holiday.
B. Change the following definitions in Section 202 of the IBC to read:
Addition. An extension or increase in floor area, number of stories, or height of a building or structure.
Ambulatory care facility. Buildings or portions thereof used to provide medical care on less than a 24-hour basis that are licensed by the Virginia Department of Health as outpatient surgical hospitals.
Automatic fire-extinguishing system. An approved system of devices and equipment that automatically detects a fire and discharges an approved fire-extinguishing agent onto or in the area of a fire and includes among other systems an automatic sprinkler system, unless otherwise expressly stated.
Building. A combination of materials, whether portable or fixed, having a roof to form a structure for the use or occupancy by persons, or property. The word "building" shall be construed as though followed by the words "or part or parts thereof" unless the context clearly requires a different meaning. "Building" shall not include roadway tunnels and bridges owned by the Virginia Department of Transportation, which shall be governed by construction and design standards approved by the Virginia Commonwealth Transportation Board.
For application of this code, each portion of a building that is completely separated from other portions by fire walls complying with Section 706 shall be considered as a separate building (see Section 503.1).
Change of occupancy. See Section 202 of the VEBC.
Clinic, outpatient. Buildings or portions thereof used to provide medical care on less than a 24-hour basis that are not licensed by the Virginia Department of Health as outpatient surgical hospitals.
Custodial care. Assistance with day-to-day living tasks, such as assistance with cooking, taking medication, bathing, using toilet facilities, and other tasks of daily living. In other than in hospice facilities, custodial care includes occupants that have the ability to respond to emergency situations and evacuate at a slower rate or who have mental and psychiatric complications, or both.
Existing structure. A structure (i) for which a legal building
permit has been issued under any edition of the USBC, (ii) which that
has been previously approved, or (iii) which that was built prior
to the initial edition of the USBC. For application of provisions in flood
hazard areas, an existing structure is any building or structure for which the
start of construction commenced before the effective date of the community's
first flood plain management code, ordinance, or standard.
Owner. The owner or owners of the freehold of the premises or lesser estate therein, a mortgagee or vendee in possession, assignee of rents, receiver, executor, trustee or lessee in control of a building or structure.
Registered Design Professional design professional
(RDP). An architect or professional engineer, licensed to practice architecture
or engineering, as defined under § 54.1-400 of the Code of Virginia.
Substantial damage. For the purpose of determining compliance with the flood provisions of this code, damage of any origin sustained by a structure whereby the cost of restoring the structure to its before-damaged condition would equal or exceed 50% of the market value of the structure before the damage occurred.
Substantial improvement. For the purpose of determining compliance with the flood provisions of this code, any improvement, including repair, reconstruction, rehabilitation, alteration, or addition, or other improvement of a building or structure or a portion thereof the cost of which equals or exceeds 50% of the market value of the building or structure before the improvement or repair is started. If the building or structure or portion thereof has sustained substantial damage, any improvements are considered substantial improvements regardless of the actual improvement performed. The term does not, however, include either:
1. Any project for improvement of a building or a structure or portion thereof required to correct existing health, sanitary, or safety code violations identified by the building official and that is the minimum necessary to assure safe living conditions; or
2. Any alteration of a historic structure, provided that the alteration will not preclude the building or structure's continued designation as a historic building or structure.
Swimming pool. A pool or spa as defined in the International Swimming Pool and Spa Code (ISPSC).
Structure. An assembly of materials forming a construction for occupancy or use including stadiums, gospel and circus tents, reviewing stands, platforms, stagings, observation towers, radio towers, water tanks, storage tanks (underground and aboveground), trestles, piers, wharves, swimming pools, amusement devices, storage bins, and other structures of this general nature but excluding water wells. The word "structure" shall be construed as though followed by the words "or part or parts thereof" unless the context clearly requires a different meaning. "Structure" shall not include roadway tunnels and bridges owned by the Virginia Department of Transportation, which shall be governed by construction and design standards approved by the Virginia Commonwealth Transportation Board.
Wall. A vertical element with a horizontal length-to-thickness ratio greater than three used to enclose space.
C. Delete the following definitions from Section 202 of the IBC:
Agricultural building
Approved
Historic buildings
13VAC5-63-220. Chapter 4 Special detailed requirements based on use and occupancy.
A. Delete Section 403.4.5 of the IBC.
B. Change Section 407.4.1.1 of the IBC to read:
407.4.1.1 Special locking arrangement. Means of egress doors shall be permitted to contain locking devices restricting the means of egress in areas in which the clinical needs of the patients require restraint of movement, where all of the following conditions are met:
1. The locks release upon activation of the fire alarm system or the loss of power.
2. The building is equipped with an approved automatic sprinkler system in accordance with Section 903.3.1.1.
3. A manual release device is provided at a nursing station responsible for the area.
4. A key-operated switch or other manual device is provided adjacent to each door equipped with the locking device. Such switch or other device, when operated, shall result in direct interruption of power to the lock -- independent of the control system electronics.
5. All staff shall have keys or other means to unlock the switch or other device or each door provided with the locking device.
C. Add Section 407.11 407.12 to the IBC to read:
407.11 407.12 Emergency power systems. Emergency
power shall be provided for medical life support equipment, operating,
recovery, intensive care, emergency rooms, fire detection and alarm systems in
any Group I-2 occupancy licensed by the Virginia Department of Health as a
hospital, nursing home or hospice facility.
D. Add Section 408.2.1 to the IBC to read:
408.2.1 Short-term holding areas. Short-term holding areas
shall be permitted to comply with Section 429 431.
E. Change Section 408.6 of the IBC to read:
408.6 Smoke barrier. Occupancies classified as Group I-3 shall have smoke barriers complying with Sections 408.8 and 709 to divide every story occupied by residents for sleeping, or any other story having an occupant load of 50 or more persons, into no fewer than two smoke compartments.
F. Change Section 408.9 of the IBC and add Sections 408.9.1 through 408.9.3 to the IBC to read:
408.9 Smoke control. Smoke control for each smoke compartment shall be in accordance with Sections 408.9.1 through 408.9.3.
Exception: Smoke compartments with operable windows or windows that are readily breakable.
408.9.1 Locations. An engineered smoke control system shall comply with Section 909 and shall be provided in the following locations:
1. Dormitory areas.
2. Celled areas.
3. General housing areas.
4. Intake areas.
5. Medical celled or medical dormitory areas.
6. Interior recreation areas.
408.9.2 Compliance. The engineered smoke control system shall provide and maintain a tenable environment in the area of origin and shall comply with all of the following:
1. Shall facilitate the timely evacuation and relocation of occupants from the area of origin.
2. Shall be independent of exhaust systems under Chapter 5 of the IMC.
3. Duration of operation in accordance with Section 909.4.6.
4. The pressurization method shall be permitted and shall provide a minimum of 24 air changes per hour of exhaust, and 20 air changes per hour of makeup, and shall comply with Section 909.6. If the pressurization method is not utilized, the exhaust method shall be provided and shall comply with Section 909.8.
408.9.3 Corridors. Egress corridors within smoke compartments shall be kept free and clear of smoke.
G. Add an exception to Section 414.2 of the IBC to read:
Exception: Higher education teaching and research
laboratories shall be permitted to comply with Section 430.
H. G. Add Section 414.6.2 to the IBC to read:
414.6.2 Other regulations. The installation, repair, upgrade, and closure of underground and aboveground storage tanks subject to the Virginia State Water Control Board regulations 9VAC25-91 and 9VAC25-580 shall be governed by those regulations, which are hereby incorporated by reference to be an enforceable part of this code. Where differences occur between the provisions of this code and the incorporated provisions of the State Water Control Board regulations, the provisions of the State Water Control Board regulations shall apply. Provisions of the International Fire Code addressing closure of such tanks that are subject to the Virginia State Water Control Board regulations 9VAC25-91 and 9VAC25-580 shall not be applicable.
I. H. Change footnote "b" of Table 428.3
of the IBC to read:
b. Shall include walls, floors, ceilings, and construction supporting the floor of the laboratory suite necessary to provide separation from other portions of the building. Fire barriers shall be constructed in accordance with Section 707, and horizontal assemblies shall be constructed in accordance with Section 711.
I. Delete Section 428.3.3 of the IBC.
J. Change Section 428.3.7 of the IBC to read:
428.3.7 Ventilation. Ventilation shall be in accordance with the Virginia Mechanical Code. The design and installation of ducts from chemical fume hoods shall be in accordance with NFPA 91.
K. Add IBC Section 427 429 to read:
Section 429 Manufactured Homes and Industrialized Buildings.
J. Add Section 427.1 to the IBC to read:
427.1 429.1 General. The provisions of this
section shall apply to the installation or erection of manufactured homes
subject to the Virginia Manufactured Home Safety Regulations (13VAC5-95) and
industrialized buildings subject to the Virginia Industrialized Building Safety
Regulations (13VAC5-91).
Note: Local building departments are also responsible for the enforcement of certain provisions of the Virginia Manufactured Home Safety Regulations (13VAC5-95) and the Virginia Industrialized Building Safety Regulations (13VAC5-91) as set out in those regulations.
K. Add Section 427.2 to the IBC to read:
427.2 429.2 Site work for manufactured homes.
Footing design, basements, grading, drainage, decks, stoops, porches and
utility connections shall comply with the provisions of this code applicable to
Group R-5 occupancies. Additionally, all applicable provisions of Chapter 1 of
this code, including but not limited to requirements for permits,
inspections, certificates of occupancy and requiring compliance, are applicable
to the installation and set-up of a manufactured home. Where the installation
or erection of a manufactured home utilizes components that are to be
concealed, the installer shall notify the building official that an inspection
is necessary and assure that an inspection is performed and approved prior to
concealment of such components, unless the building official has agreed to an
alternative method of verification.
L. Add Section 427.2.1 to the IBC to read:
427.2.1 429.2.1 Relocated manufactured homes.
Installation, set-up, and site work for relocated manufactured homes shall
comply with the provisions of this code and shall include the option of using
the manufacturer's installations instructions or the federal Model Manufactured
Home Installation Standards (24 CFR Part 3285) for the technical requirements.
M. Add Section 427.2.2 to the IBC to read:
427.2.2 429.2.2 Alterations and repairs to
manufactured homes. Alterations and repairs to manufactured homes shall either
be in accordance with federal Manufactured Home Construction and Safety
Standards (24 CFR Part 3280) or in accordance with the alteration and repair
provisions this code.
N. Add Section 427.2.3 to the IBC to read:
427.2.3 429.2.3 Additions to manufactured homes.
Additions to manufactured homes shall comply with this code and shall be
structurally independent of the manufactured home, or when not structurally
independent, shall be evaluated by an RDP to determine that the addition does
not cause the manufactured home to become out of compliance with federal
Manufactured Home Construction and Safety Standards (24 CFR Part 3280).
O. Add Section 427.3 to the IBC to read:
427.3 429.3 Wind load requirements for
manufactured homes. Manufactured homes shall be anchored to withstand the wind
loads established by the federal regulation for the area in which the
manufactured home is installed. For the purpose of this code, Wind Zone II of
the federal regulation shall include the cities of Chesapeake, Norfolk,
Portsmouth, and Virginia Beach.
P. Add Section 427.4 to the IBC to read:
427.4 429.4 Skirting requirements for
manufactured homes. As used in this section, "skirting" means a
weather-resistant material used to enclose the space from the bottom of the
manufactured home to grade. In accordance with § 36-99.8 of the Code of
Virginia, manufactured homes installed or relocated shall have skirting
installed within 60 days of occupancy of the home. Skirting materials shall be
durable, suitable for exterior exposures and installed in accordance with the
manufacturer's installation instructions. Skirting shall be secured as
necessary to ensure stability, to minimize vibrations, to minimize
susceptibility to wind damage and to compensate for possible frost heave. Each
manufactured home shall have a minimum of one opening in the skirting providing
access to any water supply or sewer drain connections under the home. Such
openings shall be a minimum of 18 inches (457 mm) in any dimension and not less
than three square feet (.28 (0.28 m2) in area. The
access panel or door shall not be fastened in a manner requiring the use of a
special tool to open or remove the panel or door. On-site fabrication of the
skirting by the owner or installer of the home shall be acceptable, provided
that the material meets the requirements of this code. In addition, as a
requirement of this code, skirting for the installation and set-up of a new
manufactured home shall also comply with the requirements of 24 CFR Part 3285
Model Manufactured Home Installation Standards.
Q. Add Section 427.5 to the IBC to read:
427.5 429.5 Site work for industrialized
buildings. Site work for the erection and installation of an industrialized building
shall comply with the manufacturer's installation instructions. To the extent
that any aspect of the erection or installation of an industrialized building
is not covered by the manufacturer's installation instructions, this code shall
be applicable, including the use of the IRC for any construction work where the
industrialized building would be classified as a Group R-5 building. In
addition, all administrative requirements of this code for permits,
inspections, and certificates of occupancy are also applicable. Further, the
building official may require the submission of plans and specifications for
details of items needed to comprise the finished building that are not included
or specified in the manufacturer's instructions, including, but not limited
to, footings, foundations, supporting structures, proper anchorage, and the
completion of the plumbing, mechanical, and electrical systems. Where the
installation or erection of an industrialized building utilizes components that
are to be concealed, the installer shall notify the building official that an
inspection is necessary and assure that an inspection is performed and approved
prior to concealment of such components, unless the building official has
agreed to an alternative method of verification.
Exception: Temporary family health care structures installed pursuant to § 15.2-2292.1 of the Code of Virginia shall not be required or permitted to be placed on a permanent foundation, but shall otherwise remain subject to all pertinent provisions of this section.
R. Add Section 427.6 to the IBC to read:
427.6 429.6 Relocated industrialized buildings;
alterations and additions. Industrialized buildings constructed prior to
January 1, 1972, shall be subject to Section 117 when relocated. Alterations
and additions to any existing industrialized buildings shall be subject to
pertinent provisions of this code. Building officials shall be permitted to
require the submission of plans and specifications for the model to aid in the
evaluation of the proposed alteration or addition. Such plans and
specifications shall be permitted to be submitted in electronic or other
available format acceptable to the building official.
S. Add Section 427.7 to the IBC to read:
427.7 429.7 Change of occupancy of industrialized
buildings. Change of occupancy of industrialized buildings is regulated by the
Virginia Industrialized Building Safety Regulations (13VAC5-91). When the
industrialized building complies with those regulations for the new occupancy,
the building official shall issue a new certificate of occupancy under the
USBC.
T. L. Add IBC Section 428 430
Aboveground Liquid Fertilizer Tanks. to the IBC to read:
U. Add Sections 428.1 through 428.6 to the IBC to read:
428.1 430.1 General. This section shall apply to
the construction of ALFSTs and shall supersede any conflicting requirements in
other provisions of this code. ALFSTs shall also comply with any applicable
nonconflicting requirements of this code.
428.1.1 430.1.1 When change of occupancy rules
apply. A change of occupancy to use a tank as an ALFST occurs when there is a
change in the use of a tank from storing liquids other than liquid fertilizers
to a use of storing liquid fertilizer and when the type of liquid fertilizer
being stored has a difference of at least 20% of the specific gravity or
operating temperature, or both, or a significant change in the material's
compatibility.
428.2 430.2 Standards. Newly constructed welded
steel ALFSTs shall comply with API 650 and TFI RMIP, as applicable. Newly
constructed ALFSTs constructed of materials other than welded steel shall be
constructed in accordance with accepted engineering practice to prevent the
discharge of liquid fertilizer and shall be constructed of materials that are
resistant to corrosion, puncture or cracking. In addition, newly constructed
ALFSTs constructed of materials other than welded steel shall comply with TFI
RMIP, as applicable. For the purposes of this code, the use of TFI RMIP shall
be construed as mandatory and any language in TFI RMIP, such as, but not
limited to, the terms "should" or "may" which indicate that
a provision is only a recommendation or a guideline shall be taken as a
requirement. ALFSTs shall be placarded in accordance with NFPA 704.
Exception: Sections 4.1.4, 4.2.5, 5.1.2, 5.2.8, 5.3 and 8.1(d)(i) of TFI RMIP shall not be construed as mandatory.
428.3 430.3 Secondary containment. When ALFSTs
are newly constructed and when there is a change of occupancy to use a tank as
an ALFST, a secondary containment system designed and constructed to prevent
any liquid fertilizer from reaching the surface water, groundwater or adjacent
land before cleanup occurs shall be provided. The secondary containment system
may include dikes, berms or retaining walls, curbing, diversion ponds, holding
tanks, sumps, vaults, double-walled tanks, liners external to the tank, or
other approved means and shall be capable of holding up to 110% of the capacity
of the ALFST as certified by an RDP.
428.4 430.4 Repair, alteration and reconstruction
of ALFSTs. Repair, alteration and reconstruction of ALFSTs shall comply with
applicable provisions of API 653 and TFI RMIP.
428.5 430.5 Inspection. Applicable inspections as
required by and in accordance with API 653 and TFI RMIP shall be performed for
repairs and alterations to ALFSTS, the reconstruction of ALFSTs and when there
is a change of occupancy to use a tank as an ALFST. When required by API 653 or
TFI RMIP, such inspections shall occur prior to the use of the ALFST.
428.6 430.6 Abandoned ALFSTs. Abandoned ALFSTs
shall comply with applicable provisions of Section 5704.2.13.2 of the IFC.
V. Add IBC Section 429 Short-term Holding Areas.
W. Add Section 429.1 to the IBC to read:
429.1 General. In all groups other than Group E, short-term holding
areas shall be permitted to be classified as the main occupancy, provided all
of the following are met:
1. Provisions are made for the release of all restrained or
detained occupants of short-term holding areas at all times.
2. Aggregate area of short-term holding areas shall not
occupy more than 10% of the building area of the story in which they are
located and shall not exceed the tabular values for building area in Table
506.2, without building area increases.
3. Restrained or detained occupant load of each short-term
holding area shall not exceed 20.
4. Aggregate restrained or detained occupant load in
short-term holding areas per building shall not exceed 80.
5. Compliance with Sections 408.3.7, 408.3.8, 408.4, and
408.7, as would be applicable to I-3 occupancies.
6. Requirements of the main occupancy in which short-term
holding areas are located shall be met.
7. Fire areas containing short-term holding areas shall be
provided with a fire alarm system and automatic smoke detection system complying
with Section 907.2.6.3, as would be applicable to I-3 occupancies.
8. Where each fire area containing short-term holding areas
exceeds 12,000 square feet (1115 m2), such fire areas shall be
provided with an automatic sprinkler system complying with Section 903.3.
9. Short-term holding areas shall be separated from other
short-term holding areas and adjacent spaces by smoke partitions complying with
Section 710.
X. Add IBC Section 430 Higher Education Laboratories.
Y. Add Sections 430.1 through 430.4 to the IBC to read:
430.1 Scope. Group B teaching and research laboratories in
educational occupancies above the 12th grade complying with the requirements of
this section shall be permitted to comply with Table 430.3, 430.4(1), or
430.4(2) without requiring classification as a Group H occupancy. Except as
specified in this section, such laboratories shall comply with all applicable
provisions of this code. In addition, as set out in Section 5001.7 of the SFPC,
approval under this section is contingent upon operational requirements in the
SFPC being complied with and maintained.
430.2 Application. The provisions of this section shall be
applied as exceptions or additions to applicable requirements of this code.
430.3 Laboratory suite construction. Where laboratory suites
are provided, they shall be constructed in accordance with this section. The
number of laboratory suites and percentage of maximum allowable quantities of
hazardous materials in laboratory suites shall be in accordance with Table
430.3.
430.3.1 Separation from adjacent areas. Laboratory suites
shall be separated from other portions of the building in accordance with the
most restrictive of either (i) Table 430.3 with fire barriers constructed in
accordance with Section 707 and horizontal assemblies constructed in accordance
with Section 711 or (ii) Section 508.4. Where individual laboratories within a
laboratory suite are separated from each other, the separation shall consist of
one-hour fire barriers.
Exception: Where an individual laboratory suite occupies
more than one story, the fire resistance rating of intermediate floors
contained within the laboratory suite shall comply with the requirements of
this code.
430.3.2 Separation from other laboratory suites. Laboratory
suites shall be separated from other laboratory suites in accordance with Table
430.3.
430.3.3 Floor assembly fire resistance. The floor assembly
supporting the laboratory suite and the construction supporting the floor of
the laboratory suite shall have a fire resistance rating of not less than two
hours.
Exception: The floor assembly of the laboratory suite and
the construction supporting the floor of the laboratory suite are allowed to be
one-hour fire resistance rated in buildings of Types IIA, IIIA, and VA
construction, provided that the building is three or fewer stories.
430.3.4 Maximum number. The maximum number of laboratory
suites per floor shall be in accordance with Table 430.3. Where a building
contains both laboratory suites complying with Section 430.3 and control areas
complying with Section 414.2, the total number of laboratory suites and control
areas shall not exceed the maximum number of laboratory suites in accordance
with Table 430.3.
430.3.5 Standby or emergency power. Standby or emergency
power shall be provided in accordance with Section 414.5.2 where laboratory
suites are located above the sixth story above grade plane or located in a
story below grade plane.
430.3.6 Ventilation. Ventilation shall be in accordance with
the International Mechanical Code. The design and installation of ducts from
chemical fume hoods shall be in accordance with NFPA 91.
430.3.7 Liquid tight floor. Portions of the laboratory suite
where hazardous materials are present shall be provided with a liquid tight
floor.
430.3.8 Automatic fire sprinkler systems. Buildings shall be
equipped throughout with an approved automatic sprinkler system in accordance
with Section 903.3.1.1.
430.3.9 Automatic fire alarm and detection system.
Laboratory suites shall be equipped throughout with an automatic fire detection
system in accordance with Section 907.2. The building shall be equipped
throughout with an automatic fire alarm system in accordance with Section 907.2.
430.3.10 Percentage of maximum allowable quantity in each
laboratory suite. The percentage of maximum allowable quantities in each
laboratory suite shall be in accordance with Table 430.3.
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
430.4 Teaching and research laboratories utilizing control
areas. Group B teaching and research laboratories in educational occupancies
above the 12th grade utilizing control areas are permitted to increase amounts
of hazardous materials stipulated in Section 414.2 without the laboratories
being classified as Group H. The percentage of maximum allowable quantities of
hazardous materials per control area and the number of control areas permitted
at each floor level within a building shall be permitted to comply with Table
430.4(1) in buildings equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1 or shall be permitted to comply with Table
430.4(2) in buildings not equipped throughout with an automatic sprinkler
system in accordance with Section 903.3.1.1. In addition, as set out in Section
5001.7 of the SFPC, approval under this section is contingent upon operational
requirements in the SFPC being complied with and maintained.
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
430.4.1 Separation requirements. Control areas shall be
separated from each other and from other non-control areas by fire barriers
constructed in accordance with Section 707 or horizontal assemblies constructed
in accordance with Section 711, or both.
430.4.2 Fire resistance rating requirements. The required
fire-resistance rating for fire barriers shall be in accordance with Table
430.4(1) in buildings equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1 or in accordance with Table 430.4(2) in
buildings not equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1. The floor assembly of the control area and
the construction supporting the floor of the control area shall have a
fire-resistance rating in accordance with Table 430.4(1) in buildings equipped
throughout with an automatic sprinkler system in accordance with Section
903.3.1.1 or in accordance with Table 430.4(2) in buildings not equipped
throughout with an automatic sprinkler system in accordance with Section
903.3.1.1.
Exception: The floor assembly of the control area and the
construction supporting the floor of the control area are allowed to be
one-hour fire resistance rated in buildings of Types IIA, IIIA, and VA
construction, provided that the building is three or fewer stories.
430.4.3 Standby or emergency power. Standby or emergency
power shall be provided where control areas are located above the sixth floor
level above grade plane or located in a floor level below grade plane.
430.4.4 Restricted materials in storage and use. Where
approved by the building official, the storage and use of the following
hazardous materials prohibited by Table 307.1(1) in buildings not equipped
throughout with an automatic sprinkler system in accordance with Section
903.3.1.1, shall be allowed within a control area at 25% of Table 307.1(1)
limits for a building equipped throughout with an automatic sprinkler system:
1. Pyrophorics.
2. Class 4 oxidizers.
No additional quantity increases shall be allowed. All such
materials shall be stored and used in accordance with Section 5001.7 of the
SFPC.
430.4.5 Automatic fire alarm and detection system. The
building shall be equipped throughout with an automatic fire alarm system in
accordance with Section 907.2, and control areas where hazardous materials are
used or stored shall be equipped throughout with an automatic fire detection
system in accordance with Section 907.2.
430.4.6 Ventilation. Ventilation shall be in accordance with
the International Mechanical code.
M. Add Section 431 Short-term Holding Areas to the IBC to read:
431.1 General. In all groups other than Group E, short-term holding areas shall be permitted to be classified as the main occupancy, provided all of the following are met:
1. Provisions are made for the release of all restrained or detained occupants of short-term holding areas at all times.
2. Aggregate area of short-term holding areas shall not occupy more than 10% of the building area of the story in which they are located and shall not exceed the tabular values for building area in Table 506.2 without building area increases.
3. Restrained or detained occupant load of each short-term holding area shall not exceed 20.
4. Aggregate restrained or detained occupant load in short-term holding areas per building shall not exceed 80.
5. Compliance with Sections 408.3.7, 408.3.8, 408.4, and 408.7 as applicable for Group I-3 occupancies.
6. Requirements of the main occupancy in which short-term holding areas are located shall be met.
7. Fire areas containing short-term holding areas shall be provided with a fire alarm system and automatic smoke detection system complying with Section 907.2.6.3 as applicable to I-3 occupancies.
8. Where each fire area containing short-term holding areas exceeds 12,000 square feet (1115 m2), such fire areas shall be provided with an automatic sprinkler system complying with Section 903.3.
9. Short-term holding areas shall be separated from other short-term holding areas and adjacent spaces by smoke partitions complying with Section 710.
13VAC5-63-230. Chapter 7 Fire and smoke protection features.
A. Change item 5 of Section 703.3 of the IBC to read:
5. Alternative protection methods as allowed by Section 112.2.
B. Change Section 703.7 of the IBC to read:
703.7 Fire-resistance assembly marking. Where there is a concealed floor, floor-ceiling, or attic space, the fire walls, fire barriers, fire partitions, smoke barriers, or any other wall required to have protected openings or penetrations shall be designated above ceilings and on the inside of all ceiling access doors that provide access to such fire rated assemblies by signage having letters no smaller than one inch (25.4 mm) in height. Such signage shall indicate the fire-resistance rating of the assembly and the type of assembly and be provided at horizontal intervals of no more than eight feet (2438 mm).
Note: An example of suggested formatting for the signage would be "ONE HOUR FIRE PARTITION."
B. C. Change the exceptions exception
and add an exception to Section 705.2 of the IBC to read:
Exceptions:
1. Buildings on the same lot and considered as portions of one building in accordance with Section 705.3 are not required to comply with this section.
2. Decks and open porches of buildings of Groups R-3 and R-4.
C. D. Add Exception 4 to Section 706.5.2 of the
IBC to read:
4. Decks and open porches of buildings in Groups R-3 and R-4.
D. E. Change Section 716.5.3.1 716.2.1.4
of the IBC to read:
716.5.3.1 716.2.1.4 Smoke and draft control. Fire
door assemblies located in smoke barrier walls shall also meet the requirements
for a smoke and draft control door assembly tested in accordance with UL 1784. The
air leakage rate of the door assembly shall not exceed 3.0 cubic feet per
minute per square foot (0.01524 m3/s ∙ m2)
of door opening at 0.10 inch (24.9 Pa) of water for both the ambient
temperature and elevated temperature tests. Louvers shall be prohibited.
Installation of smoke doors shall be in accordance with NFPA 105.
E. F. Change Section 717.5.3 of the IBC to read:
717.5.3 Shaft enclosures. Shaft enclosures that are permitted to be penetrated by ducts and air transfer openings shall be protected with approved fire and smoke dampers installed in accordance with their listing.
Exceptions:
1. Fire and smoke dampers are not required where steel exhaust subducts extend at least 22 inches (559 mm) vertically in exhaust shafts, provided there is a continuous airflow upward to the outside.
2. Fire dampers are not required where penetrations are tested in accordance with ASTM E119 as part of the fire resistance-rated assembly.
3. Fire and smoke dampers are not required where ducts are used as part of an approved smoke control system in accordance with Section 909.
4. Fire and smoke dampers are not required where the penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than two-hour fire-resistance-rated construction.
5. Smoke dampers are not required where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
F. G. Add Section 717.6.2.2 to the IBC to read:
717.6.2.2 Equipment shutdown. Where ceiling radiation dampers are listed as static dampers, the HVAC equipment shall be effectively shut down to stop the airflow prior to the damper closing using one of the following methods:
1. A duct detector installed in the return duct.
2. An area smoke detector interlocked with the HVAC equipment.
3. A listed heat sensor installed in the return duct.
13VAC5-63-235. Chapter 8 Interior finishes.
Change Section 806.3 806.2 of the IBC to read:
806.3 806.2 Combustible decorative materials. In
other than Group I-3, curtains, draperies, fabric hangings, and similar combustible
decorative materials suspended from walls or ceilings shall comply with Section
806.4 and shall not exceed 10% of the specific wall or ceiling area to which it
is attached.
Fixed or movable walls and partitions, paneling, wall pads, and crash pads applied structurally or for decoration, acoustical correction, surface insulation, or other purposes shall be considered interior finish, shall comply with Section 803, and shall not be considered decorative materials or furnishings.
Exceptions:
1. In auditoriums or similar types of spaces in Group A, the
permissible amount of curtains, draperies, fabric hangings, and similar
combustible decorative materials suspended from walls or ceilings shall not
exceed 75% of the aggregate wall area where the building is equipped throughout
with an automatic sprinkler system in accordance with Section 903.3.1.1, and
where the material is installed in accordance with Section 803.13 803.15
of this code.
2. In auditoriums or similar types of spaces in Group A, the permissible amount of decorative materials suspended from the ceiling, located no more than 12 inches (305 mm) from the wall, not supported by the floor, and meeting the flame propagation performance criteria of NFPA 701, shall not exceed 75% of the aggregate wall area when the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
3. In Group R-2 dormitories, within sleeping units and dwelling units, the permissible amount of curtains, draperies, fabric hangings, and similar decorative materials suspended from walls or ceiling shall not exceed 50% of the aggregate walls areas where the building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.
4. In Group Groups B and M occupancies, the
amount of combustible fabric partitions suspended from the ceiling and not
supported by the floor shall comply with Section 806.4 and shall not be
limited.
13VAC5-63-240. Chapter 9 Fire protection systems.
A. Add the following to the list of terms in Section 902.1
of the IBC:
Emergency communication equipment.
Emergency public safety personnel.
B. A. Change Item 2 of Section 903.2.1.2
of the IBC to read:
903.2.1.2 Group A-2. An automatic sprinkler system shall be
provided for fire areas containing Group A-2 occupancies and intervening floors
of the building where one of the following conditions exists:
1. The fire area exceeds 5,000 square feet (464.5m2).
2. The fire area has an occupant load of 100 or more in night clubs or 300 or more in other Group A-2 occupancies.
3. The fire area is located on a floor other than a level of
exit discharge serving such occupancies.
4. The fire area contains a multitheater complex.
C. B. Change Item 2 of Section 903.2.1.3 of the
IBC to read:
2. In Group A-3 occupancies other than places of religious worship, the fire area has an occupant load of 300 or more.
D. C. Change Item 1 of Section 903.2.3 of
the IBC to read:
903.2.3 Group E. An automatic sprinkler system shall be
provided for Group E occupancies as follows:
1. Throughout all Group E fire areas greater than 20,000 square feet (1858 m2) in area.
2. Throughout every portion of educational buildings below
the lowest level of exit discharge serving that portion of the building.
Exception: An automatic sprinkler system is not required in
any area below the lowest level of exit discharge serving that area where every
classroom throughout the building has at least one exterior exit door at ground
level.
E. D. Add Exception 4 to Section 903.2.6 to
read:
4. An automatic sprinkler system shall not be required for open-sided or chain link-sided buildings and overhangs over exercise yards 200 square feet (18.58 m2) or less in Group I-3 facilities, provided such buildings and overhangs are of noncombustible construction.
F. Change E. Delete Item 4 of Section 903.2.7 of
the IBC to read:.
903.2.7 Group M. An automatic sprinkler system shall be
provided throughout buildings containing a Group M occupancy where one of the
following conditions exists:
1. A Group M fire area exceeds 12,000 square feet (1115 m2).
2. A Group M fire area is located more than three stories
above grade plane.
3. The combined area of all Group M fire areas on all
floors, including any mezzanines, exceeds 24,000 square feet (2230 m2).
G. F. Change Section 903.2.8 of the IBC to read:
903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area, except for Group R-2 occupancies listed in the exceptions to this section when the necessary water pressure or volume, or both, for the system is not available:
Exceptions:
1. Group R-2 occupancies that do not exceed two stories, including basements that are not considered as a story above grade, and with a maximum of 16 dwelling units per fire area. Each dwelling unit shall have at least one door opening to an exterior exit access that leads directly to the exits required to serve that dwelling unit.
2. Group R-2 occupancies where all dwelling units are not more than two stories above the lowest level of exit discharge and not more than one story below the highest level of exit discharge of exits serving the dwelling unit and a two-hour fire barrier is provided between each pair of dwelling units. Each bedroom of a dormitory or boarding house shall be considered a dwelling unit under this exception.
H. Add G. Change Section 903.3.1.2.2 903.3.1.2.3
to the IBC to read:
903.3.1.2.2 903.3.1.2.3 Attics. Sprinkler
protection shall be provided for attics in buildings of Type III, IV or V
construction in Group R-2 occupancies that are designed or developed and
marketed to senior citizens 55 years of age or older and in Group I-1
occupancies in accordance with Section 7.2 of NFPA 13R.
I. H. Add Section 903.3.5.1.1 to the IBC and
change Section 903.3.5.2 of the IBC to Section 903.3.5.1.2; both to read as
follows:
903.3.5.1.1 Limited area sprinkler systems. Limited area sprinkler systems serving fewer than 20 sprinklers on any single connection are permitted to be connected to the domestic service where a wet automatic standpipe is not available. Limited area sprinkler systems connected to domestic water supplies shall comply with each of the following requirements:
1. Valves shall not be installed between the domestic water riser control valve and the sprinklers.
Exception: An approved indicating control valve supervised in the open position in accordance with Section 903.4.
2. The domestic service shall be capable of supplying the simultaneous domestic demand and the sprinkler demand required to be hydraulically calculated by NFPA 13, NFPA 13R, or NFPA 13D.
903.3.5.1.2 Residential combination services. A single combination water supply shall be allowed provided that the domestic demand is added to the sprinkler demand as required by NFPA 13R.
J. I. Delete Section 903.3.5.2 of the IBC and
Sections 903.3.8 through 903.3.8.5 of the IBC.
K. J. Change Section 903.4.2 of the IBC to read:
903.4.2 Alarms. Approved audible devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Group R-2 occupancies that contain 16 or more dwelling units or sleeping units, any dwelling unit or sleeping unit two or more stories above the lowest level of exit discharge, or any dwelling unit or sleeping unit more than one story below the highest level of exit discharge of exits serving the dwelling unit or sleeping unit shall provide a manual fire alarm box at an approved location to activate the suppression system alarm.
L. K. Change Section 905.3.1 of the IBC to read:
905.3.1 Height. Class III standpipe systems shall be installed throughout buildings where four or more stories are above or below grade plane, the floor level of the highest story is located more than 30 feet (9144 mm) above the lowest level of fire department vehicle access, or where the floor level of the lowest story is located more than 30 feet (9144 mm) below the highest level of fire department vehicle access.
Exceptions:
1. Class I standpipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
2. Class I manual wet standpipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1 or Section 903.3.2 and where the highest floor is located not more than 150 feet (45,720 mm) above the lowest level of fire department vehicle access.
3. Class I manual standpipes are allowed in open parking garages where the highest floor is located not more than 150 feet (45,720 mm) above the lowest level of fire department vehicle access.
4. Class I manual dry standpipes are allowed in open parking garages that are subject to freezing temperatures, provided that the hose connections are located as required for Class II standpipes in accordance with Section 905.5.
5. Class I standpipes are allowed in basements equipped throughout with an automatic sprinkler system.
6. In determining the lowest level of fire department vehicle access, it shall not be required to consider either of the following:
6.1. Recessed loading docks for four vehicles or less.
6.2. Conditions where topography makes access from the fire department vehicle to the building impractical or impossible.
M. L. Change Item 1 of Section 906.1 of the IBC
to read:
1. In Groups A, B, E, F, H, I, M, R-1, R-4, and S occupancies.
Exceptions:
1. In Groups A, B, and E occupancies equipped throughout with quick response sprinklers, portable fire extinguishers shall be required only in locations specified in Items 2 through 6.
2. In Group I-3 occupancies, portable fire extinguishers shall be permitted to be located at staff locations and the access to such extinguishers shall be permitted to be locked.
N. M. Change Section 907.2.1.1 of the IBC to
read:
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more and in certain night clubs. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more and in night clubs with an occupant load of 300 or more shall initiate a signal using an emergency voice and alarm communications system in accordance with Section 907.5.2.2.
Exception: Where approved, the prerecorded announcement is allowed to be manually deactivated for a period of time, not to exceed three minutes, for the sole purpose of allowing a live voice announcement from an approved, constantly attended location.
O. Add Section 907.2.2.2 to the IBC to read:
907.2.2.2 Higher education laboratories. An automatic fire
alarm and detection system shall be provided in Group B occupancies where an
increase in hazardous materials is permitted in accordance with Section 430.
P. N. Change Section 907.2.3 of the IBC to read:
907.2.3 Group E. A manual fire alarm system that activates the occupant notification system meeting the requirements of Section 907.5 and installed in accordance with Section 907.6 shall be installed in Group E occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system.
Exceptions:
1. A manual fire alarm system is not required in Group E occupancies with an occupant load of 50 or less.
2. Manual fire alarm boxes are not required in Group E occupancies where all of the following apply:
2.1. Interior corridors are protected by smoke detectors.
2.2. Auditoriums, cafeterias, gymnasiums, and similar areas are protected by heat detectors or other approved detection devices.
2.3. Shops and laboratories involving dusts or vapors are protected by heat detectors or other approved detection devices.
3. Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, the occupant notification system will activate on sprinkler water flow and manual activation is provided from a normally occupied location.
Q. O. Add an exception to Section 907.5.2.1.1 of
the IBC to read:
Exception: Sound pressure levels in Group I-3 occupancies shall be permitted to be limited to only the notification of occupants in the affected smoke compartment.
P. Delete Exception 1 from Section 907.5.2.3 of the IBC.
R. Q. Change Section 909.6 of the IBC to read:
909.6 Pressurization method. When approved by the building official, the means of controlling smoke shall be permitted by pressure differences across smoke barriers. Maintenance of a tenable environment is not required in the smoke-control zone of fire origin.
S. R. Change Section 911.1.3 of the IBC to read:
911.1.3 Size. The fire command center shall be a minimum of 96 square feet (9 m2) in area with a minimum dimension of eight feet (2438 mm).
Exception: Where it is determined by the building official,
after consultation with the fire chief official, that specific
building characteristics require a larger fire command center, the building
official may increase the minimum required size of the fire command center up
to 200 square feet (19 m2) in area with a minimum dimension of up to
10 feet (3048 mm).
S. Delete Section 912.2.2 of the IBC.
T. Change Sections 912.4 and 912.4.2 of the IBC to read:
912.4 Access. Immediate access to fire department connections
shall be provided without obstruction by fences, bushes, trees, walls or any
other fixed or moveable object. Access to fire department connections shall be
approved by the fire chief official.
Exception: Fences, where provided with an access gate equipped
with a sign complying with the legend requirements of this section and a means
of emergency operation. The gate and the means of emergency operation shall be
approved by the fire chief official.
912.4.2 Clear space around connections. A working space of not
less than 36 inches (762 mm) in width, 36 inches (914 mm) in depth and 78
inches (1981 mm) in height shall be provided in front of and to the sides of
wall-mounted fire department connections and around the circumference of
free-standing fire department connections, except as otherwise required or
approved by the fire chief official.
U. Replace Section 915 of the IBC with the following:
915.1 Carbon monoxide alarms. Carbon monoxide alarms shall comply with this section.
915.2 Group I or R. Group I or R occupancies located in a building containing a fuel-burning appliance or in a building that has an attached garage shall be equipped with single-station carbon monoxide alarms. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720 and the manufacturer's instructions. An open parking garage, as defined in Chapter 2, or an enclosed parking garage ventilated in accordance with Section 404 of the IMC shall not be considered an attached garage.
Exception: Sleeping units or dwelling units that do not themselves contain a fuel-burning appliance or have an attached garage but that are located in a building with a fuel-burning appliance or an attached garage, need not be equipped with single-station carbon monoxide alarms provided that:
1. The sleeping unit or dwelling unit is located more than one story above or below any story that contains a fuel-burning appliance or an attached garage;
2. The sleeping unit or dwelling unit is not connected by duct work or ventilation shafts to any room containing a fuel-burning appliance or to an attached garage; and
3. The building is equipped with a common area carbon monoxide alarm system.
915.3 Group E. Classrooms in Group E occupancies located in a building containing a fuel-burning appliance or in a building that has an attached garage or small engine or vehicle shop shall be equipped with single-station carbon monoxide alarms. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720 and the manufacturer's instructions. An open parking garage, as defined in Chapter 2, or an enclosed parking garage ventilated in accordance with Section 404 of the IMC shall not be considered an attached garage.
Exception: Classrooms that do not themselves contain a fuel-burning appliance or have an attached garage but are located in a building with a fuel-burning appliance or an attached garage, need not be equipped with single-station carbon monoxide alarms provided that:
1. The classroom is located more than 100 feet from the fuel burning appliance or attached garage or located more than one story above or below any story which contains a fuel-burning appliance or attached garage; and
2. The classroom is not connected by duct work or ventilation shafts to any room containing a fuel-burning appliance.
915.4 Carbon monoxide detection systems. Carbon monoxide detection systems, which include carbon monoxide detectors and audible notification appliances, installed and maintained in accordance with this section for carbon monoxide alarms and NFPA 720 shall be permitted. The carbon monoxide detectors shall be listed as complying with UL 2075.
V. Change the title of IBC Section 916 918 to
read:
In-Building Emergency Communications Coverage.
W. Change Section 916.1 918.1 of the IBC to
read:
916.1 918.1 General. For localities utilizing
public safety wireless communications, dedicated infrastructure to accommodate
and perpetuate continuous in-building emergency communication equipment to
allow emergency public safety personnel to send and receive emergency
communications shall be provided in new buildings and structures in accordance
with this section.
Exceptions:
1. Buildings of Use Groups A-5, I-4, within dwelling units of R-2, R-3, R-4, R-5, and U.
2. Buildings of Types IV and V construction without basements, that are not considered unlimited area buildings in accordance with Section 507.
3. Above grade single story buildings of less than 20,000 square feet.
4. Buildings or leased spaces occupied by federal, state, or local governments, or the contractors thereof, with security requirements where the building official has approved an alternative method to provide emergency communication equipment for emergency public safety personnel.
5. Where the owner provides technological documentation from a qualified individual that the structure or portion thereof does not impede emergency communication signals.
6. Buildings in localities that do not provide the additional communication equipment required for the operation of the system.
X. Add Sections 916.1.1 918.1.1, 916.1.2 918.1.2,
and 916.1.3 918.1.3 to the IBC to read:
916.1.1 918.1.1 Installation. The building owner
shall install radiating cable, such as coaxial cable or equivalent. The
radiating cable shall be installed in dedicated conduits, raceways, plenums,
attics, or roofs, compatible for these specific installations as well as other
applicable provisions of this code. The locality shall be responsible for the
installation of any additional communication equipment required for the
operation of the system.
916.1.2 918.1.2 Operations. The locality will
assume all responsibilities for the operation and maintenance of the emergency
communication equipment. The building owner shall provide sufficient
operational space within the building to allow the locality access to and the
ability to operate in-building emergency communication equipment.
916.1.3 918.1.3 Inspection. In accordance with
Section 113.3, all installations shall be inspected prior to concealment.
Y. Add Section 916.2 918.2 to the IBC to read:
916.2 918.2 Acceptance test. Upon completion of
installation, after providing reasonable notice to the owner or their representative,
emergency public safety personnel shall have the right during normal business
hours, or other mutually agreed upon time, to enter onto the property to
conduct field tests to verify that the required level of radio coverage is
present at no cost to the owner. Any noted deficiencies in the installation of
the radiating cable or operational space shall be provided in an inspection
report to the owner or the owner's representative.
13VAC5-63-245. Chapter 10 Means of egress.
A. Delete Section 1001.4 1002.2 of the IBC.
B. Change Section 1004.3 1004.9 of the IBC to
read:
1004.3 1004.9 Posting of occupant load. Every room
or space that is an assembly occupancy and where the occupant load of that room
or space is 50 or more shall have the occupant load of the room or space posted
for the intended configurations in a conspicuous place, near the main
exit or exit access doorway from the room or space. Posted signs shall be of an
approved legible permanent design and shall be maintained by the owner or the
owner's authorized agent.
C. Change Exception 1 of Section 1005.3.1 of the IBC to read:
1. For other than Groups H and I-2 occupancies, the capacity, in inches (mm), of means of egress stairways shall be calculated by multiplying the occupant load served by such stairway by a means of egress capacity factor of 0.2 inch (5.1 mm) per occupant in buildings equipped with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
D. Change Exception 1 of Section 1005.3.2 of the IBC to read:
1. For other than Groups H and I-2 occupancies, the capacity, in inches (mm), of means of egress components other than stairways shall be calculated by multiplying the occupant load served by such component by a means of egress capacity factor of 0.15 inch (3.8 mm) per occupant in buildings equipped with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
E. Change Add Exception 1 3 of
Section 1006.2.1 of the IBC to read:
1. 3. In Group R-2 and R-3 occupancies, one
means of egress is permitted within and from individual dwelling units with a
maximum occupant load of 20 where the dwelling unit is equipped throughout with
an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2
and the common path of egress travel does not exceed 125 feet (38 100 (38,100
mm). This exception shall also apply to Group R-2 occupancies where Section
903.2.8, Exception 1 or 2 is applicable.
F. Change the number "49" to "50" in the "Maximum Occupant Load of Space" column in the "Ac, E, M," "B," "F," and "U" rows of Table 1006.2.1 of the IBC.
G. Change the number "49" to "50" in the
"Maximum Occupant Load per Story" column of the "A, Bb,
E, Fb, M, U" row of Table 1006.3.2(2) 1006.3.3(2).
H. Change Exception 2 of Section 1007.1.1 of the IBC to read:
2. Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, the separation distance of the exit doors or exit access doorways shall not be less than one-fourth of the length of the maximum overall diagonal dimension of the area served.
I. Change Section 1009.6.4 of the IBC to read:
1009.6.4 Separation. Each area of refuge shall be separated from the remainder of the story by a smoke barrier complying with Section 709 or a horizontal exit complying with Section 1026. Each area of refuge shall be designed to minimize the intrusion of smoke.
Exceptions:
1. Areas of refuge located within an enclosure for interior exit stairways complying with Section 1023.
2. Areas of refuge in outdoor facilities where exit access is essentially open to the outside.
3. Areas of refuge where the area of refuge and areas served by the area of refuge are equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
J. Change Section 1010.1.4.4 of the IBC to read:
1010.1.4.4 Locking arrangements in educational occupancies. In Group E occupancies, except Group E day care facilities, and Group B educational occupancies, exit access doors from classrooms, offices, and other occupied rooms, except for exit doors and doors across corridors, shall be permitted to be provided with emergency supplemental hardware where all of the following conditions are met:
1. The door shall be capable of being opened from outside the room with a key, proprietary device provided by the manufacturer, or other approved means.
2. The door shall be openable from within the room in accordance with Section 1010.1.9, except emergency supplemental hardware is not required to comply with Chapter 11.
Note: School officials should consult with their legal counsel regarding provisions of the Americans with Disabilities Act of 1990 (42 USC § 12101 et seq.) and any other applicable requirements.
3. Installation of emergency supplemental hardware on fire door assemblies must comply with Section 716.2. Modifications shall not be made to listed panic hardware, fire door hardware, or door closures.
4. The emergency supplemental hardware shall not be capable of being used on other doors not intended to be used and shall have at least one component that requires modification to, or is permanently affixed to, the surrounding wall, floor, door, or frame assembly construction for it to properly function.
5. Employees shall engage in lockdown training procedures on how to deploy and remove the emergency supplemental hardware, and its use shall be incorporated in the approved lockdown plan complying with the SFPC.
6. The emergency supplemental hardware and its components shall be maintained in accordance with the SFPC.
7. Approved emergency supplemental hardware shall be of consistent type throughout a building.
Exception: The building official may approve alternate types of emergency supplemental hardware in accordance with Section 110.1 when a consistent device cannot be installed.
K. Add an exception to Sections 1010.1.9 and 1010.1.9.1 of the IBC to read:
Exception: Emergency supplemental hardware provided in accordance with Section 10101.1.4.4.
L. Change Section 1010.1.9.2 of the IBC to read:
1010.1.9.2 Hardware height. Door handles, pulls, latches, locks, and other operating devices shall be installed 34 inches (864 mm) minimum and 48 inches (1219 mm) maximum above the finished floor. Emergency supplemental hardware provided in accordance with Section 1010.1.4.4, shall be installed 48 inches (1219 mm) maximum above the finished floor. Locks used only for security purposes and not used for normal operation are permitted at any height.
Exception: Access doors or gates in barrier walls and fences protecting pools, spas, and hot tubs shall be permitted to have operable parts of the latch release on self-latching devices at 54 inches (1370 mm) maximum above the finished floor or ground, provided that the self-latching devices are not also self-locking devices operated by means of a key, electronic opener, or integral combination lock.
M. Change Item 2 of Section 1010.1.9.3 1010.1.9.4
of the IBC to read:
2. In buildings in occupancy Groups B, F, M and S, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.1. The locking device is readily distinguishable as locked.
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED. The sign shall be in letters one inch (25 mm) high on a contrasting background.
2.3. The use of the key-operated locking device is revokable by the building official for due cause.
N. Add Items 7, 7.1, and 7.2 to Section 1010.1.9.4 of the IBC to read:
7. Egress doors equipped with emergency supplemental hardware complying with Section 1010.1.4.4, from the egress side provided:
7.1. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS HARDWARE SHALL BE USED BY AUTHORIZED PERSONNEL ONLY. The sign shall be in letters 1 inch (25 mm) high on a contrasting background.
7.2. The use of the emergency supplemental hardware is revocable by the building official or fire official for due cause.
O. Add Item 6 to Section 1010.1.9.5 of the IBC to read:
6. Emergency supplemental hardware provided in accordance with Section 1010.1.4.4.
P. Add Item 5 to Section 1010.1.9.6 of the IBC to read:
5. One additional operation shall be permitted for release of emergency supplemental hardware provided in accordance with Section 1010.1.4.4.
K. Q. Delete Section 1010.1.9.6 1010.1.9.7
of the IBC.
L. R. Add an exception Exceptions 2
and 3 to Section 1010.1.9.7 1010.1.9.8 of the IBC to read:
Exception Exceptions:
2. Approved, listed, delayed egress locks shall be permitted to be installed on doors serving Group A-3 airport facilities, provided they are installed in accordance with this section.
3. Emergency supplemental hardware shall not be considered a delayed egress locking system.
M. S. Change Section 1010.1.6 of the IBC to
read:
1010.1.6 Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches (178 mm). Where a landing serves an occupant load of 50 or more, other doors, gates, or turnstiles in any position shall not reduce the landing to less than one-half its required width nor prevent a door, gate, or turnstile from opening to less than one-half of the required landing width. Landings shall have a length measured in the direction of travel of not less than 44 inches (1118 mm).
Exception: Landing length in the direction of travel in Groups R-3 and U and within individual units of Group R-2 need not exceed 36 inches (914 mm).
N. Change T. Delete Exception 1 and change Exception
2 of Section 1010.1.10 of the IBC to read:
1010.1.10 Panic and fire exit hardware. Doors serving a
Group H occupancy and doors serving rooms or spaces with an occupant load of 50
or more in a Group A or E occupancy shall not be provided with a latch or lock
other than panic hardware or fire exit hardware.
Exception: Doors serving a provided with panic
hardware or fire exit hardware and serving a Group A or E occupancy shall
be permitted to be electromagnetically electrically locked in
accordance with Section 1010.1.9.9 1010.1.9.10.
O. U. Add Section 1010.1.11 to the IBC to read:
1010.1.11 Locking certain residential sliding doors. In dwelling units of Group R-2 buildings, exterior sliding doors which are one story or less above grade, or shared by two dwelling units, or are otherwise accessible from the outside, shall be equipped with locks. The mounting screws for the lock case shall be inaccessible from the outside. The lock bolt shall engage the strike in a manner that will prevent it from being disengaged by movement of the door.
Exception: Exterior sliding doors which are equipped with removable metal pins or charlie bars.
P. V. Add Section 1010.1.12 to the IBC to read:
1010.1.12 Door viewers in certain residential buildings. Entrance doors to dwelling units of Group R-2 buildings shall be equipped with door viewers with a field of vision of not less than 180 degrees.
Exception: Entrance doors having a vision panel or side vision panels.
Q. W. Change Exception 3 of Section 1011.5.2 of
the IBC to read:
3. In Group R-3 occupancies; within dwelling units in Group R-2 occupancies; and in Group U occupancies that are accessory to a Group R-3 occupancy or accessory to individual dwelling units in Group R-2 occupancies; the maximum riser height shall be 8.25 inches (210 mm); the minimum tread depth shall be 9 inches (229 mm); the minimum winder tread depth at the walk line shall be 10 inches (254 mm); and the minimum winder tread depth shall be 6 inches (152 mm). A nosing not less than 0.75 inch (19.1 mm) but not more than 1.25 inches (32 mm) shall be provided on stairways with solid risers where the tread depth is less than 11 inches (279 mm).
R. Change X. Delete Exception 4 from Section
1011.5.2 of the IBC.
Y. Add Exception 2 to Section 1011.6 of the IBC to read:
1011.6 Stairway landings. There shall be a floor or landing
at the top and bottom of each stairway. The width of landings shall be not less
than the width of stairways served. Every landing shall have a minimum width
measured perpendicular to the direction of travel equal to the width of the
stairway. Where the stairway has a straight run the depth need not exceed 48
inches (1219 mm). Doors opening onto a landing shall not reduce the landing to
less than one-half the required width. When fully open, the door shall not
project more than 7 inches (178 mm) into a landing. Where wheelchair spaces are
required on the stairway landing in accordance with Section 1009.6.3, the wheelchair
space shall not be located in the required width of the landing and doors shall
not swing over the wheelchair spaces.
Exceptions:
1. Where stairways connect stepped aisles to cross aisles
or concourses, stairway landings are not required at the transition between
stairways and stepped aisles constructed in accordance with Section 1029.
2. A floor or landing is not required at the top of an interior flight of exit access stairs within individual dwelling units and sleeping units of Group R-2 occupancies and dwelling units of Group R-3 occupancies, including stairs in an enclosed private garage serving only an individual dwelling unit, provided that a door does not swing over the stairs.
S. Change Z. Delete Item 6 from Section 1011.16
of the IBC to read:.
1011.16 Ladders. Permanent ladders shall not serve as a part
of the means of egress from occupied spaces within a building. Permanent
ladders shall be permitted to provide access to the following areas:
1. Spaces frequented only by personnel for maintenance,
repair, or monitoring of equipment.
2. Nonoccupiable spaces accessed only by catwalks, crawl
spaces, freight elevators, or very narrow passageways.
3. Raised areas used primarily for purposes of security,
life safety, or fire safety including observation galleries, prison guard
towers, fire towers, or lifeguard stands.
4. Elevated levels in Group U not open to the general
public.
5. Nonoccupied roofs that are not required to have stairway
access in accordance with Section 1011.12.1.
T. AA. Change Section 1015.8 of the IBC to read:
1015.8 Window openings. Windows in Group Groups
R-2 and R-3 buildings including dwelling units where the top of the sill of an
operable window opening is located less than 18 inches (457 mm) above the
finished floor and more than 72 inches (1829 mm) above the finished grade or
other surface below on the exterior of the building shall comply with one of
the following:
1. Operable windows where the top of the sill of the opening
is located more than 75 feet (22 860 (22,860 mm) above the
finished grade or other surface below and that are provided with window fall
prevention devices that comply with ASTM F 2006.
2. Operable windows where the openings will not allow a 4-inch diameter (102 mm) sphere to pass through the opening when the window is in its largest opened position.
3. Operable windows where the openings are provided with window fall prevention devices that comply with ASTM F 2090.
4. Operable windows that are provided with window opening control devices that comply with Section 1015.8.1.
U. BB. Add Exception 3 to Item 5 of Section
1016.2 of the IBC to read:
3. A maximum of one exit access is permitted to pass through kitchens, store rooms, closets or spaces used for similar purposes provided such a space is not the only means of exit access.
V. CC. Change the following rows and delete
footnote "b" in Table 1020.1 of the IBC to read:.
|
Table 1020.1 |
|||
|
Occupancy |
Occupant Load Served By Corridor |
Required Fire-Resistance Rating (hours) |
|
|
Without sprinkler system |
With sprinkler systemb |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R |
Greater than 10 |
1 |
0.5 |
|
|
|
|
|
|
I-1, I-3 |
All |
Not Permitted |
0 |
|
|
W. DD. Add an additional row to Table 1020.2 of
the IBC to read:
|
Occupancy |
Width (minimum) |
|
In corridors of Group I-2 assisted living facilities licensed by the Virginia Department of Social Services serving areas with wheelchair, walker, and gurney traffic where residents are capable of self-preservation or where resident rooms have a means of egress door leading directly to the outside. |
44 inches |
X. Change EE. Add Exception 2 to Section 1023.5
of the IBC to read:
1023.5 Penetrations. Penetrations into or through interior
exit stairways and ramps are prohibited except for equipment and ductwork
necessary for independent ventilation or pressurization, sprinkler piping,
standpipes, electrical raceway for fire department communication systems, and
electrical raceway serving the interior exit stairway and ramp and terminating
at a steel box not exceeding 16 square inches (0.010 m2). Such
penetrations shall be protected in accordance with Section 714. There shall not
be penetrations or communication openings, whether protected or not, between
adjacent interior exit stairways and ramps.
Exceptions:
1. Membrane penetrations shall be permitted on the outside
of the interior exit stairway and ramp. Such penetrations shall be protected in
accordance with Section 714.3.2.
2. For buildings in other than Group H, with no more than two stories above grade plane and are equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1, structural members, other than columns, that are part of the primary structural frame supporting the roof sheathing, roof slab or roof deck only and structural members that are secondary members supporting the roof sheathing, roof slab or roof deck only, shall be permitted to penetrate an interior exit stairway enclosure or a ramp enclosure. Such penetrations shall be protected in accordance with Section 714.
Y. FF. Change Section 1023.9 of the IBC to read:
1023.9 Floor identification signs. A sign shall be provided at each floor landing in exit enclosures connecting more than three stories designating the floor level, the terminus of the top and bottom of the exit enclosure and the identification of the stair or ramp by designation with a letter of the alphabet. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the enclosure for the fire department. The sign shall be located five feet (1524 mm) above the floor landing in a position that is readily visible when the doors are in the open and closed positions. Floor level identification signs in tactile characters complying with ICC A117.1 shall be located at each floor level landing adjacent to the door leading from the enclosure into the corridor to identify the floor level.
Z. Change GG. Add Exception 2 to Section 1024.6
of the IBC to read:
1024.6 Penetrations. Penetrations into or through an exit
passageway are prohibited except for equipment and ductwork necessary for
independent pressurization, sprinkler piping, standpipes, electrical raceway
for fire department communication and electrical raceway serving the exit
passageway and terminating at a steel box not exceeding 16 square inches (0.010
m2). Such penetrations shall be protected in accordance with Section
714. There shall not be penetrations or communicating openings, whether
protected or not, between adjacent exit passageways.
Exceptions:
1. Membrane penetrations shall be permitted on the outside
of the exit passageway. Such penetrations shall be protected in accordance with
Section 714.3.2.
2. For buildings in other than Group H, with no more than two stories above grade plane and are equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1, structural members, other than columns, which are part of the primary structural frame supporting the roof sheathing, roof slab or roof deck only and structural members which are secondary members supporting the roof sheathing, roof slab or roof deck only, shall be permitted to penetrate an interior exit stairway enclosure or a ramp enclosure. Such penetrations shall be protected in accordance with Section 714.
AA. HH. Change Section 1025.1 of the IBC to
read:
1025.1 General. Approved luminous egress path markings
delineating the exit path shall be provided in buildings of Groups A, B, E, I,
M and R-1 having occupied floors located more than 420 feet (128 016 (128,016
mm) above the lowest level of fire department vehicle access in accordance with
Sections 1025.1 through 1025.5 this section.
Exception: Luminous egress path markings shall not be required on the level of exit discharge in lobbies that serve as part of the exit path in accordance with Section 1028.1, Exception 1.
BB. II. Change Section 1026.2 of the IBC to read:
1026.2 Separation. The separation between buildings or refuge areas connected by a horizontal exit shall be provided by a fire wall complying with Section 706, by a fire barrier complying with Section 707 or a horizontal assembly with Section 711, or by both. The minimum fire-resistance rating of the separation shall be two hours. Opening protectives in horizontal exits shall also comply with Section 716. Duct and air transfer openings in a fire wall or fire barrier that servers as a horizontal exit shall also comply with Section 717. The horizontal exit separation shall extend vertically through all levels of the building unless floor assemblies have a fire-resistance rating of not less than two hours. Openings in horizontal assemblies on the story served by horizontal exits shall be protected in accordance with Sections 712.1.1, 712.1.3, 712.1.13, and 1019.3.4.
Exception: A fire-resistance rating is not required at horizontal exits between a building area and an above-grade pedestrian walkway constructed in accordance with Section 3104, provided that the distance between connected buildings is more than 20 feet (6096).
Horizontal exits constructed as fire barriers shall be continuous from exterior wall to exterior wall as to divide completely the floor served by the horizontal exit.
Change Section 1030.1 of the IBC to read:
1030.1 General. In addition to the means of egress required
by this chapter, provisions shall be made for emergency escape and rescue
openings in Group R-2 occupancies in accordance with Tables 1006.3.2(1) and
1006.3.2(2) and in Group R-3 and R-4 occupancies. Basements and sleeping rooms
below the fourth story above grade plane shall have at least one exterior
emergency escape and rescue opening in accordance with this section. Where
basements contain one or more sleeping rooms, emergency escape and rescue
openings shall be required in each sleeping room, but shall not be required in
adjoining areas of the basement. Such openings shall open directly into a
public way or to a yard or court that opens to a public way.
Exceptions:
1. Basements with a ceiling height of less than 80 inches
(2032 mm) shall not be required to have emergency escape and rescue openings.
2. Emergency escape and rescue openings are not required
from basements or sleeping rooms that have an exit door or exit access door
that opens directly into a public way or to a yard, court or exterior exit
balcony that opens to a public way.
3. Basements without habitable spaces and having not more
than 200 square feet (18.6 m2) in floor area shall not be required
to have emergency escape and rescue openings.
JJ. Delete the last sentence from Section 1030.5.
13VAC5-63-250. Chapter 11 Accessibility.
A. Add an exception to Section 1101.2 1102.1 of
the IBC to read:
Exception: Wall-mounted visible alarm notification appliances in Group I-3 occupancies shall be permitted to be a maximum of 120 inches (3048 mm) above the floor or ground, measured to the bottom of the appliance. Such appliances shall otherwise comply with all applicable requirements.
B. Change Section to 1103.2.8 of the IBC to read:
1103.2.8 Raised and lowered areas in places of religious worship.
Raised or lowered areas, or portions of areas, in places of religious
worship are not required to be accessible or to be served by an accessible
route, provided such areas are used exclusively primarily
for the performance of religious ceremonies and are located within an
accessible story or mezzanine.
C. Add Section 1103.2.15 to the IBC to read:
1103.2.15 Emergency supplemental hardware. In Group E occupancies, except Group E day care facilities, and Group B educational occupancies, when emergency supplemental hardware is deployed during an active shooter or hostile threat event and provided in accordance with Section 1010.1.4.4.
D. Change Section 1106.1 of the IBC and replace Table 1106.1 of the IBC with Tables 1106.1(1) and 1106.1(2) to read:
1106.1 Required. Where parking is provided, accessible parking spaces shall be provided in compliance with Tables 1106.1(1) and 1106.1(2), as applicable, except as required by Sections 1106.2 through 1106.4. Where more than one parking facility is provided on a site, the number of parking spaces required to be accessible shall be calculated separately for each parking facility. Exception: This section does not apply to parking spaces used exclusively for buses, trucks, other delivery vehicles, law-enforcement vehicles, or vehicular impound and motor pools where lots accessed by the public are provided with an accessible passenger loading zone.
|
Table 1106.1(1) |
|
|
Total Parking Spaces Provided |
Required Minimum Number of Accessible Spaces |
|
1 - 25 |
1 |
|
26 - 50 |
2 |
|
51 - 75 |
3 |
|
76 - 100 |
4 |
|
101 - 125 |
5 |
|
126 - 150 |
6 |
|
151 - 200 |
7 |
|
201 - 300 |
8 |
|
301 - 400 |
9 |
|
401 - 500 |
10 |
|
501 - 1,000 |
2.33% of total |
|
1,001 and over |
23, plus one for each 100, or fraction thereof, over 1,000 |
|
a. Condominium parking in Group R-2 occupancies where parking is part of the unit purchase shall be in accordance with Table 1106.1(2). |
|
Table 1106.1(2) |
|
|
Total Parking Spaces Provided |
Required Minimum Number of Accessible Spaces |
|
1 - 25 |
1 |
|
26 - 50 |
2 |
|
51 - 75 |
3 |
|
76 - 100 |
4 |
|
101 - 150 |
5 |
|
151 - 200 |
6 |
|
201 - 300 |
7 |
|
301 - 400 |
8 |
|
401 - 500 |
9 |
|
501 - 1,000 |
2.0% of total |
|
1,001 and over |
20, plus one for each 100, or fraction thereof, over 1,000 |
D. E. Add Section 1106.8 to the IBC to read:
1106.8 Identification of accessible parking spaces. In addition to complying with applicable provisions of this chapter, all accessible parking spaces shall be identified by above grade signs. A sign or symbol painted or otherwise displayed on the pavement of a parking space shall not constitute an above grade sign. All above grade parking space signs shall have the bottom edge of the sign no lower than four feet (1219 mm) nor higher than seven feet (2133 mm) above the parking surface. All disabled parking signs shall include the following language: PENALTY, $100-500 Fine, TOW-AWAY ZONE. Such language may be placed on a separate sign and attached below existing above grade disabled parking signs, provided that the bottom edge of the attached sign is no lower than four feet above the parking surface.
E. F. Add Sections 1109.16 and 1109.16.1 to the
IBC to read:
1109.16 Dwellings containing universal design features for accessibility. Group R-5 occupancies not subject to Section R320.1 of the IRC and Group R-3 occupancies not subject to Section 1107.6.3 may comply with this section and be approved by the local building department as dwellings containing universal design features for accessibility.
1109.16.1 Standards for dwellings containing universal design features for accessibility. When the following requirements are met, approval shall be issued by the local building department indicating that a dwelling has been constructed in accordance with these standards and is deemed to be a dwelling containing universal design features for accessibility.
1. The dwelling must comply with the requirements for Type C units under Section 1005 of ICC A117.1 with the following changes to those requirements:
1.1. That at least one bedroom be added to the interior spaces required by Section 1005.4 of ICC A117.1.
1.2. In the toilet room or bathroom required by Section 1005 of ICC A117.1, in addition to the lavatory and water closet, a shower or bathtub complying with Section 1004.11.3.2.3 of ICC A117.1 shall be provided and shall include reinforcement for future installation of grab bars in accordance with Section 1004.11.1 of ICC A117.1.
1.3. That the exception to Section 1005.4 of ICC A117.1 is not applicable.
1.4. That there be a food preparation area complying with Section 1005.7 of ICC A117.1 on the entrance level.
1.5. That any thermostat for heating or cooling on the entrance
level comply with Section 1005.8 1002.9 of ICC A117.1.
F. Change G. Delete the exception for Item 1 of
Section 1111.1 of the IBC to read:.
1. Accessible parking spaces required by Section 1106.1.
13VAC5-63-260. Chapter 12 Interior environment.
A. Add the following to the list of terms in Section 1202.1
of the IBC:
Day-night average sound level (Ldn).
Sound transmission class (STC) rating.
B. A. Add Section 1203.5.4 1202.5.4
to the IBC to read:
1203.5.4 1202.5.4 Insect screens in occupancies
other than Group R. Every door, window and other outside opening for natural
ventilation serving structures classified as other than a residential group
containing habitable rooms, food preparation areas, food service areas, or any
areas where products to be included or utilized in food for human consumption
are processed, manufactured, packaged, or stored, shall be supplied with
approved tightly fitting screens of not less than 16 mesh per inch (16 mesh per
25 mm) and every screen door used for insect control shall have a self-closing
device.
Exception: Screen doors shall not be required for out swinging doors or other types of openings which make screening impractical, provided other approved means, such as air curtains or insect repellent fans are provided.
C. B. Add Section 1203.5.5 1202.5.5
to the IBC to read:
1203.5.5 1202.5.5 Insect screens in Group R
occupancies. Every door, window and other outside opening required for natural
ventilation purposes which serves a structure classified as a residential group
shall be supplied with approved tightly fitted screens of not less than 16 mesh
per inch (16 mesh per 25 mm) and every screen door used for insect control
shall have a self-closing device.
D. C. Add Section 1203.7 1202.7 to
the IBC to read:
1203.7 1202.7 Smoking areas in restaurants.
Smoking areas in restaurants, as defined in § 15.2-2820 of the Code of
Virginia, shall comply with the following:
1. The area where smoking may be permitted shall be structurally separated from the portion of the restaurant in which smoking is prohibited. For the purposes of this section, structurally separated means a stud wall covered with drywall or other building material or like barrier, which, when completed, extends from the floor to the ceiling, resulting in a physically separated room. Such wall or barrier may include portions that are glass or other gas-impervious building material and shall be permitted to have a door leading to areas in which smoking is prohibited, provided the door is capable of being closed at all times.
2. The area where smoking may be permitted shall be separately vented to prevent the recirculation of air from such area to the area of the restaurant where smoking is prohibited.
Exception: The above requirements do not apply if a restaurant is exempt from, or meets any of the exceptions to, the Virginia Indoor Clean Air Act (Chapter 28.2 of Title 15.2 (§ 15.2-2820 et seq.) of the Code of Virginia).
E. D. Change Section 1207.1 1206.1
of the IBC to read:
1207.1 1206.1 Scope. Sections 1207.2 1206.2
and 1207.3 1206.3 shall apply to common interior walls,
partitions and floor/ceiling floor or ceiling assemblies between
adjacent dwelling units or between dwelling units and adjacent public areas
such as halls, corridors, stairs or service areas. Section 1207.4 1206.4
applies to the construction of the exterior envelope of Group R occupancies
within airport noise zones and to the exterior envelope of Group Groups
A, B, E, I and M occupancies in any locality in whose jurisdiction, or adjacent
jurisdiction, is located a United States Master Jet Base, a licensed airport or
United States government or military air facility, when such requirements are
enforced by a locality pursuant to § 15.2-2295 of the Code of Virginia.
F. E. Add Section 1207.4 1206.4 to
the IBC to read:
1207.4 1206.4 Airport noise attenuation
standards. Where the Ldn is determined to be 65 dBA or greater, the minimum STC
rating of structure components shall be provided in compliance with Table 1207.4
1206.4. As an alternative to compliance with Table 1207.4 1206.4,
structures shall be permitted to be designed and constructed so as to limit the
interior noise level to no greater than 45 Ldn. Exterior structures, terrain
and permanent plantings shall be permitted to be included as part of the
alternative design. The alternative design shall be certified by an RDP.
G. F. Add Table 1207.4 1206.4 to
the IBC to read:
|
Table |
||
|
Ldn |
STC of exterior walls and roof/ceiling assemblies |
STC of doors and windows |
|
6569 |
39 |
25 |
|
7074 |
44 |
33 |
|
75 or greater |
49 |
38 |
13VAC5-63-264. Chapter 13 Energy efficiency.
Add Section 1301.1.1.1 to the IBC to read:
1301.1.1.1 Changes to the IECC. The following changes shall be made to the IECC:
1. Change the SHGC for Climate Zone 4 (Except Marine) of Table C402.4 to read:
Table C402.4 Building Envelope Requirements: Fenestration |
||||||||
Climate Zone |
|
|
|
4 (Except Marine) |
|
|
|
|
|
||||||||
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SHGC |
||||||||
SHGC |
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2. Change Section C402.4.3 to read:
C402.4.3 Maximum U-factor and SHGC. The maximum U-factor and solar heat gain coefficient (SHGC) for fenestration shall be as specified in Table C402.4.
The window projection factor shall be determined in accordance with Equation 4-5.
(Equation 4-5)
PF = A/B
where:
PF = Projection factor (decimal).
A = Distance measured horizontally from the farthest continuous extremity of any overhand, eave, or permanently attached shading device to the vertical surface of the glazing.
B = Distance measured vertically from the bottom of the glazing to the underside of the overhang, eave, or permanently attached shading device.
Where different windows or glass doors have different PF values, they shall each be evaluated separately.
Where the fenestration projection factor for a specific vertical fenestration product is greater than or equal to 0.20, the required maximum SHGC from Table C402.4 shall be adjusted by multiplying the required maximum SHGC by the multiplier specified in Table C402.4.3 corresponding with the orientation of the fenestration product and the projection factor.
3. Add Table C402.4.3 to read:
Table C402.4.3 SHGC Adjustment Multipliers |
||
Projection factor |
Oriented within 45 degrees of true north |
All other orientations |
0.2 ≤ PF < 0.5 |
1.1 |
1.2 |
PF ≤ 0.5 |
1.2 |
1.6 |
4. Add an exception to the first paragraph of Section C403.2.4.3
403.7.7 to read:
Exception: Any grease duct serving a Type I hood installed in accordance with IMC Section 506.3 shall not be required to have a motorized or gravity damper.
5. Add Section C403.2.6.3 C403.2.2.1 to read:
C403.2.6.3 C403.2.2.1 Dwelling unit mechanical
ventilation. Mechanical ventilation shall be provided for dwelling units in
accordance with the IMC.
6. Delete Section C403.7.5 and Table C403.7.5.
7. Change Section C405.5 C405.4 to read:
C405.5 C405.4 Exterior lighting (Mandatory). All
exterior lighting, other than low-voltage landscape lighting, shall comply with
Section C405.5.1 C405.4.1.
Exception: Where approved because of historical, safety, signage, or emergency considerations.
7. 8. Change Section R401.2 to read:
R401.2 Compliance. Projects shall comply with all provisions of Chapter 4 labeled "Mandatory" and one of the following:
1. Sections R401 through R404.
2. Section R405.
3. Section R406.
4. The most recent version of REScheck, keyed to the 2015
2018 IECC.
Note: See REScheck compliance guidance issued by DHCD,
available at the Department's website.
8. Delete 9. Change Section R401.3. to
read:
R401.3 A permanent certificate shall be completed by the builder or other approved party and posted on a wall in the space where the furnace is located, a utility room or an approved location inside the building. Where located on an electrical panel, the certificate shall not cover or obstruct the visibility of the circuit directory label, service disconnect label, or other required labels. Where approved, certificates for multi-family dwelling units shall be permitted to be located off-site at an identified location. The certificate shall indicate the predominant R-values of insulation installed in or on ceilings, roofs, walls, foundation components such as slabs, basement walls, crawl space walls and floors, and ducts outside conditioned spaces; U-factors of fenestration and the solar heat gain coefficient (SHGC) of fenestration; and the results from any required duct system and building envelope air leakage testing performed on the building. Where there is more than one value for each component, the certificate shall indicate the value covering the largest area. The certificate shall indicate the types and efficiencies of heating, cooling, and service water heating equipment. Where a gas-fired unvented room heater, electric furnace, or baseboard electric heater is installed in the residence, the certificate shall indicate "gas-fired unvented room heater," "electric furnace," or "baseboard electric heater," as appropriate. An efficiency shall not be indicated for gas-fired unvented room heaters, electric furnaces, and electric baseboard heaters.
9. 10. Change the ceiling R-value and wood frame
wall R-value categories for climate zone "4 except Marine" Climate
Zone 4 (Except Marine) in Table R402.1.2 to read:
|
Ceiling R-Value |
Wood Frame Wall R-Value |
|
38 |
15 or 13 + 1h |
10. 11. Change the ceiling U-factor and frame
wall U-factor categories for climate zone "4 except Marine" Climate
Zone 4 (Except Marine) in Table R402.1.4 to read:
|
Ceiling U-Factor |
Frame Wall U-Factor |
|
0.030 |
0.079 |
11. 12. Change Section R402.2.4 to read:
R402.2.4 Access hatches and doors. Access doors from conditioned spaces to unconditioned spaces (e.g., attics and crawl spaces) shall be weatherstripped and insulated in accordance with the following values:
1. Hinged vertical doors shall have a minimum overall R-5 insulation value;
2. Hatches and scuttle hole covers shall be insulated to a level equivalent to the insulation on the surrounding surfaces; and
3. Pull down stairs shall have a minimum of 75% of the panel area having R-5 rigid insulation.
Access shall be provided to all equipment that prevents damaging or compressing the insulation. A wood framed or equivalent baffle or retainer is required to be provided when loose fill insulation is installed, the purpose of which is to prevent the loose fill insulation from spilling into the living space when the attic access is opened and to provide a permanent means of maintaining the installed R-value of the loose fill insulation.
12. 13. Change Sections R402.4 and R402.4.1.1 to
read:
R402.4 Air leakage. The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.4.
R402.4.1.1 Installation (Mandatory). The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance.
13. 14. Change the title of the "Insulation
Installation Criteria" category of Table R402.4.1.1; change the
"Shower/tub on exterior wall" category of Table R402.4.1.1, and add
footnotes "b" and "c" to Table R402.4.1.1 to read:
|
Component |
Air Barrier Criteria |
Insulation Installation Criteriab |
|||
|
Shower/tub on exterior wallc |
The air barrier installed at exterior walls adjacent to showers and tubs shall be installed on the interior side and separate the exterior walls from the showers and tubs. |
Exterior walls adjacent to showers and tubs shall be insulated. |
|||
|
b. Structural integrity of headers shall be in accordance with the applicable building code. c. Air barriers used behind showers and tubs on exterior walls shall be of a permeable material that does not cause the entrapment of moisture in the stud cavity. |
|||||
14. 15. Change Section R402.4.1.2 and add
Sections R402.4.1.2.1, R402.4.1.2.2, and R402.4.1.3 to read:
R402.4.1.2 Air sealing. Building envelope air tightness
shall be demonstrated to comply with either Section R402.4.1.2.1 or R402.4.1.2.2.
R402.4.1.2.1 Testing option. The building or
dwelling unit shall be tested for and verified as having an air
leakage rate not exceeding five air changes per hour in Climate Zone 4.
Testing shall be conducted in accordance with a blower door at a
pressure of 0.2 inches w.g. (50 Pascals) RESNET/ICC 380, ASTM E 779, or
ASTM E 1827 and reported at a pressure of 0.2 inch w.g. (50 Pascals). Where
required by the building official, testing shall be conducted by an approved
third party. A written report of the results of the test shall be signed by
the party conducting the test and provided to the building official. Testing
shall be conducted by a Virginia licensed general contractor, a Virginia
licensed HVAC contractor, a Virginia licensed home inspector, a Virginia
registered design professional, a certified BPI Envelope Professional, a
certified HERS rater, or a certified duct and envelope tightness rater. The
party conducting the test shall have been trained on the equipment used to
perform the test. Testing shall be performed at any time after creation of
all penetrations of the building thermal envelope.
Note: Should additional sealing be required as a result of the test, consideration may be given to the issuance of a temporary certificate of occupancy in accordance with Section 116.1.1.
During testing:
1. Exterior windows and doors and fireplace and stove doors shall be closed, but not sealed beyond the intended weatherstripping or other infiltration control measures;
2. Dampers, including exhaust, intake, makeup air, backdraft, and flue dampers, shall be closed, but not sealed beyond intended infiltration control measures;
3. Interior doors, if installed at the time of the test, shall be open;
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed;
5. Heating and cooling systems, if installed at the time of the test, shall be turned off; and
6. Supply and return registers, if installed at the time of the test, shall be fully open.
R402.4.1.2.2 Visual inspection option. Building envelope
tightness shall be considered acceptable when the items listed in Table
R402.4.1.1, applicable to the method of construction, are field verified. Where
required by the building official, an approved party, independent from the
installer, shall inspect the air barrier. When this option is chosen, the
dwelling unit shall be ventilated by mechanical means in accordance with
Section 403 of the IMC.
R402.4.1.3 Leakage rate (Prescriptive). The building or
dwelling unit shall have an air leakage rate not exceeding 5 changes per hour
as verified in accordance with Section R402.4.1.2.
15. 16. Change Section R403.3.3 to read:
R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough-in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exception: A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. The licensed mechanical contractor installing the mechanical system shall be permitted to perform the duct testing. The contractor shall have been trained on the equipment used to perform the test.
17. Delete Section R403.3.5.
16. 18. Change Section R403.7 to read:
R403.7 Equipment and appliance sizing. Heating and cooling equipment and appliances shall be sized in accordance with ACCA Manual S or other approved sizing methodologies based on building loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies.
Exception: Heating and cooling equipment and appliance sizing shall not be limited to the capacities determined in accordance with Manual S or other approved sizing methodologies where any of the following conditions apply:
1. The specified equipment or appliance utilizes multi-stage technology or variable refrigerant flow technology and the loads calculated in accordance with the approved heating and cooling methodology fall within the range of the manufacturer's published capacities for that equipment or appliance.
2. The specified equipment or appliance manufacturer's published capacities cannot satisfy both the total and sensible heat gains calculated in accordance with the approved heating and cooling methodology and the next larger standard size unit is specified.
3. The specified equipment or appliance is the lowest capacity unit available from the specified manufacturer.
17. 19. Change footnote "a" in
Table R406.4 to read:
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a. When onsite renewable energy is included for compliance using the ERI analysis per Section R406.4, the building shall meet the mandatory requirements of Section R406.2 and the building thermal envelope shall be greater than or equal to levels of energy efficiency and solar heat gain coefficient in Table R402.1.2, with a ceiling R-value of 49 and a wood frame wall R-value of 20 or 13+5, or Table R402.1.4, with a ceiling U-factor of 0.026 and a frame wall U-factor of 0.060. |
18. 20. Delete Section R503.1.1.1.
13VAC5-63-267. Chapter 14 Exterior walls.
A. Delete Section 1403.5 1402.5 of the IBC.
B. Add Section 1403.8 1402.8 to the IBC to read:
1403.8 1402.8 Air barriers. The exterior wall
envelope shall be designed and constructed by providing air barriers that
comply with the IECC.
C. Change Section 1407.10.4 1406.10.4 of the IBC
to read:
1407.10.4 1406.10.4 Full-scale test. The MCM
system shall be tested in accordance with, and comply with, the acceptance
criteria of NFPA 285. Such testing shall be performed on the MCM system with
the MCM in the maximum thickness intended for use. Where noncombustible
materials or combustible materials permitted by Sections Section 603,
803, 806, or 1406 differ from assembly to assembly or within an assembly,
multiple tests shall not be required.
Exception: The MCM system is not required to be tested in accordance with, and comply with, acceptance criteria of NFPA 285 in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
13VAC5-63-268. Chapter 15 Roof assemblies and rooftop structures.
A. Change the title of IBC Section 1511 to read:
Roofing and Roofing Repair.
B. Change Section 1511.1 of the IBC to read as follows and delete the remainder of Section 1511 of the IBC:
1511.1 General. Materials and methods of application used for
reroofing and roof repair shall comply with the applicable requirements of
Chapter 15 and the requirements of Section 303 307 of the VEBC.
13VAC5-63-270. Chapter 16 Structural design.
A. Change Section 1609.3 of the IBC to read:
1609.3 Basic wind speed. The ultimate design wind speed, Vult,
in miles per hour (mph), for the determination of the wind loads shall be
determined by Figures 1609.3(1), 1609.3(2), and 1609.3(3), and
1609.3(4). The ultimate design wind speed, Vult, for use in the
design of Risk Category II buildings and structures shall be obtained from
Figure 1609.3(1). The ultimate design wind speed, Vult, for use in
the design of Risk Categories III and IV buildings and structures shall be
obtained from Figure Figures 1609.3(2) and 1609.3(3),
respectively. The ultimate design wind speed, Vult, for use in
the design of Risk Category I buildings and structures shall be obtained from
Figure 1609.3(3) 1609.3(4). The ultimate design wind speeds for
localities in special wind regions, near mountainous terrains, and near gorges
shall be based on elevation. Areas at 4,000 feet in elevation or higher shall
use 142 V mph (62.5 m/s) and areas under 4,000 feet in elevation shall use 116
V mph (51 m/s). Gorge areas shall be based on the highest recorded speed per
locality or in accordance with local jurisdiction requirements determined in
accordance with Section 26.5.1 of ASCE 7.
In nonhurricane-prone regions, when the ultimate design wind speed, Vult, is estimated from regional climatic data, the ultimate design wind speed, Vult, shall be determined in accordance with Section 26.5.3 of ASCE 7.
B. Add Section 1612.1.1 to the IBC to read:
1612.1.1 Elevation of manufactured homes. New or replacement manufactured homes to be located in any flood hazard zone shall be placed in accordance with the applicable elevation requirements of this code.
Exception: Manufactured homes installed on sites in an existing manufactured home park or subdivision shall be permitted to be placed so that the manufactured home chassis is supported by reinforced piers or other foundation elements of at least equivalent strength that are no less than 36 inches (914 mm) above grade in lieu of being elevated at or above the base flood elevation provided no manufactured home at the same site has sustained flood damage exceeding 50% of the market value of the home before the damage occurred.
13VAC5-63-280. Chapter 17 Special inspections and tests.
A. Change Section 1703.1 of the IBC to read:
1703.1 Approved agency. An approved agency responsible for laboratory testing or special inspections, or both, must comply with the qualification, certification and experience requirements of ASTM E329 or the alternatives listed herein.
B. Change Section 1703.1.1 of the IBC to read:
1703.1.1 Independence. An approved agency shall be objective and competent. The agency shall also disclose possible conflicts of interest so that objectivity can be confirmed. The special inspector and their agents shall be independent from the person, persons or contractor responsible for the physical construction of the project requiring special inspections.
C. Change Section 1703.1.3 of the IBC to read:
1703.1.3 Personnel. An approved agency shall employ experienced personnel educated in conducting, supervising and evaluating tests or inspections, or both. Upon request by the building official, documentation shall be provided demonstrating the applicable agency's accreditation as noted in ASTM E329 and individuals' resumes indicating pertinent training, certifications and other qualifications for special inspection personnel associated with the proposed construction requiring special inspections. The building official may prescribe the manner of qualification documentation and frequency of updating information regarding agency or individual inspector approval.
Firms providing special inspection services or individual inspectors seeking approval of alternative certifications or qualifications, or both, listed in ASTM E329 may submit documentation demonstrating equivalency. This documentation may include evidence of meeting other recognized standards or alternative certifications to demonstrate that the minimum qualifications, certification and experience intended by ASTM E329 have been met. The building official may, if satisfied that equivalency has been demonstrated, approve the credentials of the firm or individual.
D. Change Section 1704.2 of the IBC to read:
1704.2 Special inspections. Where application is made for construction as described in this section, the owner shall employ one or more special inspectors to provide inspections and tests during construction on the types of work listed under Section 1705. All individuals or agents performing special inspection functions shall operate under the direct supervision of an RDP in responsible charge of special inspection activities, also known as the "special inspector." The special inspector shall ensure that the individuals under their charge are performing only those special inspections or laboratory testing that are consistent with their knowledge, training and certification for the specified inspection or laboratory testing.
Exceptions:
1. The building official shall be permitted to waive special inspections and tests.
2. Special inspections and tests are not required for:
2.1. One story buildings under 20 feet (6096 mm) in height
which do not exceed 5000 5,000 square feet (565 m2) in
building area; or
2.2. Alterations to Group U structures which do not increase
loads in accordance with Sections 403.3 603.7.3 and 403.4 603.7.4
of the VEBC.
3. Unless otherwise required by the building official, special
inspections and tests are not required for occupancies in Groups Group
R-3, R-4 or R-5 and occupancies in Group U that are accessory to a residential
occupancy including, but not limited to, those listed in Section 312.1.
4. Special inspections and tests are not required for portions
of structures designed and constructed in accordance with the cold-formed steel
light-frame construction provisions of Section 2211.7 2211.1.2 or
the conventional light-frame construction provisions of Section 2308.
5. The contractor is permitted to employ the approved agencies where the contractor is also the owner.
E. Change Section 1704.2.3 of the IBC to read:
1704.2.3 Statement of special inspections. The permit applicant shall submit a statement of special inspections prepared by the RDP in responsible charge in accordance with Section 111.1. This statement shall be in accordance with Section 1704.3.
Exception:
The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for construction not designed by a registered design professional.
F. Change category "12" of Table 1705.3 of the IBC to read:
|
Type |
Continuous Special Inspection |
Periodic Special Inspection |
Referenced Standarda |
IBC Reference |
|
12. Inspect formwork for shape, location and dimensions of the concrete member being formed, shoring and reshoring. |
-- |
X |
ACI 318: |
-- |
G. Delete Sections 1705.17, 1705.17.1, and 1705.17.2 of the IBC.
13VAC5-63-295. Chapter 23 Wood.
A. Change Item Add Exception 2 to Item 2
of Section 2308.2.3 of the IBC to read:
2. Live loads shall not exceed 40 psf (1916 N/m2)
for floors.
Exception: 2. Concrete slab-on-grade live load
limited only by allowable soil bearing pressure.
B. Change Table 2308.4.1.1(1) of the IBC to read:
|
|||||||||||||||||||
|
|
|
|||||||||||||||||
|
|
|
|||||||||||||||||
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C. Change Table 2308.4.1.1(2) of the IBC to read:
|
|||||||
|
|
|
|||||
|
|
|
|||||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
13VAC5-63-298. Chapter 26 Plastic.
Change Section 2603.5.5 of the IBC to read:
2603.5.5 Vertical and lateral fire propagation. Exterior wall
assemblies shall be tested in accordance with, and comply with, acceptance criteria
of NFPA 285. Where noncombustible materials or combustible materials permitted
by Sections Section 603, 803, 806 or 1406 1405
differ from assembly to assembly or within an assembly, multiple tests shall
not be required.
Exceptions:
1. One-story buildings where the exterior wall covering is noncombustible.
2. Wall assemblies where the foam plastic insulation is covered on each face by not less than 1-inch (25 mm) thickness of masonry or concrete and meeting one of the following:
2.1. There is no air space between the insulation and the concrete or masonry.
2.2. The insulation has a flame spread index of not more than 25 as determined in accordance with ASTM E 84 or UL 723 and the maximum air space between the insulation and the concrete or masonry is not more than 1 inch (25 mm).
3. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
13VAC5-63-300. Chapter 27 Electrical.
A. Change Section 2701.1 of the IBC to read:
2701.1 Scope. This chapter governs the electrical components, equipment and systems used in buildings and structures covered by this code. Electrical components, equipment and systems shall be designed and constructed in accordance with the provisions of this code and NFPA 70.
B. Add Section 2701.1.1 to the IBC to read:
2701.1.1 Changes to NFPA 70. The following changes shall be made to NFPA 70:
1. Change Sections 334.10(2) and 334.10(3) of NFPA 70 to read:
(2) Multifamily dwellings not exceeding four floors above grade and multifamily dwellings of any height permitted to be of Types III, IV and V construction except in any case as prohibited in 334.12.
(3) Other structures not exceeding four floors above grade and other structures of any height permitted to be of Types III, IV and V construction except in any case as prohibited in 334.12. In structures exceeding four floors above grade, cables shall be concealed within walls, floors or ceilings that provide a thermal barrier of material that has at least a 15-minute finish rating as identified in listings of fire-rated assemblies.
For the purpose of Items 2 and 3 above, the first floor of a building shall be that floor that has 50% or more of the exterior wall surface area level with or above finished grade. One additional level that is the first level and not designed for human habitation and used only for vehicle parking, storage or similar use shall be permitted.
2. Change Section 700.12(F)(2)(6) of NFPA 70 to read:
(6) Where the normal power branch circuits that supply luminaires providing illumination immediately on the inside and outside of exit doors are supplied by the same service or feeder, the remote heads providing emergency illumination for the exterior of an exit door shall be permitted to be supplied by the unit equipment serving the area immediately inside the exit door.
C. Add Section 2701.1.2 to the IBC to read:
2701.1.2 Temporary connection to dwelling units. The building official shall give permission to energize the electrical service equipment of a one-family or two-family dwelling unit when all of the following requirements have been approved:
1. The service wiring and equipment, including the meter socket enclosure, shall be installed and the service wiring terminated.
2. The grounding electrode system shall be installed and terminated.
3. At least one receptacle outlet on a ground fault protected circuit shall be installed and the circuit wiring terminated.
4. Service equipment covers shall be installed.
5. The building roof covering shall be installed.
6. Temporary electrical service equipment shall be suitable for wet locations unless the interior is dry and protected from the weather.
D. Add Section 2701.1.3 to the IBC to read:
2701.1.3 Assisted living facility generator requirements. Generators installed to comply with regulations for assisted living facilities licensed by the Virginia Department of Social Services shall be permitted to be optional standby systems.
E. Change Section 2702.2.17 Sections 2702.2.8 and
2702.2.9 of the IBC to read:
2702.2.17 2702.2.8 Group I-2 and I-3
occupancies. Emergency power shall be provided in accordance with Section 407.10
407.11 for Group I-2 occupancies licensed by the Virginia Department of
Health as a hospital, nursing or hospice facility.
2702.2.9 Group I-3 occupancies. Emergency power shall be provided for doors in Group I-3 occupancies in accordance with Section 408.4.2.
13VAC5-63-310. Chapter 28 Mechanical systems.
A. Change Section 2801.1 of the IBC to read:
2801.1 Scope. Mechanical appliances, equipment and systems shall be constructed and installed in accordance with this chapter, the IMC and the IFGC. Masonry chimneys, fireplaces and barbecues shall comply with the IMC and Chapter 21 of this code.
Exception: This code shall not govern the construction of water heaters, boilers and pressure vessels to the extent which they are regulated by the Virginia Boiler and Pressure Vessel Regulations (16VAC25-50). However, the building official may require the owner of a structure to submit documentation to substantiate compliance with those regulations.
B. Add Section 2801.1.1 to the IBC to read:
2801.1.1 Required heating in dwelling units. Heating facilities shall be required in every dwelling unit or portion thereof which is to be rented, leased or let on terms, either expressed or implied, to furnish heat to the occupants thereof. The heating facilities shall be capable of maintaining the room temperature at 65°F (18°C) during the period from October 15 to May 1 during the hours between 6:30 a.m. and 10:30 p.m. of each day and not less than 60°F (16°C) during other hours when measured at a point three feet (914 mm) above the floor and three feet (914 mm) from the exterior walls. The capability of the heating system shall be based on the outside design temperature required for the locality by this code.
C. Add Section 2801.1.2 to the IBC to read:
2801.1.2 Required heating in nonresidential structures. Heating facilities shall be required in every enclosed occupied space in nonresidential structures. The heating facilities shall be capable of producing sufficient heat during the period from October 1 to May 15 to maintain a temperature of not less than 65°F (18°C) during all working hours. The required room temperature shall be measured at a point three feet (914 mm) above the floor and three feet (914 mm) from the exterior walls.
Processing, storage and operation areas that require cooling or special temperature conditions and areas in which persons are primarily engaged in vigorous physical activities are exempt from these requirements.
D. Add Section 2801.1.3 to the IBC to read:
2801.1.3 Changes to the IMC. The following changes shall be made to the IMC:
1. Add the following definition to Section 202 of the IMC to
read:
Pollution control unit. Manufactured equipment that is
installed in a grease exhaust duct system for the purpose of extracting smoke,
grease particles, and odors from the exhaust flow by means of a series of
filters.
2. 1. Change Section 401.2 of the IMC to read:
401.2 Ventilation required. Every occupied space shall
be ventilated by natural means in accordance with Section 402 or by mechanical
means in accordance with Section 403. Group R dwelling unit units shall
be ventilated by mechanical means in accordance with Section 403. Ambulatory
care facilities and Group I-2 occupancies shall be ventilated by mechanical
means in accordance with Section 407.
3. 2. Change Section 403.3.1.1 of the IMC to
read:
403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall not be less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1. Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
With the exception of smoking lounges and other designated areas where smoking is permitted, the ventilation rates in Table 403.3.1.1 are based on the absence of smoking in occupiable spaces.
Exception: The occupant load is not required to be determined based on the estimated maximum occupant load rate indicated in Table 403.3.1.1 where approved statistical data document the accuracy of an alternate anticipated occupant density.
4. 3. Add and change the following areas
in rows to Table 403.3.1.1 of the IMC to read:
|
OCCUPANCY CLASSIFICATION |
Occupant Density #/1000 ft2 a |
People Outdoor Airflow Rate in Breathing Zone, |
Area Outdoor Airflow Rate in Breathing Zone, Ra cfm/ft2a |
Exhaust Airflow Rate |
|
Food and beverage service |
|
|
|
|
|
Bars or cocktail lounges designated as an area where smoking is permittedb |
100 |
30 |
-- |
-- |
|
Cafeteria or fast food designated as an area where smoking is permittedb |
100 |
20 |
-- |
-- |
|
Dining rooms designated as an area where smoking is permittedb |
70 |
20 |
-- |
-- |
|
Public spaces |
|
|
|
|
|
Lounges designated as an area where smoking is permittedb |
100 |
30 |
-- |
-- |
5. 4. Change Section 504.8.2 of the IMC to read:
504.8.2 Duct installation. Exhaust ducts shall be supported at 4-foot (1219 mm) intervals and secured in place. The insert end of the duct shall extend into the adjoining duct or fitting in the direction of airflow. Ducts shall not be joined with screws or similar fasteners that protrude into the inside of the duct.
Where dryer exhaust ducts are enclosed in wall or ceiling cavities, such cavities shall allow the installation of the duct without deformation.
6. 5. Change Exception 1 of Section 505.1
505.3 of the IMC to read:
505.1 Domestic systems. Where domestic range hoods and
domestic appliances equipped with downdraft exhaust are provided, such hoods
and appliances shall discharge to the outdoors through sheet metal ducts
constructed of galvanized steel, stainless steel, aluminum, or copper. Such
ducts shall have smooth inner walls, shall be air tight, shall be equipped with
a backdraft damper, and shall be independent of all other exhaust systems.
Exceptions:
1. In Group R buildings, where installed in accordance with the manufacturer's installation instructions and where mechanical or natural ventilation is otherwise provided in accordance with Chapter 4, listed and labeled ductless range hoods shall not be required to discharge to the outdoors.
2. Ducts for domestic kitchen cooking appliances equipped
with downdraft exhaust systems shall be permitted to be constructed of Schedule
40 PVC pipe and fittings provided that the installation complies with all of
the following:
2.1. The PVC duct shall be installed under a concrete slab
poured on grade.
2.2. The underfloor trench in which the PVC duct is
installed shall be completely backfilled with sand or gravel.
2.3. The PVC duct shall extend not more than 1 inch (25 mm)
above the indoor concrete floor surface.
2.4. The PVC duct shall extend not more than 1 inch (25 mm)
above grade outside of the building.
2.5. The PVC duct shall be solvent cemented.
7. 6. Change Section 505.4 505.6 to
the IMC to read:
505.4 505.6 Other than Group R. In other than Group
R occupancies, where electric domestic cooking appliances are utilized for
domestic purposes, such appliances shall be provided with domestic range
hoods shall be permitted for such appliances. Hoods and exhaust systems
for such electric domestic cooking appliances shall be in accordance with
Sections 505.1 505.2 and 505.2 505.4. In other than
Group R occupancies, where fuel-fired domestic cooking appliances are utilized
for domestic purposes, a Type I or Type II hood shall be provided as required
for the type of appliances and processes in accordance with Section 507.1.
8. 7. Change Section 506.5 of the IMC to read:
506.5 Exhaust equipment. Exhaust equipment, including fans and grease reservoirs, shall comply with Sections 506.5.1 through 506.5.6 and shall be of an approved design or shall be listed for the application.
9. Add 8. Change Section 506.5.6 to 506.5.2,
including Items 1, 3, and 5 of the IMC to read: (Items not shown remain
the same.)
506.5.6 506.5.2 Pollution control units. The
installation of pollution control units shall be in accordance with the
manufacturer's installation instructions and all of the following:
1. Pollution control units shall be listed and labeled in
accordance with UL 1978 8782.
2. Fans serving pollution control units shall be listed and
labeled in accordance with UL 762.
3. Pollution Bracing and supports for pollution
control units shall be mounted and secured in accordance with the
manufacturer's installation instructions and the of noncombustible
material securely attached to the structure and designed to carry gravity and
seismic loads within the stress limitations of the International Building
Code.
4. Pollution control units located indoors shall be listed
and labeled for such use. Where enclosed duct systems, as required by Section
506.3.11, are connected to a pollution control unit, such unit shall be located
in a room or space having the same fire-resistance rating as the duct
enclosure. Access shall be provided for serving and cleaning of the unit. The
space or enclosure shall be ventilated in accordance with the manufacturer's
installation instructions.
5. A clearance of not less than 18 inches (457 mm) Clearances
shall be maintained between the pollution control unit and combustible material
in accordance with the listing.
6. Roof mounted pollution control units shall be listed for
exterior installation and shall be mounted not less than 18 inches (457 mm)
above the roof.
7. Exhaust outlets for pollution control units shall be in
accordance with Section 506.3.13.
8. An airflow differential pressure control shall be
provided to monitor the pressure drop across the filter sections of a pollution
control unit. When the airflow is reduced below the design velocity, the
airflow differential pressure control shall activate a visual alarm located in
the area where cooking operations occur.
9. Pollution control units shall be provided with a factory
installed fire suppression system.
10. Service space shall be provided in accordance with the
manufacturer's instructions for the pollution control unit and the requirements
of Section 306.
11. Wash down drains shall discharge through a grease
interceptor and shall be sized for the flow. Drains shall be sealed with a trap
or other approved means to prevent air bypass. Where a trap is utilized it
shall have a seal depth that accounts for the system pressurization and
evaporation between cleanings.
12. Protection from freezing shall be provided for the
water supply and fire suppression systems where such systems are subject to freezing.
13. Duct connections to pollution control units shall be in
accordance with Section 506.3.2.3. Where water splash or carryover can occur in
the transition duct as a result of a washing operation, the transition duct
shall slope downward toward the cabinet drain pan for a length not less than 18
inches (457 mm). Ducts shall transition to the full size of the unit inlet and
outlet openings.
14. Extra heavy duty appliance exhaust systems shall not
be connected to pollution control units except where such units are
specifically designed and listed for use with solid fuels.
15. Pollution control units shall be maintained in
accordance with the manufacturer's instructions.
10. 9. Change Section 510.7.1.1 of the IMC to read:
510.7.1.1 Shaft penetrations. Hazardous exhaust ducts that penetrate fire-resistance-rated shafts shall comply with Section 713.11 of the International Building Code.
10. Change Section 607.5.5 of the IMC to read:
607.5.5 Shaft enclosures. Shaft enclosures that are permitted to be penetrated by ducts and air transfer openings shall be protected with approved fire and smoke dampers installed in accordance with their listing.
Exceptions:
1. Fire and smoke dampers are not required where steel exhaust subducts extend at least 22 inches (559 mm) vertically in exhaust shafts, provided there is a continuous airflow upward to the outside.
2. Fire dampers are not required where penetrations are tested in accordance with ASTM E119 as part of the fire-resistance-rated assembly.
3. Fire and smoke dampers are not required where ducts are used as part of an approved smoke control system in accordance with Section 909 of the International Building Code.
4. Fire and smoke dampers are not required where the penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than two-hour fire-resistance-rated construction.
5. Smoke dampers are not required where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the International Building Code.
11. Add Section 607.6.2.2 to the IMC to read:
607.6.2.2 Equipment shutdown. Where ceiling radiation dampers are listed as static dampers, the HVAC equipment shall be effectively shut down to stop the airflow prior to the damper closing using one of the following methods:
1. A duct detector installed in the return duct.
2. An area smoke detector interlocked with the HVAC equipment.
3. A listed heat sensor installed in the return duct.
E. Add Section 2801.1.4 to the IBC to read:
2801.1.4 Changes to the IFGC. The following changes shall be made to the IFGC:
1. Change Section 301.1 of the IFGC to read:
301.1 Scope. This code shall apply to the installation of fuel gas piping systems, fuel gas utilization equipment, and related accessories as follows:
1. Coverage of piping systems shall extend from the point of delivery to the connections with gas utilization equipment. (See "point of delivery.")
2. Systems with an operating pressure of 125 psig (862 kPa gauge) or less.
Piping systems for gas-air mixtures within the flammable range with an operating pressure of 10 psig (69 kPa gauge) or less.
LP-Gas piping systems with an operating pressure of 20 psig (140 kPa gauge) or less.
3. Piping systems requirements shall include design, materials, components, fabrication, assembly, installation, testing and inspection.
4. Requirements for gas utilization equipment and related accessories shall include installation, combustion and ventilation air and venting.
This code shall not apply to the following:
1. Portable LP-Gas equipment of all types that are not connected to a fixed fuel piping system.
2. Installation of farm equipment such as brooders, dehydrators, dryers, and irrigation equipment.
3. Raw material (feedstock) applications except for piping to special atmosphere generators.
4. Oxygen-fuel gas cutting and welding systems.
5. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon monoxide, oxygen, and nitrogen.
6. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms, and natural gas processing plants.
7. Integrated chemical plants or portions of such plants where flammable or combustible liquids or gases are produced by chemical reactions or used in chemical reactions.
8. LP-Gas installations at utility gas plants.
9. Liquefied natural gas (LNG) installations.
10. Fuel gas piping in power and atomic energy plants.
11. Proprietary items of equipment, apparatus, or instruments such as gas generating sets, compressors, and calorimeters.
12. LP-Gas equipment for vaporization, gas mixing, and gas manufacturing.
13. Temporary LP-Gas piping for buildings under construction or renovation that is not to become part of the permanent piping system.
14. Installation of LP-Gas systems for railroad switch heating.
15. Installation of LP-Gas and compressed natural gas (CNG) systems on vehicles.
16. Except as provided in Section 401.1.1, gas piping, meters, gas pressure regulators, and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP-Gas.
17. Building design and construction, except as specified herein.
2. Change Sections 310.1 and 310.1.1 310.2 of the
IFGC to read:
310.1 Pipe and tubing. Each above-group portion of a gas
piping system that is likely to become energized shall be electrically
continuous and bonded to an effective ground-fault current path. Gas piping
shall be considered to be bonded where it is connected to appliances that are
connected to the equipment grounding conductor of the circuit supplying that
appliance. Corrugated stainless steel tubing (CSST) piping systems listed with
an arc resistant jacket or coating system in accordance with ANSI LC 1/CSA 6.26
shall comply with this section. Where any CSST segments of a piping system are
not listed with an arc resistant jacket or coating system in accordance with
ANSI LC 1/CSA 6.26, Section 310.1.1 310.2 shall apply.
310.1.1 310.2 CSST without arc resistant jacket
or coating system. CSST gas piping systems and piping systems containing one or
more segments of CSST not listed with an arc resistant jacket or coating system
in accordance with ANSI LC 1/CSA 6.26 shall be bonded to the electrical service
grounding electrode system or, where provided, the lightning protection
electrode system and shall comply with Sections 310.1.1.1 310.2.1
through 310.1.1.5 310.2.5.
3. Add Section 404.11.3 404.11.6 to the IFGC to
read:
404.11.3 404.11.6 Coating application. Joints in
gas piping systems shall not be coated prior to testing and approval.
4. Change Section 614.8.2 of the IFGC to read:
614.8.2 Duct installation. Exhaust ducts shall be supported at 4-foot (1219 mm) intervals and secured in place. The insert end of the duct shall extend into the adjoining duct or fitting in the direction of airflow. Ducts shall not be joined with screws or similar fasteners that protrude into the inside of the duct.
Where dryer exhaust ducts are enclosed in wall or ceiling cavities, such cavities shall allow the installation of the duct without deformation.
5. Change the following referenced standard in Chapter 8 of the IFGC:
Standard Reference Number |
Title |
Referenced in Code Section Number |
ANSI LC1/CSA |
Fuel Gas Piping Systems Using Corrugated Stainless Steel Tubing (CSST) |
310.1, 310.1.1, 403.5.4 |
UL8782-17 |
Outline of Investigation for Pollution Control Units for Commercial Cooking |
506.5.2 |
13VAC5-63-320. Chapter 29 Plumbing systems.
A. Change Section 2901.1 of the IBC to read:
2901.1 Scope. The provisions of this chapter and the IPC shall govern the design and installation of all plumbing systems and equipment, except that as provided for in Section 103.5 for functional design, water supply sources and sewage disposal systems are regulated and approved by the Virginia Department of Health and the Virginia Department of Environmental Quality. The approval of pumping and electrical equipment associated with such water supply sources and sewage disposal systems shall, however, be the responsibility of the building official.
Note: See also the Memorandum of Agreement in the "Related Laws Package," which is available from DHCD.
B. Add Section 2901.1.1 to the IBC to read:
2901.1.1 Changes to the IPC. The following changes shall be made to the IPC:
1. Add the following definitions to the IPC to read:
Nonpotable fixtures and outlets. Fixtures and outlets that are
not dependent on potable water for the safe operation to perform their intended
use. Such fixtures and outlets may include, but are not limited to water
closets, urinals, irrigation, mechanical equipment, and hose connections to
perform operations, such as vehicle washing and lawn maintenance.
Nonpotable water systems. Water systems for the collection, treatment, storage, distribution, and use or reuse of nonpotable water. Nonpotable systems include reclaimed water, rainwater, and gray water systems.
Service sink. A general purpose sink exclusively intended to be used for facilitating the cleaning of a building or tenant space.
Stormwater. Precipitation that is discharged across the land surface or through conveyances to one or more waterways and that may include stormwater runoff, snow melt runoff, and surface runoff and drainage.
2. Change the following definitions in the IPC to read:
Gray water. Water discharged from lavatories, bathtubs,
showers, clothes washers, and laundry trays.
Rainwater. Natural precipitation, including snow melt, from roof surfaces only.
Reclaimed water. Reclaimed water means water resulting from the treatment of domestic, municipal, or industrial wastewater that is suitable for a water reuse that would not otherwise occur. Specifically excluded from this definition is "gray water."
3. Change the exception to Section 301.3 of the IPC to read:
Exception: Bathtubs, showers, lavatories, clothes washers and laundry trays shall not be required to discharge to the sanitary drainage system where such fixtures discharge to an approved nonpotable gray water system in accordance with the applicable provisions of Chapter 13.
4. Delete Sections Section 311 and 311.1
of the IPC in its entirety.
5. Modify the Group A-5 following Assembly
"Description" category of Table 403.1 of the IPC to read:
|
Stadiums, amusement parks, pools, bleachers, and grandstands
for outdoor sporting events and activities |
6. Add footnote "f" "g" to
Table 403.1 of the IPC to read:
f. g. The occupant load for pools shall be in
accordance with the "Skating rinks, swimming pools" category of Table
1004.1.2 1004.5 of the IBC.
7. Add Section 403.1.3 403.1.4 and Table 403.1.3
403.1.4 to the IPC to read:
403.1.3 403.1.4 Marina fixtures. Notwithstanding
any provision to the contrary, plumbing fixtures shall be provided for marinas
in the minimum number shown in Table 403.1.3 403.1.4. Fixtures
shall be located within 500 feet walking distance from the shore end of any
dock they serve. Separate facilities shall be provided for each sex with an
equal number of fixtures of each type in each facility, except that separate
facilities are not required where the number of slips is less than 25. Urinals
may be substituted for up to 50% of water closets.
|
Table |
|||
|
Number of Slips |
Plumbing Fixtures |
||
|
Water Closets |
Lavatories |
Showers |
|
|
1 - 24 |
1 |
1 |
1 |
|
25 - 49 |
4 |
4 |
2 |
|
50 - 99 |
6 |
4 |
2 |
|
100 - 149 |
8 |
6 |
4 |
|
150 - 199 |
10 |
8 |
4 |
|
200 - 249 |
12 |
10 |
6 |
|
250 or greater |
Two additional fixtures of each type for each 100 additional slips. |
8. Change Add Exception 2 to Section 403.3.3 of
the IPC to read:
403.3.3 Location of toilet facilities in occupancies other than
malls. In occupancies other than covered and open mall buildings, the required
public and employee toilet facilities shall be located not more than one story
above or below the space required to be provided with toilet facilities, and
the path of travel to such facilities shall not exceed a distance of 500 feet
(152 m).
Exceptions:
1. The location and maximum distances of travel to required
employee facilities in factory and industrial occupancies are permitted to
exceed that required by this section, provided that the location and maximum
travel distance are approved.
2. The location and maximum distances of travel to the required public facilities located on cemetery property are permitted to exceed that required by this section, provided that the location and maximum travel distance are located on the same property and approved.
9. Change Add an exception to Section 405.3.2 of
the IPC to read:
405.3.2 Public lavatories. In employee and public toilet
rooms, the required lavatory shall be located in the same room as the required
water closet.
Exception: In educational use occupancies, the required lavatory shall be permitted to be located adjacent to the room or space containing the water closet provided that not more than one operational door is between the water closet and the lavatory.
10. Change Section 410.4 of the IPC to read:
410.4 Substitution. Where restaurants provide drinking water in a container free of charge, drinking fountains shall not be required in those restaurants. In other occupancies where more than two drinking fountains are required, water dispensers shall be permitted to be substituted for not more than 50% of the required number of drinking fountains.
11. Change Section 423.1 of the IPC to read:
423.1 Water connections. Baptisteries, ornamental and lily pools, aquariums, ornamental fountain basins, swimming pools, footbaths and pedicure baths, and similar constructions, where provided with water supplies, shall be protected against backflow in accordance with Section 608.
12. Add Section 602.2.1 to the IPC to read:
602.2.1 Nonpotable fixtures and outlets. Nonpotable water shall be permitted to serve nonpotable type fixtures and outlets in accordance with Chapter 13.
11. 13. Add Section 603.3 to the IPC to read:
603.3 Tracer wire. Nonmetallic water service piping that connects to public systems shall be locatable. An insulated copper tracer wire, 18 AWG minimum in size and suitable for direct burial or an equivalent product, shall be utilized. The wire shall be installed in the same trench as the water service piping and within 12 inches (305 mm) of the pipe and shall be installed to within five feet (1524 mm) of the building wall to the point where the building water service pipe intersects with the public water supply. At a minimum, one end of the wire shall terminate above grade to provide access to the wire in a location that is resistant to physical damage, such as with a meter vault or at the building wall.
12. Change Section 608.16.10 of the IPC to read:
608.16.10 Coffee machines and noncarbonated beverage
dispensers. The water supply connection to coffee machines and noncarbonated
beverage dispensers shall be protected against backflow by a backflow preventer
conforming to ASSE 1022 or 1024, or by an air gap.
13. Delete Section 701.8 of the IPC.
14. Change Section 605.2.1 to read:
605.2.1 Lead content of drinking water pipe and fittings. Pipe, pipe fittings, joints, valves, faucets and fixture fittings utilized to supply water for drinking or cooking purposes shall comply with NSF 372.
15. Add Section 703.7 to the IPC to read:
703.7 Tracer wire. Nonmetallic sanitary sewer piping that discharges to public systems shall be locatable. An insulated copper tracer wire, 18 AWG minimum in size and suitable for direct burial or an equivalent product, shall be utilized. The wire shall be installed in the same trench as the sewer within 12 inches (305 mm) of the pipe and shall be installed to within five feet (1524 mm) of the building wall to the point where the building sewer intersects with the public system. At a minimum, one end of the wire shall terminate above grade in an accessible location that is resistant to physical damage, such as with a cleanout or at the building wall.
16. Delete the exception for Section 705.10.2 of the IPC.
17. Add Section 717 Relining Building Sewers and Building Drains to the IPC.
18. Add Sections 717.1 through 717.10, including subsections, to the IPC to read:
717.1 General. This section shall govern the relining of existing building sewers and building drainage piping.
717.2 Applicability. The relining of existing building sewer and building drainage piping shall be limited to gravity drainage piping, 4 inches (102 mm) in diameter and larger. The relined piping shall be of the same nominal size as the existing piping.
717.3 Pre-installation requirements. Prior to commencement of the relining installation, the existing piping sections to be relined shall be descaled and cleaned. After the cleaning process has occurred and water has been flushed through the system, the piping shall be inspected internally by a recorded video camera survey.
717.3.1 Pre-installation recorded video camera survey. The video survey shall include verification of the project address location. The video shall include notations of the cleanout and fitting locations, and the approximate depth of the existing piping. The video shall also include notations of the length of piping at intervals no greater than 25 feet.
717.4 Permitting. Prior to permit issuance, the code official shall review and evaluate the pre-installation recorded video camera survey to determine if the piping system is capable to be relined in accordance with the proposed lining system manufacturer's installation requirements and applicable referenced standards.
717.5 Prohibited applications. Where review of the pre-installation recorded video camera survey reveals that piping systems are not installed correctly or defects exist, relining shall not be permitted. The defective portions of piping shall be exposed and repaired with pipe and fittings in accordance with this code. Defects shall include backgrade or insufficient slope, complete pipe wall deterioration or complete separations, such as from tree root invasion or improper support.
717.6 Relining materials. The relining materials shall be manufactured in compliance with applicable standards and certified as required in Section 303. Fold-and-form pipe reline materials shall be manufactured in compliance with ASTM F1504 or ASTM F1871.
717.7 Installation. The installation of relining materials shall be performed in accordance with the manufacturer's installation instructions, applicable referenced standards and this code.
717.7.1 Material data report. The installer shall record the data as required by the relining material manufacture and applicable standards. The recorded data shall include the location of the project, relining material type, amount of product installed, and conditions of the installation. A copy of the data report shall be provided to the code official prior to final approval.
717.8 Post-installation recorded video camera survey. The completed relined piping system shall be inspected internally by a recorded video camera survey after the system has been flushed and flow-tested with water. The video survey shall be submitted to the code official prior to finalization of the permit. The video survey shall be reviewed and evaluated to provide verification that no defects exist. Any defects identified shall be repaired and replaced in accordance with this code.
717.9 Certification. A certification shall be provided in writing to the code official, from the permit holder, that the relining materials have been installed in accordance with the manufacturer's installation instructions, the applicable standards, and this code.
717.10 Approval. Upon verification of compliance with the requirements of Sections 717.1 through 717.9, the code official shall approve the installation.
15. 19. Add an exception to Section 1101.2 of the
IPC to read:
Exception. Rainwater nonpotable water systems shall be permitted in accordance with Chapter 13.
20. Delete the last sentence from Section 1101.7 of the IPC.
21. Delete Section 1105.2 of the IPC.
16. 22. Change Section 1106.2 of the IPC to read:
1106.2 Vertical conductors and leaders. Vertical conductors and leaders shall be sized for the maximum projected roof area, in accordance with Tables 1106.2(1) and 1106.2(2).
17. 23. Delete Table 1106.2 of the IPC and add
Tables 1106.2.(1) 1106.2(1) and 1106.2(2) to the IPC to read:
Table 1106.2(1) Size of Circular Vertical Conductors and Leaders |
||||||||||||||||||||||||
Diameter of Leader (inchesa) |
Horizontally Projected Roof Area (square feet) |
|||||||||||||||||||||||
Rainfall rate (inches per hour) |
||||||||||||||||||||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
|||||||||||||
2 |
2,280 |
1,440 |
960 |
720 |
575 |
480 |
410 |
360 |
320 |
290 |
260 |
240 |
||||||||||||
3 |
8,800 |
4,400 |
2,930 |
2,200 |
1,760 |
1,470 |
1,260 |
1,100 |
980 |
880 |
800 |
730 |
||||||||||||
4 |
18,400 |
9,200 |
6,130 |
4,600 |
3,680 |
3,070 |
2,630 |
2,300 |
2,045 |
1,840 |
1,675 |
1,530 |
||||||||||||
5 |
34,600 |
17,300 |
11,530 |
8,650 |
6,920 |
5,765 |
4,945 |
4,325 |
3,845 |
3,460 |
3,145 |
2,880 |
||||||||||||
6 |
54,000 |
27,000 |
17,995 |
13,500 |
10,800 |
9,000 |
7,715 |
6,750 |
6,000 |
5,400 |
4,910 |
4,500 |
||||||||||||
8 |
116,000 |
58,000 |
38,660 |
29,000 |
23,200 |
19,315 |
16,570 |
14,500 |
12,890 |
11,600 |
10,545 |
9,600 |
||||||||||||
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2. a. Sizes indicated are the diameter of circular piping. This table is applicable to piping of other shapes, provided the cross-sectional shape fully enclosed a circle of the diameter indicated in this table. For rectangular leaders, see Table 1106.2(2). Interpolation is permitted for pipe sizes that fall between those listed in this table. |
||||||||||||||||||||||||
Table 1106.2(2) Size of Rectangular Vertical Conductors and Leaders |
||||||||||||||||||||||||
Dimensions of Common Leader Sizes width x length (inches)a,b |
Horizontally Projected Roof Area (square feet) |
|||||||||||||||||||||||
Rainfall rate (inches per hour) |
||||||||||||||||||||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
|||||||||||||
1-3/4 x 2-1/2 |
3,410 |
1,700 |
1,130 |
850 |
680 |
560 |
480 |
420 |
370 |
340 |
310 |
280 |
||||||||||||
2 x 3 |
5,540 |
2,770 |
1,840 |
1,380 |
1,100 |
920 |
790 |
690 |
610 |
550 |
500 |
460 |
||||||||||||
2-3/4 x 4-1/4 |
12,830 |
6,410 |
4,270 |
3,200 |
2,560 |
2,130 |
1,830 |
1,600 |
1,420 |
1,280 |
1,160 |
1,060 |
||||||||||||
3 x 4 |
13,210 |
6,600 |
4,400 |
3,300 |
2,640 |
2,200 |
1,880 |
1,650 |
1,460 |
1,320 |
1,200 |
1,100 |
||||||||||||
3-1/2 x 4 |
15.900 |
7,950 |
5,300 |
3,970 |
3,180 |
2,650 |
2,270 |
1,980 |
1,760 |
1,590 |
1,440 |
1,320 |
||||||||||||
3-1/2 x 5 |
21,310 |
10,650 |
7,100 |
5,320 |
4,260 |
3,550 |
3,040 |
2,660 |
2,360 |
2,130 |
1,930 |
1,770 |
||||||||||||
3-3/4 x 4-3/4 |
21,960 |
10,980 |
7,320 |
5,490 |
4,390 |
3,660 |
3,130 |
2,740 |
2,440 |
2,190 |
1,990 |
1,830 |
||||||||||||
3-3/4 x 5-1/4 |
25,520 |
12,760 |
8,500 |
6,380 |
5,100 |
4,250 |
3,640 |
3,190 |
2,830 |
2,550 |
2,320 |
2,120 |
||||||||||||
3-1/2 x 6 |
27,790 |
13,890 |
9,260 |
6,940 |
5,550 |
4,630 |
3,970 |
3,470 |
3,080 |
2,770 |
2,520 |
2,310 |
||||||||||||
4 x 6 |
32,980 |
16,490 |
10,990 |
8,240 |
6,590 |
5,490 |
4,710 |
4,120 |
3,660 |
3,290 |
2,990 |
2,740 |
||||||||||||
5-1/2 x 5-1/2 |
44,300 |
22,150 |
14,760 |
11,070 |
8,860 |
7,380 |
6,320 |
5,530 |
4,920 |
4,430 |
4,020 |
3,690 |
||||||||||||
7-1/2 x 7-1/2 |
100,500 |
50,250 |
33,500 |
25,120 |
20,100 |
16,750 |
14,350 |
12,560 |
11,160 |
10,050 |
9,130 |
8,370 |
||||||||||||
For SI: 1 inch =m, 1 square foot = 0.0929 m2. a. Sizes indicated are nominal width x length of the opening for rectangular piping. b. For shapes not included in this table, Equation 11-1 shall be used to determine the equivalent circular diameter, De, of rectangular piping for use in interpolation using the data from Table 1106.2(1). (Equation 11-1) De = (width x length)1/2 where: De = equivalent circular diameter and De, width and length are in inches. |
||||||||||||||||||||||||
18. 24. Change Section 1106.3 and Table 1106.3 of
the IPC to read:
1106.3 Building storm drains and sewers. The size of the building storm drain, building storm sewer and their horizontal branches having a slope of 1/2 unit or less vertical in 12 units horizontal (4% slope) shall be based on the maximum projected roof area in accordance with Table 1106.3. The slope of horizontal branches shall be not less than 1/8 unit vertical in 12 units horizontal (1% slope) unless otherwise approved.
Table 1106.3 Size of Horizontal Storm Drainage Piping |
||||||
Size of Horizontal Piping (inches) |
Horizontally Projected Roof Area (square feet) |
|||||
Rainfall rate (inches per hour) |
||||||
1 |
2 |
3 |
4 |
5 |
6 |
|
1/8 unit vertical in 12 units horizontal (1% slope) |
||||||
3 4 5 6 8 10 12 15 |
3,288 7,520 13,360 21,400 46,000 82,800 133,200 218,000 |
1,644 3,760 6,680 10,700 23,000 41,400 66,600 109,000 |
1,096 2,506 4,453 7,133 15,330 27,600 44,400 72,800 |
822 1,800 3,340 5,350 11,500 20,700 33,300 59,500 |
657 1,504 2,672 4,280 9,200 16,580 26,650 47,600 |
548 1,253 2,227 3,566 7,600 13,800 22,200 39,650 |
1/4 unit vertical in 12 units horizontal (2% slope) |
||||||
3 |
4,640 |
2,320 |
1,546 |
1,160 |
928 |
773 |
1/2 unit vertical in 12 units horizontal (4% slope) |
||||||
3 |
6,576 |
3,288 |
2,295 |
1,644 |
1,310 |
1,096 |
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2. |
19. 25. Change Section 1106.6 and Table 1106.6 of
the IPC to read:
1106.6 Size of roof gutters. The size of semicircular gutters shall be based on the maximum projected roof area in accordance with Table 1106.6.
Table 1106.6 Size of Semicircular Roof Gutters |
||||||
Diameter of Gutters (inches) |
Horizontally Projected Roof Area (square feet) |
|||||
Rainfall rate (inches per hour) |
||||||
1 |
2 |
3 |
4 |
5 |
6 |
|
1/16 unit vertical in 12 units horizontal (0.5% slope) |
||||||
3 |
680 |
340 |
226 |
170 |
136 |
113 |
1/8 unit vertical in 12 units horizontal (1% slope) |
||||||
3 |
960 |
480 |
320 |
240 |
192 |
160 |
1/4 unit vertical in 12 units horizontal (2% slope) |
||||||
3 |
1,360 |
680 |
454 |
340 |
272 |
226 |
1/2 unit vertical in 12 units horizontal (4% slope) |
||||||
3 |
1,920 |
960 |
640 |
480 |
384 |
320 |
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2. |
26. Add Section 1114 Values for Continuous Flow to the IPC.
27. Add Section 1114.1 to the IPC to read:
1114.1 Equivalent roof area. Where there is a continuous or semicontinuous discharge into the building storm drain or building storm sewer, such as from a pump, ejector, air conditioning plant, or similar device, each gallon per minute (L/m) of such discharge shall be computed as being equivalent to 96 square feet (9 m2) of roof area, based on a rainfall rate of 1 inch (25.4 mm) per hour.
20. 28. Change Sections 1301.1 through 1301.12
and add Sections 1301.13 through 1301.18, including subsections, to the IPC to
read:
1301.1 Scope. The provisions of Chapter 13 shall govern the materials, design, construction, and installation of nonpotable water systems subject to this code. In addition to the applicable provision of this section, reclaimed water shall comply with the requirements of Section 1304.
1301.1.1 Design of nonpotable water systems. All portions of nonpotable water systems subject to this code shall be constructed using the same standards and requirements for the potable water systems or drainage systems as provided for in this code unless otherwise specified in this chapter.
1301.2 Makeup water. Makeup water shall be provided for all nonpotable water supply systems. The makeup water system shall be designed and installed to provide supply of water in the amounts and at the pressures specified in this code. The makeup water supply shall be potable and be protected against backflow in accordance with the applicable requirements of Section 608.
1301.2.1 Makeup water sources. Potable water shall be provided as makeup water for reclaimed water systems. Nonpotable water shall be permitted to serve as makeup water for gray water and rainwater systems.
1301.2.2 Makeup water supply valve. A full-open valve shall be provided on the makeup water supply line.
1301.2.3 Control valve alarm. Makeup water systems shall be fitted with a warning mechanism that alerts the user to a failure of the inlet control valve to close correctly. The alarm shall activate before the water within the storage tank begins to discharge into the overflow system.
1301.3 Sizing. Nonpotable water distribution systems shall be designed and sized for peak demand in accordance with approved engineering practice methods that comply with the applicable provisions of Chapter 6.
1301.4 Signage required. All nonpotable water outlets, other than water closets and urinals, such as hose connections, open-ended pipes, and faucets shall be identified at the point of use for each outlet with signage that reads as follows: "Nonpotable water is utilized for (insert application name). Caution: nonpotable water. DO NOT DRINK." The words shall be legibly and indelibly printed on a tag or sign constructed of corrosion-resistant waterproof material or shall be indelibly printed on the fixture. The letters of the words shall be not less than 0.5 inches (12.7 mm) in height and in colors in contrast to the background on which they are applied. The pictograph shown in Figure 1301.4 shall appear on the signage required by this section.
|
1301.5 Potable water supply system connections. Where a potable water supply system is connected to a nonpotable water system, the potable water supply shall be protected against backflow in accordance with the applicable provisions of Section 608.
1301.6 Nonpotable water system connections. Where a nonpotable water system is connected and supplies water to another nonpotable water system, the nonpotable water system that supplies water shall be protected against backflow in accordance with the applicable provisions of Section 608.
1301.7 Approved components and materials. Piping, plumbing components, and materials used in the nonpotable water drainage and distribution systems shall be approved for the intended application and compatible with the water and any disinfection or treatment systems used.
1301.8 Insect and vermin control. Nonpotable water systems shall be protected to prevent the entrance of insects and vermin into storage and piping systems. Screen materials shall be compatible with system material and shall not promote corrosion of system components.
1301.9 Freeze protection. Nonpotable water systems shall be protected from freezing in accordance with the applicable provisions of Chapter 3.
1301.10 Nonpotable water storage tanks. Nonpotable water storage tanks shall be approved for the intended application and comply with Sections 1301.10.1 through 1301.10.12.
1301.10.1 Sizing. The holding capacity of storage tanks shall be sized for the intended use.
1301.10.2 Inlets. Storage tank inlets shall be designed to introduce water into the tank and avoid agitating the contents of the storage tank. The water supply to storage tanks shall be controlled by fill valves or other automatic supply valves designed to stop the flow of incoming water before the tank contents reach the overflow pipes.
1301.10.3 Outlets. Outlets shall be located at least 4 inches (102 mm) above the bottom of the storage tank and shall not skim water from the surface.
1301.10.4 Materials and location. Storage tanks shall be constructed of material compatible with treatment systems used to treat water. Above grade storage vessels shall be constructed using opaque, UV-resistant materials such as tinted plastic, lined metal, concrete, or wood or painted to prevent algae growth. Above grade storage tanks shall be protected from direct sunlight unless their design specifically incorporates the use of the sunlight heat transfer. Wooden storage tanks shall be provided with a flexible liner. Storage tanks and their manholes shall not be located directly under soil or waste piping or sources of contamination.
1301.10.5 Foundation and supports. Storage tanks shall be supported on a firm base capable of withstanding the storage tank's weight when filled to capacity. Storage tanks shall be supported in accordance with the applicable provisions of the IBC.
1301.10.5.1 Ballast. Where the soil can become saturated, an underground storage tank shall be ballasted, or otherwise secured, to prevent the effects of buoyancy. The combined weight of the tank and hold down ballast shall meet or exceed the buoyancy force of the tank. Where the installation requires a foundation, the foundation shall be flat and shall be designed to support the storage tank weight when full, consistent with the bearing capability of adjacent soil.
1301.10.5.2 Structural support. Where installed below grade, storage tank installations shall be designed to withstand earth and surface structural loads without damage.
1301.10.6 Overflow. The storage tank shall be equipped with an overflow pipe having a diameter not less than that shown in Table 606.5.4. The overflow outlet shall discharge at a point not less than 6 inches (152 mm) above the roof or roof drain, floor or floor drain, or over an open water-supplied fixture. The overflow outlet shall terminate through a check valve. Overflow pipes shall not be directed on walkways. The overflow drain shall not be equipped with a shutoff valve. A minimum of one cleanout shall be provided on each overflow pipe in accordance with the applicable provisions of Section 708.
1301.10.7 Access. A minimum of one access opening shall be provided to allow inspection and cleaning of the tank interior. Access openings shall have an approved locking device or other approved method of securing access. Below grade storage tanks, located outside of the building, shall be provided with either a manhole not less than 24 inches (610 mm) square or a manhole with an inside diameter not less than 24 inches (610 mm). The design and installation of access openings shall prohibit surface water from entering the tank. Each manhole cover shall have an approved locking device or other approved method of securing access.
Exception: Storage tanks under 800 gallons (3028 L) in volume installed below grade shall not be required to be equipped with a manhole, but shall have an access opening not less than 8 inches (203 mm) in diameter to allow inspection and cleaning of the tank interior.
1301.10.8 Venting. Storage tanks shall be vented. Vents shall not be connected to sanitary drainage system. Vents shall be at least equal in size to the internal diameter of the drainage inlet pipe or pipes connected to the tank. Where installed at grade, vents shall be protected from contamination by means of a U-bend installed with the opening directed downward. Vent outlets shall extend a minimum of 12 inches (304.8 mm) above grade, or as necessary to prevent surface water from entering the storage tank. Vent openings shall be protected against the entrance of vermin and insects. Vents serving gray water tanks shall terminate in accordance with the applicable provisions of Sections 903 and 1301.8.
1301.10.9 Drain. Where drains are provided they shall be located at the lowest point of the storage tank. The tank drain pipe shall discharge as required for overflow pipes and shall not be smaller in size than specified in Table 606.5.7. A minimum of one cleanout shall be provided on each drain pipe in accordance with Section 708.
1301.10.10 Labeling and signage. Each nonpotable water storage tank shall be labeled with its rated capacity and the location of the upstream bypass valve. Underground and otherwise concealed storage tanks shall be labeled at all access points. The label shall read: "CAUTION: NONPOTABLE WATER DO NOT DRINK." Where an opening is provided that could allow the entry of personnel, the opening shall be marked with the words: "DANGER CONFINED SPACE." Markings shall be indelibly printed on a tag or sign constructed of corrosion-resistant waterproof material mounted on the tank or shall be indelibly printed on the tank. The letters of the words shall be not less than 0.5 inches (12.7 mm) in height and shall be of a color in contrast with the background on which they are applied.
1301.10.11 Storage tank tests. Storage tanks shall be tested in accordance with the following:
1. Storage tanks shall be filled with water to the overflow line prior to and during inspection. All seams and joints shall be left exposed and the tank shall remain watertight without leakage for a period of 24 hours.
2. After 24 hours, supplemental water shall be introduced for a period of 15 minutes to verify proper drainage of the overflow system and verify that there are no leaks.
3. Following a successful test of the overflow, the water level in the tank shall be reduced to a level that is at 2 inches (50.8 mm) below the makeup water offset point. The tank drain shall be observed for proper operation. The makeup water system shall be observed for proper operation, and successful automatic shutoff of the system at the refill threshold shall be verified. Water shall not be drained from the overflow at any time during the refill test.
4. Air tests shall be permitted in lieu of water testing as recommended by the tank manufacturer or the tank standard.
1301.10.12 Structural strength. Storage tanks shall meet the applicable structural strength requirements of the IBC.
1301.11 Trenching requirements for nonpotable water system piping. Underground nonpotable water system piping shall be horizontally separated from the building sewer and potable water piping by 5 feet (1524 mm) of undisturbed or compacted earth. Nonpotable water system piping shall not be located in, under, or above sewage systems cesspools, septic tanks, septic tank drainage fields, or seepage pits. Buried nonpotable system piping shall comply with the requirements of this code for the piping material installed.
Exceptions:
1. The required separation distance shall not apply where the bottom of the nonpotable water pipe within 5 feet (1524 mm) of the sewer is equal to or greater than 12 inches (305 mm) above the top of the highest point of the sewer and the pipe materials conforms to Table 702.3.
2. The required separation distance shall not apply where the bottom of the potable water service pipe within 5 feet (1524 mm) of the nonpotable water pipe is a minimum of 12 inches (305 mm) above the top of the highest point of the nonpotable water pipe and the pipe materials comply with the requirements of Table 605.4.
3. Nonpotable water pipe is permitted to be located in the same trench with building sewer piping, provided that such sewer piping is constructed of materials that comply with the requirements of Table 702.2.
4. The required separation distance shall not apply where a nonpotable water pipe crosses a sewer pipe, provided that the pipe is sleeved to at least 5 feet (1524 mm) horizontally from the sewer pipe centerline on both sides of such crossing with pipe materials that comply with Table 702.2.
5. The required separation distance shall not apply where a potable water service pipe crosses a nonpotable water pipe provided that the potable water service pipe is sleeved for a distance of at least 5 feet (1524 mm) horizontally from the centerline of the nonpotable pipe on both sides of such crossing with pipe materials that comply with Table 702.2.
1301.12 Outdoor outlet access. Sillcocks, hose bibs, wall hydrants, yard hydrants, and other outdoor outlets that are supplied by nonpotable water shall be located in a locked vault or shall be operable only by means of a removable key.
1301.13 Drainage and vent piping and fittings. Nonpotable drainage and vent pipe and fittings shall comply with the applicable material standards and installation requirements in accordance with provisions of Chapter 7.
1301.13.1. Labeling and marking. Identification of nonpotable drainage and vent piping shall not be required.
1301.14 Pumping and control system. Mechanical equipment, including pumps, valves, and filters, shall be accessible and removable in order to perform repair, maintenance, and cleaning. The minimum flow rate and flow pressure delivered by the pumping system shall be designed for the intended application in accordance with the applicable provisions of Section 604.
1301.15 Water-pressure reducing valve or regulator. Where the water pressure supplied by the pumping system exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the nonpotable water distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with the applicable provisions of Section 604.8.
1301.16 Distribution pipe. Distribution piping utilized in nonpotable water stems shall comply with Sections 1301.16.1 through 1301.16.4.
1301.16.1 Materials, joints, and connections. Distribution piping and fittings shall comply with the applicable material standards and installation requirements in accordance with applicable provisions of Chapter 6.
1301.16.2 Design. Distribution piping shall be designed and sized in accordance with the applicable provisions of Chapter 6.
1301.16.3 Labeling and marking. Distribution piping labeling
and marking shall comply with Section 608.8 608.9.
1301.16.4 Backflow prevention. Backflow preventers shall be installed in accordance with the applicable provisions of Section 608.
1301.17 Tests and inspections. Tests and inspections shall be performed in accordance with Sections 1301.17.1 through 1301.17.5.
1301.17.1 Drainage and vent pipe test. Drain, waste, and vent piping used for gray water and rainwater nonpotable water systems shall be tested in accordance with the applicable provisions of Section 312.
1301.17.2 Storage tank test. Storage tanks shall be tested in accordance with the Section 1301.10.11.
1301.17.3 Water supply system test. Nonpotable distribution piping shall be tested in accordance with Section 312.5.
1301.17.4 Inspection and testing of backflow prevention assemblies. The testing of backflow preventers and backwater valves shall be conducted in accordance with Section 312.10.
1301.17.5 Inspection of vermin and insect protection. Inlets and vent terminations shall be visually inspected to verify that each termination is installed in accordance with Section 1301.10.8.
1301.18 Operation and maintenance manuals. Operations and maintenance materials for nonpotable water systems shall be provided as prescribed by the system component manufacturers and supplied to the owner to be kept in a readily accessible location.
21. 29. Change the title of Section 1302 of the
IPC to "Gray Water Nonpotable Water Systems."
22. 30. Change Sections 1302.1 through 1302.6,
including subsections, of the IPC to read as follows and delete Sections
1302.7 through 1302.13:
1302.1 Gray water nonpotable water systems. This code is applicable to the plumbing fixtures, piping or piping systems, storage tanks, drains, appurtenances, and appliances that are part of the distribution system for gray water within buildings and to storage tanks and associated piping that are part of the distribution system for gray water outside of buildings. This code does not regulate equipment used for, or the methods of, processing, filtering, or treating gray water, that may be regulated by the Virginia Department of Health or the Virginia Department of Environmental Quality.
1302.1.1 Separate systems. Gray water nonpotable water systems, unless approved otherwise under the permit from the Virginia Department of Health, shall be separate from the potable water system of a building with no cross connections between the two systems except as permitted by the Virginia Department of Health.
1302.2 Water quality. Each application of gray water reuse shall meet the minimum water quality requirements set forth in Sections 1302.2.1 through 1302.2.4 unless otherwise superseded by other state agencies.
1302.2.1 Disinfection. Where the intended use or reuse application for nonpotable water requires disinfection or other treatment or both, it shall be disinfected as needed to ensure that the required water quality is delivered at the point of use or reuse.
1302.2.2 Residual disinfectants. Where chlorine is used for disinfection, the nonpotable water shall contain not more than 4 parts per million (4 mg/L) of free chlorine, combined chlorine, or total chlorine. Where ozone is used for disinfection, the nonpotable water shall not exceed 0.1 parts per million (by volume) of ozone at the point of use.
1302.2.3 Filtration. Water collected for reuse shall be filtered as required for the intended end use. Filters shall be accessible for inspection and maintenance. Filters shall utilize a pressure gauge or other approved method to indicate when a filter requires servicing or replacement. Shutoff valves installed immediately upstream and downstream of the filter shall be included to allow for isolation during maintenance.
1302.2.4 Filtration required. Gray water utilized for water closet and urinal flushing applications shall be filtered by a 100 micron or finer filter.
1302.3 Storage tanks. Storage tanks utilized in gray water nonpotable water systems shall comply with Section 1301.10.
1302.4 Retention time limits. Untreated gray water shall be retained in storage tanks for a maximum of 24 hours.
1302.5 Tank Location. Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table 1302.5.1.
|
Table 1302.5.1 |
|
|
Element |
Minimum Horizontal Distance |
|
Lot line adjoining private lots |
5 |
|
Sewage systems |
5 |
|
Septic tanks |
5 |
|
Water wells |
50 |
|
Streams and lakes |
50 |
|
Water service |
5 |
|
Public water main |
10 |
1302.6 Valves. Valves shall be supplied on gray water nonpotable water drainage systems in accordance with Sections 1302.6.1 and 1302.6.2.
1302.6.1 Bypass valve. One three-way diverter valve certified to NSF 50 or other approved device shall be installed on collection piping upstream of each storage tank, or drainfield, as applicable, to divert untreated gray water to the sanitary sewer to allow servicing and inspection of the system. Bypass valves shall be installed downstream of fixture traps and vent connections. Bypass valves shall be labeled to indicate the direction of flow, connection, and storage tank or drainfield connection. Bypass valves shall be provided with access for operation and maintenance. Two shutoff valves shall not be installed to serve as a bypass valve.
1302.6.2 Backwater valve. Backwater valves shall be installed on each overflow and tank drain pipe to prevent unwanted water from draining back into the storage tank. If the overflow and drain piping arrangement is installed to physically not allow water to drain back into the tank, such as in the form of an air gap, backwater valves shall not be required. Backwater valves shall be constructed and installed in accordance with Section 715.
23. 31. Delete Sections 1302.7 through 1302.13.4,
including subsections, of the IPC.
32. Change the title of Section 1303 of the IPC to "Rainwater Nonpotable Water Systems."
24. 33. Change Sections 1303.1 through 1303.10,
including subsections, of the IPC to read as follows and delete Sections
1303.11 through 1303.16:
1303.1 General. The provisions of this section shall govern the design, construction, installation, alteration, and repair of rainwater nonpotable water systems for the collection, storage, treatment, and distribution of rainwater for nonpotable applications. The provisions of CSA B805/ICC 805 shall be permitted as an alternative to the provisions contained in this section for the design, construction, installation, alteration, and repair of rainwater nonpotable water systems for the collection, storage, treatment, and distribution of rainwater for nonpotable applications. Roof runoff or stormwater runoff collection surfaces shall be limited to roofing materials, public pedestrian accessible roofs, and subsurface collection identified in CSA B805/ICC 805 Table 7.1. Stormwater runoff shall not be collected from any other surfaces.
1303.2 Water quality. Each application of rainwater reuse shall meet the minimum water quality requirements set forth in Sections 1303.2.1 through 1303.2.4 unless otherwise superseded by other state agencies.
1303.2.1 Disinfection. Where the intended use or reuse application for nonpotable water requires disinfection or other treatment or both, it shall be disinfected as needed to ensure that the required water quality is delivered at the point of use or reuse.
1303.2.2 Residual disinfectants. Where chlorine is used for disinfection, the nonpotable water shall contain not more than 4 parts per million (4 mg/L) of free chlorine, combined chlorine, or total chlorine. Where ozone is used for disinfection, the nonpotable water shall not exceed 0.1 parts per million (by volume) of ozone at the point of use.
1303.2.3 Filtration. Water collected for reuse shall be filtered as required for the intended end use. Filters shall be accessible for inspection and maintenance. Filters shall utilize a pressure gauge or other approved method to indicate when a filter requires servicing or replacement. Shutoff valves installed immediately upstream and downstream of the filter shall be included to allow for isolation during maintenance.
1303.2.4 Filtration required. Rainwater utilized for water closet and urinal flushing applications shall be filtered by a 100 micron or finer filter.
1303.3 Collection surface. Rainwater shall be collected only from aboveground impervious roofing surfaces constructed from approved materials. Overflow or discharge piping from appliances or equipment, or both, including but not limited to evaporative coolers, water heaters, and solar water heaters shall not discharge onto rainwater collection surfaces.
1303.4 Collection surface diversion. At a minimum, the first
0.04 inches (1.016 mm) of each rain event of 25 gallons (94.6 L) per 1000
1,000 square feet (92.9 m2) shall be diverted from the
storage tank by automatic means and not require the operation of manually operated
valves or devices. Diverted water shall not drain onto other collection
surfaces that are discharging to the rainwater system or to the sanitary sewer.
Such water shall be diverted from the storage tank and discharged in an
approved location.
1303.5 Pre-tank filtration. Downspouts, conductors, and leaders shall be connected to a pre-tank filtration device. The filtration device shall not permit materials larger than 0.015 inches (0.4 mm).
1303.6 Roof gutters and downspouts. Gutters and downspouts shall be constructed of materials that are compatible with the collection surface and the rainwater quality for the desired end use. Joints shall be made watertight.
1303.6.1 Slope. Roof gutters, leaders, and rainwater collection piping shall slope continuously toward collection inlets. Gutters and downspouts shall have a slope of not less than 1 unit in 96 units along their entire length and shall not permit the collection or pooling of water at any point.
Exception: Siphonic roof drainage systems installed in accordance with Chapter 11 shall not be required to have slope.
1303.6.2 Size. Gutters and downspouts shall be installed and sized in accordance with Section 1106.6 and local rainfall rates.
1303.6.3 Cleanouts. Cleanouts or other approved openings shall be provided to permit access to all filters, flushes, pipes, and downspouts.
1303.7 Storage tanks. Storage tanks utilized in rainwater nonpotable water systems shall comply with Section 1301.10.
1303.8 Location. Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table 1303.8.1.
|
Table 1303.8.1 |
|
|
Element |
Minimum Horizontal Distance |
|
Lot line adjoining private lots |
5 |
|
Sewage systems |
5 |
|
Septic tanks |
5 |
1303.9 Valves. Valves shall be installed in collection and conveyance drainage piping of rainwater nonpotable water systems in accordance with Sections 1303.9.1 and 1303.9.2.
1303.9.1 Influent diversion. A means shall be provided to divert storage tank influent to allow maintenance and repair of the storage tank system.
1303.9.2 Backwater valve. Backwater valves shall be installed on each overflow and tank drain pipe to prevent unwanted water from draining back into the storage tank. If the overflow and drain piping arrangement is installed to physically not allow water to drain back into the tank, such as in the form of an air gap, backwater valves shall not be required. Backwater valves shall be constructed and installed in accordance with Section 715.
1303.10 Tests and inspections. Tests and inspections shall be performed in accordance with Sections 1303.10.1 through 1303.10.2.
1303.10.1 Roof gutter inspection and test. Roof gutters shall be inspected to verify that the installation and slope is in accordance with Section 1303.6.1. Gutters shall be tested by pouring a minimum of one gallon of water into the end of the gutter opposite the collection point. The gutter being tested shall not leak and shall not retain standing water.
1303.10.2 Collection surface diversion test. A collection surface diversion test shall be performed by introducing water into the gutters or onto the collection surface area. Diversion of the first quantity of water in accordance with the requirements of Section 1303.4 shall be verified.
25. 34. Delete Sections 1303.11 through 1303.16.4,
including subsections, of the IPC.
35. Change Sections 1304.1 and 1304.2 of the IPC to read
as follows and delete Sections 1304.3 and 1304.4:
1304.1 General. Reclaimed water, water reclamation systems, reclaimed water distribution systems, and allowable nonpotable reuses of reclaimed water are as defined or specified in and governed by the Virginia Water Reclamation and Reuse Regulation (9VAC25-740). Permits from the Virginia State Water Control Board are required for such systems and reuses. The provisions of Section 1304 shall govern the design, construction, installation, alterations, and repair of plumbing fixtures, piping or piping systems, storage tanks, drains, appurtenances, and appliances that are part of the distribution system for reclaimed water within buildings and to storage tanks for reclaimed water as defined in the Virginia Water Reclamation and Reuse Regulation (9VAC25-740) and associated piping outside of buildings that deliver reclaimed water into buildings. Where conflicts occur between this code and the Virginia Water Reclamation and Reuse Regulation (9VAC25-740), the provisions of the Virginia Water Reclamation and Reuse Regulation (9VAC25-740) shall apply unless determined otherwise by the Virginia Department of Environmental Quality and DHCD through a memorandum of agreement.
1304.2 Design of reclaimed water systems. The design of reclaimed water systems shall conform to applicable requirements of Section 1301.
Exception: The design of reclaimed water systems shall conform to applicable requirements of the Virginia Water Reclamation and Reuse Regulation (9VAC25-740) for the following:
1. Identification, labeling, and posting of signage for reclaimed water systems in lieu of signage requirements described in Section 1301.4.
2. Sizing of system storage as defined in the Virginia Water Reclamation and Reuse Regulation (9VAC25-740), in addition to storage sizing requirements described in Section 1301.10.1.
3. Signage and labeling for reclaimed water storage in addition to labeling and signage requirements described in Section 1301.10.10.
4. Minimum separation distances and configurations for in-ground reclaimed water distribution piping in lieu of trenching requirements for nonpotable water systems described in Section 1301.11.
36. Delete Sections 1304.3 and 1304.4.2, including subsections, of the IPC.
37. Add the following referenced standards to Chapter 15 as follows: (Standards not shown remain the same.)
|
Standard Reference Number |
Title |
Referenced in Code Section Number |
|
ASTM F1871-2011 |
Standard Specification for Folded/Formed Poly (Vinyl Chloride) Pipe Type A for Existing Sewer and Conduit Rehabilitation |
717.6 |
|
ASTM F1504-2014 |
Standard Specification for Folded Poly (Vinyl Chloride) (PVC) for Existing Sewer and Conduit Rehabilitation |
717.6 |
|
CSA B805-18/ICC 805-2018 |
Rainwater Harvesting Systems |
1303.1 |
C. Modify the Group A-5 following Assembly
"Description" category of Table 2902.1 of the IBC to read:
|
Stadiums, amusement parks, pools, bleachers, and grandstands
for outdoor sporting events and activities |
D. Add footnote "f" "g" to
Table 2902.1 of the IBC to read:
f. g. The occupant load for pools shall be in
accordance with the "Skating rinks, swimming pools" category of Table
1004.1.2 1004.5.
13VAC5-63-330. Chapter 30 Elevators and conveying systems.
A. Change Section 3002.4 of the IBC to read:
3002.4 Elevator car to accommodate ambulance stretcher. Where
elevators are provided in buildings four or more stories above, or four or more
stories below, grade plane, at least one elevator shall be provided for fire
department emergency access to all floors. The elevator car shall be of such a
size and arrangement to accommodate an ambulance stretcher 24 inches by 84
inches (610 mm by 2134 mm) with not less than five-inch (127 mm) radius
corners, in the horizontal, open position and shall be identified by the
international symbol for emergency medical services (star of life). The symbol
shall not be less than three inches (76 mm) high and shall be placed inside on
both sides of the hoistway door frame on the designated and alternate
landing floors required to be established by ASME A17.1.
Exception: Elevators in multistory dwelling units or guest rooms.
B. Change Section 3003.3 of the IBC to read:
3003.3 Fire service elevator keys. All elevators shall be equipped to operate with either a standardized or non-standardized fire service elevator key in accordance with the IFC.
C. Change Section 3005.4 of the IBC to read:
3005.4 Machine and control rooms, control spaces, and machinery spaces. Elevator machine rooms, rooms and spaces housing elevator controllers, and machinery spaces outside of but attached to a hoistway that have openings into the hoistway shall be enclosed with fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. The fire-resistance rating shall not be less than the required rating of the hoistway enclosure. Openings in the fire barriers shall be protected with assemblies having a fire protection rating not less than that required for the hoistway enclosure doors.
Exception Exceptions:
1. Where elevator machine rooms, rooms and spaces housing elevator controllers, and machinery spaces do not abut and do not have openings to the hoistway enclosure they serve, the fire barrier constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, shall be permitted to be reduced to a one-hour fire-resistance rating.
2. In buildings four stories or less above grade plane when elevator machine rooms, rooms and spaces housing elevator controllers, and machinery spaces do not abut and have no openings to the hoistway enclosure they serve, the elevator machine rooms, rooms and spaces housing elevator controllers, and machinery spaces are not required to be fire-resistance rated.
D. Add Section 3005.7 to the IBC to read:
3005.7 Machine-room-less designs. Where machine-room-less designs are utilized they shall comply with the provisions of ASME A17.1 and incorporate the following:
1. Where the elevator car-top will be used as a work platform, it shall be equipped with permanently installed guards on all open sides. Guards shall be permitted to be of collapsible design, but otherwise must conform to all applicable requirements of this code for guards.
2. Where the equipment manufacturer's procedures for machinery removal and replacement depend on overhead structural support or lifting points, such supports or lifting points shall be permanently installed at the time of initial equipment installation.
3. Where the structure that the elevator will be located in is required to be fully sprinklered by this code, the hoistway that the elevator machine is located in shall be equipped with a fire suppression system as a machine room in accordance with NFPA 13. Smoke detectors for the automatic initiation of Phase I Emergency Recall Operation, and heat detectors or other approved devices that automatically disconnect the main line power supply to the elevators, shall be installed within the hoistway.
E. Delete Section 3006 of the IBC in its entirety.
F. Change the exception to 3007.6 to read:
Exception: Where a fire service access elevator has two entrances onto a floor, the second entrance shall be permitted to be protected in accordance with IBC Section 3006.3.
G. Change Section 3008.1 of the IBC to read:
3008.1 General. Where elevators in buildings greater than 420
feet (128 016 (128,016 mm) in building height are to be used for
occupant self-evacuation during fires, all passenger elevators for general
public use shall comply with this section.
13VAC5-63-336. Chapter 31 Special construction.
A. Change the title of IBC Section 3109 to read:
Swimming Pools, Swimming Pool Enclosures, and Aquatic Recreational Facilities.
B. Change Section 3109.1 of the IBC to read as follows, add Section 3109.1.1 to the IBC to read as follows, and delete the remainder of Section 3109 of the IBC:
3109.1 General. Swimming pools, swimming pool enclosures, and aquatic recreational facilities, as that term is defined in the ISPSC, shall comply with applicable provisions of the ISPSC.
3109.1.1 Changes to the ISPSC. The following changes shall be made to the ISPSC:
1. Add Section 410.2 and related subsections to the ISPSC to read:
410.2 Showers. Showers shall be in accordance with Sections 410.2.1 through 410.2.5.
410.2.1 Deck hand shower or shower spray unit. Not less than one and not greater than half of the total number of showers required by Section 410.1 shall be a hand shower or spray shower unit located on the deck of or at the entrance of each pool.
410.2.2 Anti-scald device. Where heated water is provided to the showers, the shower water supply shall be controlled by an anti-scald device.
410.2.3 Water heater and mixing valve. Bather access to water heaters and thermostatically controlled mixing valves for showers shall be prohibited.
410.2.4 Flow rate. Each showerhead shall have a water flow of not less than 2 gallons per minute (7.6 lpm).
410.2.5 Temperature. At each showerhead, the heated shower water temperature shall not exceed 120oF (49oC) and shall not be less than 90oF (32oC).
2. Change the title of Section 609 of the ISPSC to read:
Dressing and Sanitary Facilities.
3. Change Section 609.3.1 of the ISPSC to read:
609.3.1 Deck hand shower or shower spray unit. Not less than one and not greater than half of the total number of showers required by Section 609.2 shall be a hand shower or shower spray unit located on the deck of or at the entrance of each pool.
C. Delete Section 3113 of the IBC in its entirety.
13VAC5-63-340. Chapter 33 Safeguards during construction.
A. Delete Section 3302.1 of the IBC.
B. Delete IBC Sections 3303 and 3305 and
3305.1 in their entirety.
C. Change Section 3310.2 of the IBC to read:
3310.2 Maintenance of means of egress. Means of egress and required accessible means of egress shall be maintained at all times during construction.
13VAC5-63-360. Chapter 35 Referenced standards.
Change the referenced standards in Chapter 35 of the IBC as follows (standards not shown remain the same):
Standard reference number |
Title |
Referenced in code section number |
ASTM E329‑02 |
Standard Specification for Agencies Engaged in the Testing and/or Inspection of Materials Used in Construction |
1703.1, 1703.1.3 |
API 650‑09 |
Welded Steel Tanks for Oil Storage |
|
API 653‑09 |
Tank Inspection, Repair, Alteration and Reconstruction |
|
|
|
|
NFPA 91‑15 |
Standard for Exhaust Systems for Air Conveying of Vapors, Mists and Particulate Solids |
|
|
International Swimming Pool and Spa Code |
202, 3109.1, 3109.1.1 |
TFI RMIP‑09 |
Aboveground Storage Tanks Containing Liquid Fertilizer, Recommended Mechanical Integrity Practices |
|
UL 2075‑13 |
Standard for Gas and Vapor Detectors and Sensors |
915.4, 915.5.1, 915.5.3 |
Part II
Existing Buildings
13VAC5-63-400. Chapter 1 Administration; Section 101 General.
A. Section 101.1 Short title. The Virginia Uniform Statewide Building Code, Part II, Existing Buildings, may be cited as the "Virginia Existing Building Code" or as the "VEBC."
B. Section 101.2 Incorporation by reference. Chapters 2 - 16
of the 2015 2018 International Existing Building Code, published
by the International Code Council, Inc., are adopted and incorporated by
reference to be an enforceable part of the VEBC. The term "IEBC"
means the 2015 2018 International Existing Building Code,
published by the International Code Council, Inc. Any codes and standards
referenced in the IEBC are also considered to be part of the incorporation by
reference, except that such codes and standards are used only to the prescribed
extent of each such reference.
C. Section 101.3 Numbering system. A dual numbering system is used in the VEBC to correlate the numbering system of the Virginia Administrative Code with the numbering system of the IEBC. IEBC numbering system designations are provided in the catchlines of the Virginia Administrative Code sections and cross references between sections or chapters of the VEBC use only the IEBC numbering system designations. The term "chapter" is used in the context of the numbering system of the IEBC and may mean a chapter in the VEBC, a chapter in the IEBC or a chapter in a referenced code or standard, depending on the context of the use of the term. The term "chapter" is not used to designate a chapter of the Virginia Administrative Code, unless clearly indicated.
D. Section 101.4 Arrangement of code provisions. The VEBC is comprised of the combination of (i) the provisions of Chapter 1, Administration, which are established herein, (ii) Chapters 2 - 16 of the IEBC, which are incorporated by reference in Section 101.2, and (iii) the changes to the text of the incorporated chapters of the IEBC that are specifically identified, including any new chapters added. The terminology "changes to the text of the incorporated chapters of the IEBC that are specifically identified, including any new chapters added" shall also be referred to as the "state amendments to the IEBC." Such state amendments to the IEBC are set out using corresponding chapter and section numbers of the IEBC numbering system. In addition, since Chapter 1 of the IEBC is not incorporated as part of the VEBC, any reference to a provision of Chapter 1 of the IEBC in the provisions of Chapters 2 - 16 of the IEBC is generally invalid. However, where the purpose of such a reference would clearly correspond to a provision of Chapter 1 established herein, then the reference may be construed to be a valid reference to such corresponding Chapter 1 provision.
E. Section 101.5 Use of terminology and notes. The provisions of this code shall be used as follows:
1. The term "this code," or "the code," where used in the provisions of Chapter 1, in Chapters 2 - 16 of the IEBC, or in the state amendments to the IEBC, means the VEBC, unless the context clearly indicates otherwise.
2. The term "this code," or "the code," where used in a code or standard referenced in the VEBC, means that code or standard, unless the context clearly indicates otherwise.
3. The term "USBC" where used in this code, means the VCC, unless the context clearly indicates otherwise.
4. The use of notes in Chapter 1 is to provide information only and shall not be construed as changing the meaning of any code provision.
5. Notes in the IEBC, in the codes and standards referenced in the IEBC and in the state amendments to the IEBC, may modify the content of a related provision and shall be considered to be a valid part of the provision, unless the context clearly indicates otherwise.
6. References to International Codes and standards, where used in this code, include state amendments made to those International Codes and standards in the VCC.
Note: See Section 101.2 of the VCC for a list of major codes and standards referenced in the VCC.
F. Section 101.6 Order of precedence. The provisions of this code shall be used as follows:
1. The provisions of Chapter 1 of this code supersede any provisions of Chapters 2 - 16 of the IEBC that address the same subject matter and impose differing requirements.
2. The provisions of Chapter 1 of this code supersede any provisions of the codes and standards referenced in the IEBC that address the same subject matter and impose differing requirements.
3. The state amendments to the IEBC supersede any provisions of Chapters 2 - 16 of the IEBC that address the same subject matter and impose differing requirements.
4. The state amendments to the IEBC supersede any provisions of the codes and standards referenced in the IEBC that address the same subject matter and impose differing requirements.
5. The provisions of Chapters 2 - 16 of the IEBC supersede any provisions of the codes and standards referenced in the IEBC that address the same subject matter and impose differing requirements.
G. Section 101.7 Administrative provisions. The provisions of Chapter 1 establish administrative requirements, which include but are not limited to provisions relating to the scope and enforcement of the code. Any provisions of Chapters 2 - 16 of the IEBC or any provisions of the codes and standards referenced in the IEBC that address the same subject matter to a lesser or greater extent are deleted and replaced by the provisions of Chapter 1. Further, any administrative requirements contained in the state amendments to the IEBC shall be given the same precedence as the provisions of Chapter 1. Notwithstanding the above, where administrative requirements of Chapters 2 - 16 of the IEBC or of the codes and standards referenced in the IEBC are specifically identified as valid administrative requirements in Chapter 1 of this code or in the state amendments to the IEBC, then such requirements are not deleted and replaced.
Note: The purpose of this provision is to eliminate overlap, conflicts and duplication by providing a single standard for administrative, procedural and enforcement requirements of this code.
H. Section 101.8 Definitions. The definitions of terms used in this code are contained in Chapter 2 along with specific provisions addressing the use of definitions. Terms may be defined in other chapters or provisions of the code and such definitions are also valid.
13VAC5-63-410. Section 102 Purpose and scope.
A. Section 102.1 Purpose. In accordance with § 36-99.01 of the Code of Virginia, the General Assembly of Virginia has declared that (i) there is an urgent need to improve the housing conditions of low and moderate income individuals and families, many of whom live in substandard housing, particularly in the older cities of the Commonwealth; (ii) there are large numbers of older residential buildings in the Commonwealth, both occupied and vacant, which are in urgent need of rehabilitation and must be rehabilitated if the state's citizens are to be housed in decent, sound, and sanitary conditions; and (iii) the application of those building code requirements currently in force to housing rehabilitation has sometimes led to the imposition of costly and time-consuming requirements that result in a significant reduction in the amount of rehabilitation activity taking place.
The General Assembly further declares that (i) there is an urgent need to improve the existing condition of many of the Commonwealth's stock of commercial properties, particularly in older cities; (ii) there are large numbers of older commercial buildings in the Commonwealth, both occupied and vacant, that are in urgent need of rehabilitation and that must be rehabilitated if the citizens of the Commonwealth are to be provided with decent, sound and sanitary work spaces; and (iii) the application of the existing building code to such rehabilitation has sometimes led to the imposition of costly and time-consuming requirements that result in a significant reduction in the amount of rehabilitation activity taking place.
B. Section 102.2 Scope. The provisions of this code shall govern construction and rehabilitation activities in existing buildings and structures.
C. 102.2.1 Change of occupancy to Group I-2 or I-3. A change of occupancy to Group I-2 or I-3 shall comply with the provisions of the VCC. Written application shall be made to the local building department for a new certificate of occupancy, and the new certificate of occupancy shall be obtained prior to the change of occupancy. When impractical to achieve compliance with the VCC for the new occupancy classification, the building official shall consider modifications upon application and as provided for in Section 106.3 of the VCC.
D. 102.2.2 Reconstruction, alteration, or repair in Group R-5 occupancies. Compliance with this section shall be an acceptable alternative to compliance with this code at the discretion of the owner or owner's agent. The VCC may be used for the reconstruction, alteration, or repair of Group R-5 buildings or structures subject to the following criteria:
1. Any reconstruction, alteration or repair shall not adversely affect the performance of the building or structure, or cause the building or structure to become unsafe or lower existing levels of health and safety.
2. Parts of the building or structure not being reconstructed, altered, or repaired shall not be required to comply with the requirements of the VCC applicable to newly constructed buildings or structures.
3. The installation of material or equipment, or both, that is neither required nor prohibited shall only be required to comply with the provisions of the VCC relating to the safe installation of such material or equipment.
4. Material or equipment, or both, may be replaced in the same location with material or equipment of a similar kind of capacity.
Exceptions:
1. This section shall not be construed to permit noncompliance with any applicable flood load or flood-resistant construction requirements of the VCC.
2. Reconstructed decks, balconies, porches, and similar structures located 30 inches (762 mm) or more above grade shall meet the current code provisions for structural loading capacity, connections, and structural attachment. This requirement excludes the configuration and height of handrails and guardrails.
5. In accordance with § 36-99.2 of the Code of Virginia, any
replacement glass installed in buildings constructed prior to the first edition
of the USBC shall meet the quality and standards for glass installed in new
buildings as are in effect at the time of installation. In addition, as a
requirement of this code, the installation of replacement of glass in buildings
constructed under any edition of the USBC shall be as required for new
installations installation or replacement of glass shall comply with
Section R308 or Chapter 24 of the VCC.
13VAC5-63-420. Section 103 Application of code.
A. Section 103.1 General. All administrative provisions of the VCC, including requirements for permits, inspections and approvals by the local building department, provisions for appeals from decisions of the local building department and the issuance of modifications, are applicable to the use of this code, except where this code sets out differing requirements. Where there is a conflict between a general requirement and a specific requirement in the IEBC, the specific requirement shall govern.
B. Section 103.1.1 Use of performance code. Compliance with the provisions of a nationally recognized performance code when approved as a modification shall be considered to constitute compliance with this code. All documents submitted as part of such consideration shall be retained in the permanent records of the local building department.
C. Section 103.1.2 Preliminary meeting. When requested by a prospective permit applicant or when determined necessary by the code official, the code official shall meet with the prospective permit applicant prior to the application for a permit to discuss plans for the proposed work or change of occupancy in order to establish the specific applicability of the provisions of this code.
D. Section 103.2 Change of occupancy. Prior to a change of occupancy of the building or structure, the owner or the owner's agent shall make written application to the local building department for a new certificate of occupancy and shall obtain the new certificate of occupancy.
When impractical to achieve compliance with this code for the new occupancy, the building official shall consider modifications upon application and as provided for in Section 106.3 of the VCC.
E. Section 103.3 Retrofit requirements. The local building department shall enforce the provisions of Section 1101 that require certain existing buildings to be retrofitted with fire protection systems and other safety equipment. Retroactive fire protection system requirements contained in the IFC shall not be applicable unless required for compliance with the provisions of Section 1101.
F. Section 103.4 Nonrequired equipment. The following criteria
for nonrequired equipment is are in accordance with § 36-103 of
the Code of Virginia. Building owners may elect to install partial or full fire
alarms or other safety equipment that was not required by the edition of the
VCC in effect at the time a building was constructed without meeting current
requirements of the code, provided the installation does not create a hazardous
condition. Permits for installation shall be obtained in accordance with the
VCC. In addition, as a requirement of this code, when such nonrequired
equipment is to be installed, the building official shall notify the
appropriate fire official or fire chief.
G. Section 103.4.1 Reduction in function or discontinuance of nonrequired fire protection systems. When a nonrequired fire protection system is to be reduced in function or discontinued, it shall be done in such a manner so as not to create a false sense of protection. Generally, in such cases, any features visible from interior areas shall be removed, such as sprinkler heads, smoke detectors, or alarm panels or devices, but any wiring or piping hidden within the construction of the building may remain. Approval of the proposed method of reduction or discontinuance shall be obtained from the building official.
H. Section 103.5 Equipment changes. Upon the replacement or
new installation of any fuel-burning appliances or equipment in existing
buildings, an inspection or inspections shall be conducted in accordance with
Section 113.3.1 of the VCC.
I. H. Section 103.6 103.5
Requirements relating to maintenance. Any requirements of the IEBC requiring
the maintenance of existing buildings or structures are invalid.
Note: Requirements for the maintenance of existing buildings and structures and for unsafe conditions are contained in the VMC.
J. I. Section 103.7 103.6 Use of
Appendix A. Appendix A of the IEBC provides guidelines for the seismic retrofit
of existing buildings. The use of this appendix is not mandatory but shall be
permitted to be utilized at the option of an owner, the owner's agent or the
RDP involved in a rehabilitation project. However, in no case shall the use of
Appendix A be construed to authorize the lowering of existing levels of health
or safety in buildings or structures being rehabilitated.
K. J. Section 103.8 103.7 Use of
Appendix B. Appendix B of the IEBC provides supplementary accessibility
requirements for existing buildings and facilities. All applicable requirements
of Appendix B shall be met in buildings and structures being rehabilitated.
L. K. Section 103.9 103.8 Use of
Resource A. Resource A of the IEBC provides guidelines for the evaluation of
fire resistance ratings of archaic materials and may be used in conjunction
with rehabilitation projects.
M. 103.10 L. 103.9 Construction documents.
Construction documents shall be submitted with the application for a permit.
The work proposed to be performed on an existing building or structure shall be
classified on the construction documents as repairs, alterations, change of
occupancy, addition, historic building, or moved building. All work areas
shall be identified on the construction documents. Alterations shall
further be identified classified as Level 1, Level 2, or
Level 3 2.
Exception: construction Construction documents
or classification of the work does not need to be submitted when the building
official determines the proposed work does not require such documents,
classification, or identification.
13VAC5-63-430. Chapter 2 Definitions.
A. Change Section 201.3 of the IEBC to read:
201.3 Terms defined in other codes. Where terms are not defined in this code and are defined in the other International Codes, such terms shall have the meanings ascribed to them in those codes, except that terms that are not defined in this code and that are defined in the VCC shall take precedence over other definitions.
B. Change the following definitions in Section 202 of the IEBC to read:
Alteration. Any construction or renovation to an existing
structure other than a repair or addition.
Building. A combination of materials, whether portable or fixed, having a roof to form a structure for the use or occupancy by persons or property. The word "building" shall be construed as though followed by the words "or part or parts thereof" unless the context clearly requires a different meaning. "Building" shall not include roadway tunnels and bridges owned by the Virginia Department of Transportation, which shall be governed by construction and design standards approved by the Commonwealth Transportation Board.
For application of this code, each portion of a building that is completely separated from other portions by fire walls complying with Section 706 of the VCC shall be considered as a separate building (see Section 503.1 of the VCC).
Change of occupancy. Either of the following shall be considered a change of occupancy where the current VCC requires a greater degree of accessibility, structural strength, fire protection, means of egress, ventilation or sanitation than is existing in the current building or structure:
1. Any change in the occupancy classification of a building or structure.
2. Any change in the purpose of, or a change in the level of activity within, a building or structure.
Note: The use and occupancy classification of a building or structure, shall be determined in accordance with Chapter 3 of the VCC.
Existing building. A building for which a legal certificate of occupancy has been issued under any edition of the USBC or approved by the building official when no legal certificate of occupancy exists, and that has been occupied for its intended use; or, a building built prior to the initial edition of the USBC.
Existing structure. A structure (i) for which a legal building permit has been issued under any edition of the USBC, (ii) that has been previously approved, or (iii) that was built prior to the initial edition of the USBC. For application of provisions in flood hazard areas, an existing structure is any building or structure for which the start of construction commenced before the effective date of the community's first flood plain management code, ordinance, or standard.
Substantial improvement. For the purpose of determining compliance with the flood provisions of this code, any improvement, including repair, reconstruction, rehabilitation, alteration, or addition, or other improvement of a building or structure or a portion thereof, the cost of which equals or exceeds 50% of the market value of the building or structure before the improvement or repair is started. If the building or structure has sustained substantial damage, any improvements are considered substantial improvement regardless of the actual improvement performed. The term does not, however, include either:
1. Any project for improvement of a building or structure required to correct existing health, sanitary, or safety code violations identified by the building official and that is the minimum necessary to assure safe living conditions; or
2. Any alteration of a historic structure, provided that the alteration will not preclude the building or structure's continued designation as a historic building or structure.
Work area. That intended room, space, or portion of a
building or structure where a wall or walls are added, relocated, or removed.
Work area excludes (i) the addition or elimination of any door or window; (ii)
the reconfiguration or extension of any system; (iii) the installation of any
additional equipment; (iv) the removal of finished flooring or ceiling
materials; (v) adjacent rooms or other rooms, spaces, or portions of the
building or structure where incidental work entailed by the intended work must
be performed; and (vi) portions of the building or structure where work not
initially intended is specifically required by this code.
C. Add the following definitions to Section 202 of the IEBC to read:
Building. A combination of materials, whether portable or
fixed, having a roof to form a structure for the use or occupancy by persons,
or property. The word "building" shall be construed as though
followed by the words "or part of parts thereof" unless the context
clearly requires a different meaning. "Building" shall not include
roadway tunnels and bridges owned by the Virginia Department of Transportation,
which shall be governed by construction and design standards approved by the
Virginia Commonwealth Transportation Board.
For application of this code, each portion of a building
that is completely separated from other portions by fire walls complying with
Section 706 of the VCC shall be considered as a separate building (see Section
503.1 of the VCC).
Existing structure. A structure (i) for which a legal
building permit has been issued under any edition of the USBC, (ii) which has
been previously approved, or (iii) which was built prior to the initial edition
of the USBC. For application of provisions in flood hazard areas, an existing
structure is any building or structure for which the start of construction
commenced before the effective date of the community's first flood plain
management code, ordinance, or standard.
Moved building or structure. An existing building or structure that is moved to a new location.
Structure. An assembly of materials forming a construction for occupancy or use including stadiums, gospel and circus tents, reviewing stands, platforms, stagings, observation towers, radio towers, water tanks, storage tanks (underground and aboveground), trestles, piers, wharves, swimming pools, amusement devices, storage bins, and other structures of this general nature but excluding water wells. The word "structure" shall be construed as though followed by the words "or part or parts thereof" unless the context clearly requires a different meaning. "Structure" shall not include roadway tunnels and bridges owned by the Virginia Department of Transportation, which shall be governed by construction and design standards approved by the Virginia Commonwealth Transportation Board.
D. Delete the following definitions from Section 202 of the IEBC:
Approved
Dangerous
Deferred submittal
Facility
Flood hazard area
Registered design professional in responsible charge
Relocatable building
Unsafe
Work area
13VAC5-63-431. Chapter 3 General provisions and special detailed requirements.
A. Change IEBC Section 301 to General.
B. Change Section 301.1 and delete Sections 301.1.1 through
301.1.4.2, including tables, of the IEBC. to read:
301.1 Applicability. The applicable provisions of this chapter shall be used in conjunction with the requirements in this code, and shall apply to all construction and rehabilitation.
C. Add Change Section 301.2 to the IEBC to read:
301.2 Occupancy and use. When determining the appropriate application of the referenced sections of this code, the occupancy and use of a building shall be determined in accordance with Chapter 3 of the VCC.
D. Change IEBC Section 302 to Building Materials and Systems.
E. Change Sections 302.1 through 302.3 302.2 of
the IEBC to read:
302.1 Existing materials. Materials already in use in a
building in compliance with requirements or approvals in effect at the time of
their erection or installation shall be permitted to remain in use unless the
VCC would not permit their use in buildings or structures of similar occupancy,
purpose, and location.
302.2 302.1 New and replacement materials. Except
as otherwise required or permitted by this code, materials permitted by the
applicable code for new construction shall be used. Like materials shall be
permitted for repairs and alterations, provided no hazard to life, health or
property is created. Hazardous materials shall not be used where the VCC would
not permit their use in buildings or structures of similar occupancy, purpose,
and location.
302.3 302.2 Existing seismic force-resisting
systems. Where the existing seismic force-resisting system is a type that can
be designated ordinary, values of R, Ω0, and Cd for
the existing seismic force-resisting system shall be those specified by the VCC
for an ordinary system unless it is demonstrated that the existing system will
provide performance equivalent to that of a detailed, intermediate, or special
system.
F. Delete Sections 302.4 and 302.5 302.3 through
302.6 of the IEBC.
G. Add Change IEBC Section 303 to Fire
escapes.
H. Add Change Sections 303.1 through 303.3.2,
including subsections, and add Sections 303.4 through 303.6, including
subsections, to the IEBC to read:
303.1 Where permitted. Fire escapes shall be permitted only
as provided for in Sections 303.1.1 through 303.1.4 comply with this
section and shall not constitute more than 50% of the required number of exits
nor more than 50% of the required exit capacity.
303.1.1 Existing fire escapes. Existing fire escapes shall
continue to be accepted as a component in the means of egress in existing
buildings only.
303.1.2 New fire escapes. Newly For other than Group
I-2, newly constructed fire escapes for existing buildings shall be
permitted only where exterior stairs cannot be utilized due to lot lines
limiting stair size or due to the sidewalks, alleys, or roads at grade level. New
fire escapes shall not incorporate ladders or access by windows.
Exception: Fire Replacement fire escapes that
are replaced or repaired shall only be required to or existing fire
escapes undergoing repairs shall comply with Sections 303.3 and 303.4 if
feasible, and if not feasible, such that the replaced or repaired fire
escape is not less safe than its existing condition to the greatest
extent possible.
303.1.3 Limitations. Fire escapes shall comply with this
section and shall not constitute more than 50% of the required number of exits
nor more than 50% of the required exit capacity.
303.1.4 Fire escapes required. For other than Group I-2,
where more than one exit is required, newly constructed fire escapes complying
with Section 303.6 shall be accepted as providing one of the required means of
egress. Replacement fire escapes or existing fire escapes undergoing repairs
shall comply with Sections 303.3 and 303.4 if feasible, and if not feasible, to
the greatest extent possible.
303.2 Location. Where located on the front of the building and where projecting beyond the building line, the lowest landing shall not be less than 7 feet (2134 mm) or more than 12 feet (3658 mm) above grade, and shall be equipped with a counterbalanced stairway to the street. In alleyways and thoroughfares less than 30 feet (9144 mm) wide, the clearance under the lowest landing shall not be less than 12 feet (3658 mm).
303.3 Construction. The fire escape shall be designed to support a live load of 100 pounds per square foot (4788 Pa) and shall be constructed of steel or other approved noncombustible materials. Fire escapes constructed of wood not less than nominal 2 inches (51 mm) thick are permitted on buildings of Type V construction. Walkways and railings located over or supported by combustible roofs in buildings of Types III and IV construction are permitted to be of wood not less than nominal 2 inches (51 mm) thick.
303.4 Dimensions. Stairs shall be at least 22 inches (559 mm) wide with risers not more than, and treads not less than, 8 inches (203 mm) and landings at the foot of stairs not less than 40 inches (1016 mm) wide by 36 inches (914 mm) long, located not more than 9 inches (203 mm) below the door.
303.5 Opening protectives. Openings within 10 feet (3048 mm) of newly constructed fire escape stairways shall be protected by fire assemblies having minimum 3/4-hour-fire-resistance ratings.
Exception: Opening protection shall not be required in buildings equipped throughout with an approved automatic sprinkler system.
303.6 Fire escape access and details. Newly constructed fire escapes shall comply with all of the following requirements:
1. Occupants shall have unobstructed access to the fire escape without having to pass through a room subject to locking.
2. Access to a new fire escape shall be through a door, except
that windows shall be permitted to provide access from single dwelling units or
sleeping units in Group Groups R-1, R-2 and I-1 occupancies or to
provide access from spaces having a maximum occupant load of 10 in other
occupancy classifications.
2.1. The window shall have a minimum net clear opening of 5.7 square feet (0.53 m2) or 5 square feet (0.46 m2) where located at grade.
2.2. The minimum net clear opening height shall be 24 inches (610 mm) and net clear opening width shall be 20 inches (508 mm).
2.3. The bottom of the clear opening shall not be greater than 44 inches (1118 mm) above the floor.
2.4. The operation of the window shall comply with the operational constraints of the VCC.
3. In all buildings of Group E occupancy, up to and including the 12th grade, buildings of Group I occupancy, rooming houses and child care centers, ladders of any type are prohibited on fire escapes used as a required means of egress.
I. Add IEBC Change Section 304 to Glass
replacement and replacement windows.
J. Add Sections Change Section 304.1 and add
Sections 304.2 through 304.3, including subsections, 304.3.1
to the IEBC to read:
304.1 Conformance Replacement glass. In
accordance with § 36-99.2 of the Code of Virginia, any replacement glass
installed in buildings constructed prior to the first edition of the USBC shall
meet the quality and installation standards for glass installed in new
buildings as are in effect at the time of installation. In addition, as a
requirement of this code, the installation or replacement of glass in
buildings constructed under any edition of the USBC shall be as required for
new installations shall comply with Chapter 24 of the VCC.
304.2 Replacement window opening devices. In Group R-2 or R-3 buildings containing dwelling units, window opening control devices complying with ASTM F 2090 shall be installed where an existing window is replaced and where all of the following apply to the replacement window:
1. The window is operable;
2. The window replacement includes replacement of the sash and the frame;
3. The top of the sill of the window opening is at a height less than 36 inches (915 mm) above the finished floor;
4. The window will permit openings that will allow passage of a 4-inch diameter (102 mm) sphere when the window is in its largest opened position; and
5. The vertical distance from the top of the sill of the window opening to the finished grade or other surface below, on the exterior of the building, is greater than 72 inches (1829 mm).
The window opening control device, after operation to release the control device allowing the window to fully open, shall not reduce the minimum net clear opening area of the window unit to less than the area required by Section 1029.2 of the VCC.
Exceptions:
1. Operable windows where the top of the sill of the window opening is located more than 75 feet (22 860 mm) above the finished grade or other surface below, on the exterior of the room, space or building, and that are provided with window fall prevention devices that comply with ASTM F 2006.
2. Operable windows with openings that are provided with window fall prevention devices that comply with ASTM F 2090.
304.3 Replacement window emergency escape and rescue openings.
Where windows are required by the VCC or International Residential Code
to provide emergency escape and rescue openings in Groups R-2 and R-3
occupancies and one-family and two-family dwellings and townhouses regulated
by the International Residential Code, replacement windows shall be exempt
from the requirements of Sections 1030.2, 1030.3, and 1030.5 1030.4
of the VCC or Sections R310.2.1, R310.2.2, and R310.2.3 of the International
Residential Code, provided the replacement window meets the following
conditions:
1. The replacement window is the manufacturer's largest standard size window that will fit within the existing frame or existing rough opening. The replacement window shall be permitted to be of the same operating style as the existing window or a style that provides for an equal or greater window opening area than the existing window.
2. The replacement of the window is not part of a change of occupancy.
304.3.1 Operational constraints. Where bars, grilles, grates, or similar devices are installed over emergency escape and rescue openings as permitted by Section 1030.4 of the VCC, smoke alarms shall also be provided in accordance with Section 907.2.11 of the VCC.
K. Add IEBC Change Section 305 Seismic
force-resisting systems.
L. Add Change Sections 305.1 and 305.2,
including subsections, to the IEBC to read:
305.1 General. Where this code requires consideration of the seismic
force-resisting system of an existing building subject to repair, alteration,
change of occupancy, addition or relocation moving of existing
buildings, the seismic evaluation and design shall be based on Section 305.2 regardless
of which compliance method is used.
305.2 Seismic evaluation and design procedures. The seismic evaluation and design shall be based on the procedures specified in the VCC or ASCE 41. The procedures contained in Appendix A of this code shall be permitted to be used as specified in Section 305.2.2.
305.2.1 Compliance with VCC-level seismic forces. Where compliance with the seismic design provisions of the VCC is required, the criteria shall be in accordance with one of the following:
1. 100% of the values in the VCC. Where the existing seismic force-resisting system is a type that can be designated as "Ordinary," values of R, Ω0, and Cd used for analysis in accordance with Chapter 16 of the VCC shall be those specified for structural systems classified as "Ordinary" in accordance with Table 12.2-1 of ASCE 7, unless it can be demonstrated that the structural system will provide performance equivalent to that of a "Detailed," "Intermediate" or "Special" system.
2. ASCE 41, using a Tier 3 procedure and the two level performance objective in Table 305.2.1 for the applicable risk category.
Table 305.2.1 |
||
Risk Category |
Structural Performance Level for Use with BSE-1E Earthquake Hazard Level |
Structural Performance Level for Use with BSE-2N Earthquake Hazard Level |
I |
Life Safety (S-3) |
Collapse Prevention (S-5) |
II |
Life Safety (S-3) |
Collapse Prevention (S-5) |
III |
Damage Control (S-2) |
Limited Safety (S-4) |
IV |
Immediate Occupancy (S-1) |
Life Safety (S-3) |
305.2.2 Compliance with reduced VCC-level seismic forces. Where seismic evaluation and design is permitted to meet reduced VCC seismic force levels, the criteria used shall be in accordance with one of the following:
1. The VCC using 75% of the prescribed forces. Values of R, Ω0 and Cd used for analysis shall be as specified in Section 305.2.1 of this code.
2. Structures or portions of structures that comply with the requirements of the applicable chapter in Appendix A as specified in Items 2.1 through 2.5 and subject to the limitations of the respective Appendix A chapters shall be deemed to comply with this section.
2.1. The seismic evaluation and design of unreinforced masonry bearing wall buildings in Risk Category I or II are permitted to be based on the procedures specified in Appendix Chapter A1.
2.2. Seismic evaluation and design of the wall anchorage system in reinforced concrete and reinforced masonry wall buildings with flexible diaphragms in Risk Category I or II are permitted to be based on the procedures specified in Chapter A2.
2.3. Seismic evaluation and design of cripple walls and sill plate anchorage in residential buildings of light-frame wood construction in Risk Category I or II are permitted to be based on the procedures specified in Chapter A3.
2.4. Seismic evaluation and design of soft, weak, or open-front wall conditions in multiunit residential buildings of wood construction in Risk Category I or II are permitted to be based on the procedures specified in Chapter A4.
2.5. Seismic evaluation and design of concrete buildings assigned to Risk Category I, II, or III are permitted to be based on the procedures specified in Chapter A5.
3. ASCE 41, using the performance objective in Table 305.2.2 for the applicable risk category.
Table 305.2.2 Performance Objectives for Use in ASCE 41 for Compliance with Reduced VCC-Level Seismic Forces |
|
Risk Category (Based on VCC Table 1604.5) |
Structural Performance Level for Use with BSE-1E Earthquake Hazard Level |
I |
Life Safety (S-3) |
II |
Life Safety (S-3) |
III |
Damage Control (S-2a) |
IV |
Immediate Occupancy (S-1) |
a. Tier 1 evaluation at the Damage Control performance level shall use the Tier 1 Life Safety checklists and Tier 1 Quick Check provision midway between those specified for Life Safety and Immediate Occupancy performance |
M. Delete Sections 305.3 through 305.9, including subsections, of the IEBC.
N. Add IEBC Section 306 Group B teaching and
research Higher education laboratories.
N. O. Add Section 306.1, including subsections,
to the IEBC to read:
306.1 Change of occupancy in existing Group B teaching and
research higher education laboratories. Where the use of new or different
hazardous materials or a change in the amount of hazardous materials in
existing Group B testing and research laboratories in educational
occupancies above the 12th grade higher education laboratories would
constitute a change of occupancy, this section shall be permitted to be used as
an acceptable alternative to compliance with change of occupancy requirements
to permit the increased amounts of hazardous materials stipulated without the
laboratories being classified as Group H. In addition, as set out in Section
5001.7 of such laboratories shall comply with the applicable operational
and maintenance requirements in Chapter 38 of the SFPC, approval.
Approval under this section is contingent upon operational requirements in
the SFPC being complied with and maintained.
306.1.1 Hazardous materials in existing Group B teaching
and research higher education laboratories. The percentage of
maximum allowable quantities of hazardous materials per control area and the number
of control areas permitted at each floor level within an existing building
shall be permitted to comply with Table 302.6.1(1) in buildings equipped
throughout with an automatic sprinkler system in accordance with Section
903.3.1.1 of the VCC or shall be permitted to comply with Table 302.6.1(2) in
buildings not equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1 of the VCC.
Table 306.1.1(1) Design and Number of Control Areas in Existing Buildings
Equipped throughout with an Automatic Sprinkler System in Accordance with
Section 903.3.1.1 of the VCC with |
||||
Floor Level |
Percentage of the Maximum Allowable Quantity per Control Areaa |
Number of Control Areas per Floor |
Fire-Resistance Rating for Fire Barriers and Horizontal Assemblies in Hoursb |
|
Above Grade Plane |
Higher than 20 10-20 7-9 4-6 3 2 1 |
5 10 25 50 75 100 100 |
1 1 2 2 2 3 4 |
2 2 2 2 1 1 1 |
Below Grade Plane |
1 2 Lower than 2 |
75 50 Not Allowed |
3 2 Not Allowed |
1 1 Not Allowed |
a. Percentage shall be of the maximum allowable quantity per control area shown in Tables 307.1(1) and 307.1(2) of the VCC, with all increases allowed in the notes to those tables. b. Separation shall include fire barriers and horizontal assemblies as necessary to provide separation from other portions of the building. |
Table 306.1.1(2) Design and Number of Control Areas in Existing Buildings Not
Equipped throughout with an Automatic Sprinkler System in Accordance with
Section 903.3.1.1 of the VCC with |
||||
Floor Level |
Percentage of the Maximum Allowable Quantity per Control Areaa |
Number of Control Areas per Floor |
Fire-Resistance Rating for Fire Barriers and Horizontal Assemblies in Hoursb |
|
Above Grade Plane |
Higher than 9 7-9 4-6 3 2 1 |
5 10 25 75 100 100 |
1 2 2 2 3 4 |
2 2 2 1 1 1 |
Below Grade Plane |
1 2 Lower than 2 |
75 50 Not Allowed |
3 2 Not Allowed |
1 1 Not Allowed |
a. Percentage shall be of the maximum allowable quantity per control area shown in Tables 307.1(1) and 307.1(2) of the VCC, with all increases allowed in the notes to those tables. b. Separation shall include fire barriers and horizontal assemblies as necessary to provide separation from other portions of the building. |
306.1.2 Automatic fire alarm and detection systems. An
automatic A fire alarm system shall be provided throughout the
building in accordance with Section 907 of the VCC. An automatic fire detection
system shall be provided in the control area in accordance with Section 907 of
the VCC where pyrophics or Class 4 oxidizers are used and the building
is not equipped throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1 of the VCC.
306.1.3 System supervision and monitoring. Automatic fire alarm and detection systems shall be electronically supervised and monitored by an approved supervising station or, where approved, shall initiate an audible and visual signal at a constantly attended onsite location.
306.1.4 Restricted materials in storage and use. Where approved by the building official, the storage and use of the following hazardous materials prohibited by VCC Table 307.1(1) in buildings not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 shall be allowed within a control area at 25% of Table 307.1(1) limits for a building equipped throughout with an automatic sprinkler system:
1. Pyrophorics.
2. Class 4 oxidizers.
No additional quantity increases shall be allowed. All such materials shall be stored and used in accordance with Sections 3805.2.1 and 3805.2.2 of the SFPC.
O. P. Add IEBC Section 307 Reroofing and roof
repair.
P. Q. Add Sections 307.1 through 307.7,
including subsections, to the IEBC to read:
307.1 Reroofing. Materials and methods of application used for recovering or replacing an existing roof covering shall comply with this section and the applicable requirements of Chapter 15 of the VCC.
Exceptions:
1. Roof replacement of roof recover of existing low-slope roof
coverings shall not be required to meet the minimum design slope requirement of
one-quarter unit vertical in 12 units horizontal (2% (2.0% slope)
in Section 1507 of the VCC for roofs that provide positive roof drainage.
2. Recovering or replacing an existing roof covering shall not
be required to meet the requirement of secondary (emergency overflow) drains or
scuppers in Section 1503.4 1502 of the VCC for roofs that provide
for positive roof drainage. For the purposes of this exception, existing
secondary drainage or scupper systems required in accordance with the VCC shall
not be removed unless they are replaced by secondary drains or scuppers
designed and installed in accordance with Section 1503.4 1502 of
the VCC.
307.2 Structural and construction loads. Structural roof components shall be capable of supporting the roof covering system and the material and equipment loads that will be encountered during installation of the system.
Exceptions:
1. Structural elements where the additional dead load from the roofing or equipment does not increase the force in the element by more than 5.0%.
2. Buildings constructed in accordance with the International Residential Code or the conventional light frame construction methods of the International Building Code and where the dead load from the roofing or equipment is not increased by more than 5.0%.
3. Addition of a second layer of roof covering weighing three pounds per square foot (0.1437 kN/m2) or less over an existing, single layer of roof covering.
307.3 Roof replacement. Roof replacement shall include the removal of all existing layers of roof coverings down to the roof deck.
Exception: Where the existing roof assembly includes an ice barrier membrane that is adhered to the roof deck, the existing ice barrier membrane shall be permitted to remain in place and covered with an additional layer of ice barrier membrane in accordance with Section 1507 of the VCC.
307.3.1 Roof recover limitation. A roof recover shall not be permitted where any of the following conditions occur:
1. Where the existing roof or roof covering is water soaked or has deteriorated to the point that the existing roof or roof covering is not adequate as a base for additional roofing.
2. Where the existing roof covering is slate, clay, cement, or asbestos-cement tile.
3. Where the existing roof has two or more applications of any type of roof covering.
307.3.1 307.3.2 Roof recover. The installation of
a new roof covering over an existing roof covering shall be permitted where any
of the following conditions occur:
1. Complete and separate roofing systems, such as standing-seam metal roof systems, that are designed to transmit the roof loads directly to the building's structural system and that do not rely on existing roofs and roof coverings for support, shall not require the removal of exiting roof coverings.
2. Metal panel, metal shingle and concrete and clay tile roof coverings shall be permitted to be installed over existing wood shake roofs when applied in accordance with Section 307.4.
3. The application of a new protective coating over an existing spray polyurethane foam roofing system shall be permitted without tear-off of existing roof coverings.
4. Where the new roof covering is installed in accordance with the roof covering manufacturer's approved instructions.
Exceptions: A roof recover shall not be permitted where any
of the following conditions occur:
1. Where the existing roof or roof covering is water soaked
or has deteriorated to the point that the existing roof or roof covering is not
adequate as a base for additional roofing.
2. Where the existing roof covering is slate, clay, cement,
or asbestos-cement tile.
3. Where the existing roof has two or more applications of
any type of roof covering.
307.4 Roof recovering. Where the application of a new roof covering over wood shingle or shake roofs creates a combustible concealed space, the entire existing surface shall be covered with gypsum board, mineral fiber, glass fiber or other approved materials securely fastened in place.
307.5 Reinstallation of materials. Existing slate, clay, or cement tile shall be permitted for reinstallation, except that damaged, cracked or broken slate or tile shall not be reinstalled. Existing vent flashing, metal edgings, drain outlets, collars, and metal counter-flashings shall not be reinstalled where rusted, damaged, or deteriorated. Aggregate surfacing materials shall not be reinstalled.
307.6 Flashings. Flashings shall be reconstructed in accordance with approved manufacturer's installation instructions. Metal flashing to which bituminous materials are to be adhered shall be primed prior to installation.
307.7 Roof repair. Roof repairs shall comply with this section. Work on nondamaged components that is necessary for the required repair of damaged components shall be considered part of the roof repair and shall not be subject to the requirements of other parts of this code.
Exception: Routine maintenance required by this section, ordinary repairs exempt from permit in accordance with Section 108.2 of the VCC, and abatement of wear due to normal service conditions shall not be subject to the requirements for roof repairs in this section.
307.7.1 Building materials and systems. Building materials and
systems shall comply with the requirements of Sections Section
307.7.1.1 and 307.7.1.2.
307.7.1.1 Existing materials. Materials already in use in a building
in compliance with requirements or approvals in effect at the time of their
erection or installation shall be permitted to remain in use unless determined
by the building official to be unsafe.
307.7.1.2 307.7.1.1 New and replacement
materials. Except as otherwise required or permitted by this code, materials
permitted by the applicable code for new construction shall be used. Like
materials shall be permitted for repairs, provided no hazard to life, health or
property is created. Hazardous materials shall not be used where the code for
new construction would not permit their use in buildings of similar occupancy,
purpose and location.
13VAC5-63-432.5. Chapter 4 Accessibility.
A. Change IEBC Section 401 to General.
B. A. Change Section 401.1 of the IEBC to read:
401.1 Scope. The applicable provisions of this chapter shall apply to all construction and rehabilitation.
C. B. Delete Sections 401.1.1 401.2
through 401.3 of the IEBC.
D. C. Change IEBC Section 402 of to
Change of Occupancy.
E. D. Change Sections Section
402.1 through and add Sections 402.2 and 402.3 of to
the IEBC to read:
402.1 Change of occupancy. Existing buildings or structures that undergo a change of occupancy shall comply with this section.
Exception: Type B dwelling or sleeping units required by
Section 1107 of the VCC are not required to be provided in existing buildings
and facilities undergoing a change of occupancy in conjunction with Level 2
alterations where the work area intended portion of a building or
structure involving walls that are added, relocated, or removed is 50% or
less of the aggregate area of the building area.
402.2 Partial change in occupancy. Where a portion of the building is changed to a new occupancy classification, additional accessible features are not required due to the change of occupancy.
402.3 Complete change of occupancy. Where an entire building undergoes a change of occupancy classification, it shall have all of the following accessible features:
1. At least one accessible building entrance.
2. At least one accessible route from an accessible building entrance to primary function areas.
3. Signage complying with Section 1111 of the VCC.
4. Accessible parking, where parking is being provided.
5. At least one accessible passenger loading zone, when loading zones are provided.
6. At least one accessible route connecting accessible parking and accessible passenger loading zones to an accessible entrance.
Where it is technically infeasible to comply with the new construction standards for any of these requirements of a change of occupancy, Items 1 through 6 shall conform to the requirements to the maximum extent technically feasible.
Exception: The accessible features listed in Items 1 through 6 are not required for an accessible route to Type B units.
F. Delete Sections 402.3.1, 402.4 and 402.5 of the IEBC.
G. E. Change IEBC Section 403 to Additions.
H. F. Change Sections Section
403.1 through 403.3 of the IEBC to read:
403.1 Additions. Accessibility provisions for new construction
shall apply to additions. An addition that affects the accessibility to, or
contains an area of, a primary function shall comply with the requirements in
Section 410.7 404.3, as applicable.
G. Add Sections 403.2 through 403.4 to the IEBC to read:
403.2 Accessible dwelling units and sleeping units. Where Group I-1, I-2, I-3, R-1, R-2, or R-4 dwelling or sleeping units are being added, the requirements of Section 1107 of the VCC for accessible units apply only to the quantity of spaces being added.
403.3 Type A dwelling or sleeping units. Where more than 20 Group R-2 dwelling or sleeping units are being added, the requirements of Section 1107 of the VCC for Type A units and Chapter 9 of the VCC for visible alarms apply only to the quantity of the spaces being added.
I. Delete Section 403.3.1.
J. Change Section 403.4 of the IEBC to read:
403.4 Type B dwelling or sleeping units. Where four or more Group I-1, I-2, R-1, R-2, R-3, or R-4 dwelling or sleeping units are being added, the requirements of Section 1107 of the VCC for Type B units and Chapter 9 of the VCC for visible alarms apply only to the quantity of spaces being added.
K. Delete Sections 403.4.1 through 403.11, including
subsections, of the IEBC.
L. H. Change IEBC Section 404 to Alterations.
M. I. Change Sections Section
404.1 through 404.4.15, including subsections, of the IEBC to read:
404.1 General. An alteration of an existing facility shall not impose a requirement for greater accessibility than that which would be required for new construction. Alterations shall not reduce or have the effect of reducing accessibility of a facility or portion of a facility.
J. Add Sections 404.2 through 404.4.15, including subsections, to the IEBC to read:
404.2 Alterations. A facility that is altered shall comply with the applicable provisions in this section and Chapter 11 of the VCC, except as modified by Sections 404.3 and 404.4, unless technically infeasible. Where compliance with this section is technically infeasible, the alteration shall provide access to the maximum extent technically feasible.
Exceptions:
1. The altered element or space is not required to be on an accessible route, unless required by Section 404.3.
2. Accessible means of egress required by Chapter 10 of the VCC are not required to be provided in existing facilities.
3. The alteration to Type A individually owned dwelling units within a Group R-2 occupancy shall be permitted to meet the provision for a Type B dwelling unit.
4. Type B dwelling or sleeping units required by Section
1107 of the VCC are not required to be provided in existing buildings and
facilities undergoing a change of occupancy in conjunction with alterations
where the work area is 50% or less of the aggregate area of the building.
404.3 Alterations affecting an area containing a primary function. Where an alteration affects the accessibility to, or contains an area of primary function, the route to the primary function area shall be accessible. The accessible route to the primary function area shall include toilet facilities and drinking fountains that shall also be accessible to and useable by individuals with disabilities, serving the area of primary function.
Exceptions:
1. The costs of providing the accessible route are not required to exceed 20% of the costs of the alterations affecting the area of primary function.
2. This provision does not apply to alterations limited solely to windows, hardware, operating controls, electrical outlets and signs.
3. This provision does not apply to alterations limited solely to mechanical systems, electrical systems, installation or alteration of fire protection systems and abatement of hazardous materials.
4. This provision does not apply to alterations undertaken for the primary purpose of increasing the accessibility of a facility.
5. This provision does not apply to altered areas limited to Type B dwelling and sleeping units.
404.4 Scoping for alterations. The provisions of Sections 404.4.1 through 404.4.14 shall apply to alterations to existing buildings and facilities.
404.4.1 Entrances. Where an alteration includes alterations to an entrance, and the facility has an accessible entrance on an accessible route, the altered entrance is not required to be accessible unless required by Section 404.3. Signs complying with Section 1111 of the VCC shall be provided.
Exception: Where an alteration includes alterations to an
entrance, and the facility has an accessible entrance, the altered entrance is
not required to be accessible, unless required by Section 410.7 404.3.
Signs complying with Section 1111 of the VCC shall be provided.
404.4.2 Elevators. Altered elements of existing elevators shall comply with ASME A17.1/CSA B44 and ICC A117.1. Such elements shall also be altered in elevators programmed to respond to the same hall call control as the altered elevator.
404.4.3 Platform lifts. Platform (wheelchair) lifts complying with ICC A117.1 and installed in accordance with ASME A18.1 shall be permitted as a component of an accessible route.
404.4.4 Stairways and escalators. In alterations, change of
occupancy or additions where Where an escalator or stairway is added
where none existed previously and major structural modifications are necessary
for installation, an accessible route shall be provided between the levels
served by the escalator or stairways in accordance with Section 1104.4 of the
VCC.
404.4.5 Ramps. Where steeper slopes than allowed by Section 1012.2 of the VCC are necessitated by space limitations, the slope of ramps in or providing access to existing facilities shall comply with Table 404.4.5.
Table 404.4.5 Ramps |
|
Slope |
Maximum Rise |
Steeper than 1:10 but not steeper than 1:8 |
3 inches |
Steeper than 1:12 but not steeper than 1:10 |
6 inches |
For SI: 1 inch = 25.4 mm |
404.4.6 Accessible dwelling or sleeping units. Where Group I-1, I-2, I-3, R-1, R-2, or R-4 dwelling or sleeping units are being altered, the requirements of Section 1107 of the VCC for Accessible units apply only to the quantity of the spaces being altered.
404.4.7 Type A dwelling or sleeping units. Where more than 20 Group R-2 dwelling or sleeping units are being altered, the requirements of Section 1107 of the VCC for Type A units and Chapter 9 of the VCC for visible alarms apply only to the quantity of the spaces being altered.
404.4.8 Type B dwelling or sleeping units. Where four or more
Group I-1, I-2, R-1, R-2, R-3, or R-4 dwelling or sleeping units are being
altered and where the work area is greater than 50% of the aggregate area of
the building, the requirements of Section 1107 of the VCC for Type B units
and Chapter 9 of the VCC for visible alarms apply only to the quantity of the
spaces being altered.
Exceptions: Group Groups I-1, I-2, R-2, R-3, and
R-4 dwelling or sleeping units where the first certificate of occupancy was
issued before March 15, 1991, are not required to provide Type B dwelling or
sleeping units.
404.4.9 Jury boxes and witness stands. In alterations, accessible wheelchair spaces are not required to be located within the defined area of raised jury boxes or witness stands and shall be permitted to be located outside these spaces where ramp or lift access poses a hazard by restricting or projecting into a required means of egress.
404.4.10 Toilet and bathing rooms. Where it is technically infeasible to alter existing toilet and bathing rooms to be accessible, an accessible single-user or family or assisted-use toilet or bathing room constructed in accordance with Section 1109.2.1 of the VCC is permitted. The single-user or family or assisted-use toilet or bathing room shall be located on the same floor and in the same area as the existing toilet or bathing rooms. At the inaccessible toilet and bathing rooms, provide directional signs indicating the location of the nearest single-user or family or assisted-use toilet room or bathing room. These directional signs shall include the International Symbol of Accessibility and sign characters shall meet the visual character requirements in accordance with ICC A117.1.
404.4.11 Dressing, fitting and locker rooms. Where it is technically infeasible to provide accessible dressing, fitting or locker rooms at the same location as similar types of rooms, one accessible room on the same level shall be provided. Where separate-sex facilities are provided, accessible rooms for each sex shall be provided. Separate sex facilities are not required where only unisex rooms are provided.
404.4.12 Fuel dispensers. Operable parts of replacement fuel dispensers shall be permitted to be 54 inches (1370 mm) maximum, measuring from the surface of the vehicular way where fuel dispensers are installed on existing curbs.
404.4.13 Thresholds. The maximum height of thresholds at doorways shall be 3/4 inch (19.1 mm). Such thresholds shall have beveled edges on each side.
404.4.14 Amusement rides. Where the structural or operational characteristics of an amusement ride are altered to the extent that the amusement ride's performance differs from that specified by the manufacturer or the original design, the amusement ride shall comply with requirements for new construction in Section 1110.4.8 of the VCC.
404.4.15 Dining areas. An accessible route to raised or sunken dining areas or to outdoor seating areas is not required provided that the same services and décor are provided in an accessible space usable by any occupant and not restricted to use by people with a disability.
N. Delete Sections 404.2.1, 404.2.2, 404.2.3, 404.3.1 and
404.5 of the IEBC.
O. K. Change Section 405 to Historic Buildings.
P. L. Change Section 405.1, including
subsections, to read:
405.1 General. These provisions shall apply to facilities designated as historic buildings or structures that undergo alterations or a change of occupancy, unless technically infeasible. Where compliance with the requirements for accessible routes, entrances or toilet rooms would threaten or destroy the historic significance of the facility, the alternative requirements of Sections 405.1.1 through 405.1.4 for that element shall be permitted.
Exception: Type B dwelling or sleeping units required by Section 1107 of the VCC are not required to be provided in historical buildings.
M. Add Sections 405.1.1 through 405.1.4 to the IEBC to read:
405.1.1 Site arrival points. At least one accessible route from a site arrival point to an accessible entrance shall be provided.
405.1.2 Multilevel buildings and facilities. An accessible route from an accessible entrance to public spaces on the level of the accessible entrance shall be provided.
405.1.3 Entrances. At least one main entrance shall be accessible.
Exceptions:
1. If a main entrance cannot be made accessible, an accessible nonpublic entrance that is unlocked while the building is occupied shall be provided; or
2. If a main entrance cannot be made accessible, a locked accessible entrance with a notification system or remote monitoring shall be provided.
Signs complying with Section 1111 of the VCC shall be provided at the primary entrance and the accessible entrance.
405.1.4 Toilet and bathing facilities. Where toilet rooms are provided, at least one accessible single-user or family or assisted-use toilet or bathing room complying with Section 1109.2.1 of the VCC shall be provided.
Q. N. Delete Sections 405.2 through 405.5
405.2.5, including subsections, of the IEBC.
R. O. Delete Sections 406, 407, and 408,
409 and 410 of the IEBC in their entirety.
13VAC5-63-433. Chapter 5 Repairs.
A. Change Section 501.1 and 501.2 of the IEBC to read:
501.1 Scope. Repairs, including the patching or restoration or
replacement of damaged materials, elements, equipment or fixtures for the purpose
of maintaining such components in good or sound condition with respect to
existing loads or performance requirements, shall comply with the
requirements of this chapter. Repairs to historic buildings need only comply
with Chapter 9. Portions of the existing building or structure not being
repaired shall not be required to comply with the requirements of this code
applicable to newly constructed buildings or structures. Work on nondamaged
components that is necessary for the required repair of damaged components
shall be considered part of the repair and shall not be subject to the
provisions of Chapter 6, 7 or 8. Routine maintenance required by Section
302, ordinary repairs exempt from permit in accordance with Section 108.2 of
the VCC, and abatement of wear due to normal service conditions shall not be
subject to the requirements for repairs in this section.
Exception: Repairs complying with the requirements of the
building code under which the building or structure or the affected portions
thereof was built, or as previously approved by the building official, shall be
considered in compliance with the provisions of this code, unless the building
or structure or the affected portions thereof is undergoing a substantial
structural alteration as described in Section 604.7.1. New structural members
added as part of the alteration or repairs shall comply with the VCC. Repairs
of existing buildings in flood hazard areas shall comply with Section 503.
501.2 Conformance. The work shall not make the building less conforming than it was before the repair was undertaken. Repairs shall be done in a manner that maintains the following:
1. Level of fire protection that is existing.
2. Level of protection that is existing for the means of egress.
3. Level of accessibility that is existing.
B. Delete Section 501.1.1 of the IEBC.
C. Change Section 502 to Structural.
D. Change Sections 502.1 and 502.2, including subsections
through 502.4 and add Section 502.4.1, of to the IEBC to
read:
502.1 General. Structural repairs shall be in compliance with this section and Section 501.2. Regardless of the scope of repair, new structural members and connections used for repair or rehabilitation shall comply with the detailing provisions of the VCC for new buildings of similar structure, purpose and location.
502.2 Repairs to damaged buildings. Repairs to damaged
buildings shall comply with this section.
502.2.1 502.2 Less than substantial structural
damage. For damage less than substantial structural damage, repairs shall be
allowed that restore the building to its predamage state. New structural
members and connection used for this repair shall comply with the detailing
provisions of the VCC for new buildings of similar structure, purpose, and
location.
502.2.2 502.3 Substantial structural damage to
vertical elements of the lateral force-resisting system. A building that has
sustained substantial structural damage to the vertical elements of its lateral
force-resisting system shall be evaluated in accordance with Section 502.2.2.1
502.3.1 and either repaired in accordance with Section 502.2.2. 502.3.2
or repaired and rehabilitated in accordance with Section 502.2.2.3 502.3.3,
depending on the results of the evaluation.
Exceptions:
1. Buildings assigned to Seismic Design Category A, B, or C whose substantial structural damage was not caused by earthquake need not be evaluated or rehabilitated for load combinations that include earthquake effects.
2. One-family and two-family dwellings need not be evaluated or rehabilitated for load combinations that include earthquake effects.
502.2.2.1 502.3.1 Evaluation. The building shall
be evaluated by a registered design professional, and the evaluation findings
shall be submitted to the building official. The evaluation shall establish
whether the damaged building if repaired to its predamage state, would comply
with the provisions of the VCC for load combinations that include wind or
earthquake effects, except that the seismic forces shall be the reduced
VCC-level seismic forces.
Wind loads for this evaluation shall be those prescribed in Section 1609 of the VCC. Earthquake loads for this evaluation, if required, shall be permitted to be 75% of those prescribed in Section 1613 of the VCC. Alternatively, compliance with ASCE 41, using the performance objective in Table 305.2.2 for the applicable risk category, shall be deemed to meet the earthquake evaluation requirement.
502.2.2.2 502.3.2 Extent of repair for compliant
buildings. If the evaluation establishes that the building in its predamage condition
complies with the provisions of Section 502.2.2.1 502.3.1, then
repairs shall be permitted that restore the building to its predamage state.
502.2.2.3 502.3.3 Extent of repair for
noncompliant buildings. If the evaluation does not establish that the building
in its predamage condition complies with the provisions of Section 502.2.2.1
502.3.1, then the building shall be rehabilitated to comply with the
provisions of this section. The wind loads for the repair shall be as required
by the building code in effect at the time of original construction, unless the
damage was caused by wind, in which case the wind loads shall be in accordance
with the VCC. The earthquake loads for this rehabilitation design shall be
those required by the building code in effect at the time of original
construction, but not less than the reduced VCC-level seismic forces. New
structural members and connections required by this rehabilitation design shall
comply with the detailing provisions of the VCC for new buildings of similar
structure, purpose and location. Alternatively, compliance with ASCE 41, using
the performance objective in Table 305.2.2 for the applicable risk category,
shall be deemed to meet the earthquake rehabilitation requirement.
502.2.3 502.4 Substantial structural damage to
gravity load-carrying components. Gravity load-carrying components that have
sustained substantial structural damage shall be rehabilitated to comply with
the applicable provisions for dead and live loads in the VCC. Snow loads shall
be considered if the substantial structural damage was caused by or related to
snow load effects. Existing gravity load carrying structural elements shall be
permitted to be designed for live loads approved prior to the damage. If the
approved live load is less than that required by Section 1607 of the VCC, the
area designed for the nonconforming live load shall be posted with placards of
approved design indicating the approved live load. Nondamaged gravity
load-carrying components that receive dead, live, or snow loads from
rehabilitated components shall also be rehabilitated if required to comply with
the design loads of the rehabilitation design, or shown to have the capacity to
carry the design loads of the rehabilitation design. New structural members and
connections required by this rehabilitation design shall comply with the
detailing provisions of the VCC for new buildings of similar structure purpose
and location.
502.2.3.1 502.4.1 Lateral force-resisting
elements. Regardless of the level of damage to gravity elements of the lateral
force-resisting system, if substantial structural damage to gravity
load-carrying components was caused primarily by wind or earthquake effects,
then the building shall be evaluated in accordance with Section 502.2.2.1
502.3.1 and, if noncompliant, rehabilitated in accordance with Section 502.2.2.3
502.3.3.
Exceptions:
1. Buildings assigned to Seismic Design Category A, B, or C whose substantial structural damage was not caused by earthquake need not be evaluated or rehabilitated for load combinations that include earthquake effects.
2. One-family and two-family dwellings need not be evaluated or rehabilitated for load combinations that include earthquake effects.
E. Delete Section 502.3 Sections 502.5 through 502.8
of the IEBC.
F. Change Section 503 to Flood Hazard Areas.
G. Change Section 503.1 of the IEBC to read:
503.1 Flood hazard areas. For buildings and structures, in flood hazard areas established in Section 1612.3 of the VCC, or Section R322 of the International Residential Code, as applicable, any repair that constitutes substantial improvement or repair of substantial damage of the existing building or structure shall comply with the flood design requirements for new construction and all aspects of the existing building or structure shall be brought into compliance with the requirements for new construction for flood design.
For buildings and structures in flood hazard areas established in Section 1612.3 of the VCC, or Section R322 of the International Residential Code, as applicable, any repairs that do not constitute substantial improvement or repair of substantial damage of the existing building or structure are not required to comply with the flood design requirements for new construction.
H. Delete Section Sections 503.2 through
503.16.3, including subsections, of the IEBC.
I. Change Section 504 to Electrical.
J. Change Section 504.1, including subsections, and add section 504.1.5 of the IEBC to read:
504.1 Material. Existing electrical wiring and equipment undergoing repair shall be allowed to be repaired or replaced with like material.
504.1.1 Receptacles. Replacement of electrical receptacles shall comply with the applicable requirements of Section 406.4(D) of NFPA 70.
504.1.2 Plug fuses. Plug fuses of the Edison-base type shall be used for replacements only where there is no evidence of over fusing or tampering per applicable requirements of Section 240.51(B) of NFPA 70.
504.1.3 Nongrounding-type receptacles. For replacement of nongrounding-type receptacles with grounding-type receptacles and for branch circuits that do not have an equipment grounding conductor in the branch circuitry, the grounding conductor of a grounding-type receptacle outlet shall be permitted to be grounded to any accessible point on the grounding electrode system or to any accessible point on the grounding electrode conductor in accordance with Section 250.130(C) of NFPA 70.
504.1.4 Group I-2 receptacles. Non-"hospital grade" receptacles in patient bed locations of Group I-2 shall be replaced with "hospital grade" receptacles, as required by NFPA 99 and Article 517 of NFPA 70.
504.1.5 Grounding of appliances. Frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers and outlet or junction boxes that are part of the existing branch circuit for these appliances shall be permitted to be grounded to the grounded circuit conductor in accordance with Section 250.140 of NFPA 70.
K. Delete Section Sections 504.2 through
504.5 of the IEBC.
L. Change Section 505 to Mechanical.
M. Change Sections 505.1 and 505.2 of the IEBC to read:
505.1 General. Existing mechanical systems undergoing repair shall not make the building less conforming than it was before the repair was undertaken.
505.2 Mechanical draft systems for manually fired appliances and fireplaces. A mechanical draft system shall be permitted to be used with manually fired appliances and fireplaces where such a system complies with all of the following requirements:
1. The mechanical draft device shall be listed and installed in accordance with the manufacturer's installation instructions.
2. A device shall be installed that produces visible and audible warning upon failure of the mechanical draft device or loss of electrical power at any time that the mechanical draft device is turned on. This device shall be equipped with a battery backup if it receives power from the building wiring.
3. A smoke detector shall be installed in the room with the appliance or fireplace. This device shall be equipped with a battery backup if it receives power from the building wiring.
N. Delete Sections 505.3 and 505.4 of the IEBC.
O. Change Section 506 to Plumbing.
O. P. Change Sections 506.1 and 506.2 of the
IEBC to read:
506.1 Materials. Plumbing materials and supplies shall not be used for repairs that are prohibited in the International Plumbing Code.
506.2 Water closet replacement. The maximum water consumption flow rates and quantities for all replaced water closets shall be 1.6 gallons (6 L) per flushing cycle.
Exception: Blowout-design water closets 3.5 gallons (13 L) per flushing cycle.
P. Q. Delete Section 506.1.1 and Sections 506.3
through 506.4.4, including subsections, of the IEBC.
R. Delete Section 507 of the IEBC in its entirety.
Q. Delete Section 508 of the IEBC in its entirety.
R. Delete Section 509 of the IEBC in its entirety.
13VAC5-63-433.3. Chapter 6 Alterations.
A. Change Sections 601.1 through 601.5, including
subsections, and 601.2 of the IEBC to read:
601.1 General. Except as provided by Section 905.1 modified
in Chapter 9 or this chapter, alterations to any building or structure
shall comply with the requirements of the VCC for new construction. Alterations
shall be such that the existing building or structure is no less conforming to
the provisions of the VCC than the existing building or structure was prior to
the alteration. Portions of the building or structure not being altered
shall not be required to comply with the requirements of the VCC.
Exceptions:
1. Any stairway replacing an existing stairway shall not be required to comply with the requirements of Section 1011 of the VCC where the existing space and construction does not allow a reduction in pitch or slope.
2. Handrails otherwise required to comply with Section 1011.11 of the VCC shall not be required to comply with the requirements of Section 1014.6 of the VCC regarding full extension of the handrails where such extensions would be hazardous due to plan configuration.
3. Where the current level of safety or sanitation is proposed to be reduced, the portion altered shall conform to the requirements of the VCC.
4. Alterations complying with the requirements of the building
code under which the building or structure or the affected portions thereof was
built, or as previously approved by the building official, shall be considered
in compliance with the provisions of this code, unless the building or
structure or the affected portions thereof is undergoing a substantial
structural alteration as described in Section 604.7.1. New structural
members added as part of the alteration or repairs shall comply with the
VCC. Alterations of existing buildings in flood hazard areas shall comply with
Section 601.3.
601.2 Levels of alterations. Alterations to any building or structure shall be classified as the following:
B. Delete Section 601.1.1.
C. Add Sections 601.2.1 through 601.5, including subsections, to the IEBC to read:
601.2.1 Level 1. Level 1 alterations include the removal and replacement or the covering of existing materials, elements, equipment, or fixtures using new materials, elements, equipment, or fixtures that serve the same purpose, or the removal without replacement of materials, elements, equipment, or fixtures. Level 1 alterations shall comply with the applicable provisions Section 602.
601.2.2 Level 2. Level 2 alterations shall comply with the
applicable provisions of Sections 602 and 603 and shall include the
addition or elimination of any door or window, the reconfiguration or extension
of any system, or the installation of any additional equipment and shall apply
where the work area is less than 50% of the building area. Level 2 alterations
shall comply with the applicable provisions Sections 602 and 603.
601.2.3 Level 3. Level 3 alterations apply where the work
area exceeds 50% of the building area. Level 3 alterations shall comply with
the applicable provisions of Sections 602, 603 and 604.
601.2.3.1 Special provisions. A building separated
horizontally in compliance with VCC Section 510.2 shall be considered as
separate and distinct buildings for the purpose of determining building area
used for application of Section 601.2.3. the following:
1. The addition or elimination of any door or window.
2. The addition of elimination of any wall, floor, or ceiling assembly.
3. The reconfiguration or extension of any system.
4. The installation of any addition equipment.
601.3 Flood hazard areas. In flood hazard areas, alterations that constitute substantial improvement shall require that the building comply with Section 1612 of the VCC or Section R322 of the International Residential Code, as applicable.
601.4 Energy conservation. Level 1, 2, and 3 alterations to existing buildings or structures are permitted without requiring the entire building or structure to comply with the energy requirements of the International Energy Conservation Code or International Residential Code. The alterations shall conform to the energy requirements of the International Energy Conservation Code or International Residential Code as they relate to new construction only.
Exception: Except for window and door openings, like materials, assemblies or thicknesses shall be permitted for alterations involving the exterior building thermal envelope, provided no hazard to life, health or property is created. Hazardous materials shall not be used where the code for new construction would not permit their use in buildings of similar occupancy, purpose and location.
601.5 Accessibility. Accessibility shall be provided in accordance with applicable provisions of Section 404.
B. Change Section 602 to Level 1 Alterations.
C. D. Change Sections 602.1 through 602.3
and 602.2, including subsections, of the IEBC to read:
602.1 Scope. Level 1 alterations as described in Section
601.2.1 shall comply with the requirements of this section. Level 1
alterations to historic buildings shall comply with this chapter, except as
modified in Chapter 9.
602.2 Conformance. Alterations shall be done in a manner that maintains the following:
1. Level of fire protection that is existing.
2. Level of protection that is existing for the means of egress.
E. Add Sections 602.3 through 602.3.5 to the IEBC to read:
602.3 Building elements and materials. Building elements and
materials shall comply with the applicable provisions of Sections 302 and
602.3.1 through 602.3.5 602.3.3.
602.3.1 Interior finishes and trim. All newly installed interior finish and trim materials and wall, floor, and ceiling finishes shall comply with Chapter 8 of the VCC.
602.3.2 Interior floor finish. New interior floor finish,
including new carpeting used as an interior floor finish material, shall comply
with Section 804 of the VCC.
602.3.3 Interior trim. All newly installed interior trim
materials shall comply with Section 806 of the VCC.
602.3.4 602.3.2 Materials and methods. All new work
building elements and materials shall comply with the materials and
methods requirements in the VCC, International Energy Conservation Code,
International Mechanical Code, and International Plumbing Code, as applicable,
that specify material standards, detail of installation and connection, joints,
penetrations, and continuity of any element, component, or system in the
building.
602.3.5 602.3.3 International Fuel Gas Code. The
following sections of the International Fuel Gas Code shall constitute the fuel
gas materials and methods requirements for Level 1 alterations.
1. All of Chapter 3, entitled "General Regulations," except Sections 303.7 and 306.
2. All of Chapter 4, entitled "Gas Piping Installations," except Sections 401.8 and 402.3.2.1. Sections 401.8 and 402.3 shall apply when the work being performed increases the load on the system such that the existing pipe does not meet the size required by code. Existing systems that are modified shall not require resizing as long as the load on the system is not increased and the system length is not increased even if the altered system does not meet code minimums.
3. All of Chapter 5, entitled "Chimneys and Vents."
4. All of Chapter 6, entitled "Specific Appliances."
D. Change Section 603 to Level 2 Alterations.
E. F. Change Section 603.1 and 603.2, and
add Sections 603.2 603.3 through 603.10 603.7.6,
including subsections, of to the IEBC to read:
603.1 Scope. Level 2 alterations as described in Section 601.2.2 shall comply with the requirements of this section.
Exception: Buildings in which the alteration is exclusively the result of compliance with the accessibility requirements of Section 404.3 shall be permitted to comply with Section 602.
603.2 Level 1 alteration compliance. In addition to the
requirements of this section, all work alterations shall comply
with the applicable requirements of Section 602.
603.3 Compliance. All new construction elements, components, systems, and spaces shall comply with the requirements of the VCC.
Exceptions:
1. Windows may be added without requiring compliance with the light and ventilation requirements of the VCC.
2. Newly installed electrical equipment shall comply with
the requirements of Section 603.8.
3. The length of dead-end corridors in newly constructed
spaces shall only be required to comply with the provisions of Section 603.6.5.
2. Where an approved automatic sprinkler system is installed throughout the story, the required fire-resistance rating for any corridor located on the story shall be permitted to be reduced in accordance with the VCC. In order to be considered for a corridor rating reduction, such system shall provide coverage for the stairway landings serving the floor and the intermediate landings immediately below.
3. In other than Groups A and H occupancies, the maximum length of a newly constructed or extended dead-end corridor shall not exceed 50 feet (15240 mm) on floors equipped with an automatic sprinkler system installed in accordance with the VCC.
4. The minimum ceiling height of the newly created habitable and occupiable spaces and corridors shall be 7 feet (2134 mm).
5. Where provided in below-grade transportation stations, new escalators shall be permitted to have a clear width of less than 32 inches (815 mm).
603.4 Building elements and materials. The requirements of
Section 603.4 are limited to work areas in which Level 2 alterations are being
performed and shall apply beyond the work area where specified.
603.4.1 Vertical openings. Existing vertical openings shall
comply with the provisions of Sections 603.4.1.1, 603.4.1.2, and 603.4.1.3.
603.4.1.1 Existing vertical openings. Existing interior
vertical openings connecting two or more floors shall be enclosed with approved
assemblies having a fire-resistance rating of not less than one hour with
approved opening protectives.
Exceptions:
1. Where vertical opening enclosure is not required by the
VCC or the International Fire Code.
2. Interior vertical openings other than stairways may be
blocked at the floor and ceiling of the work area by installation of not less
than 2 inches (51 mm) of solid wood or equivalent construction.
3. The enclosure shall not be required where:
3.1. Connecting the main floor and mezzanines; or
3.2. All of the following conditions are met:
3.2.1. The communicating area has a low hazard occupancy or
has a moderate hazard occupancy that is protected throughout by an automatic
sprinkler system.
3.2.2. The lowest or next to the lowest level is a street
floor.
3.2.3. The entire area is open and unobstructed in a manner
such that it may be assumed that a fire in any part of the interconnected
spaces will be readily obvious to all of the occupants.
3.2.4. Exit capacity is sufficient to provide egress
simultaneously for all occupants of all levels by considering all areas to be a
single floor area for the determination of required exit capacity.
3.2.5. Each floor level, considered separately, has at
least one half of its individual required exit capacity provided by exits leading
directly out of that level without having to traverse another communicating
floor level or be exposed to the smoke or fire spreading from another
communicating floor level.
4. In Group A occupancies, a minimum 30-minute enclosure
shall be provided to protect all vertical openings not exceeding three stories.
5. In Group B occupancies, a minimum 30-minute enclosure
shall be provided to protect all vertical openings not exceeding three stories.
This enclosure, or the enclosure specified in Section 603.4.1.1, shall not be
required in the following locations:
5.1. Buildings not exceeding 3,000 square feet (279 m2)
per floor.
5.2. Buildings protected throughout by an approved
automatic fire sprinkler system.
6. In Group E occupancies, the enclosure shall not be
required for vertical openings not exceeding three stories when the building is
protected throughout by an approved automatic fire sprinkler system.
7. In Group F occupancies, the enclosure shall not be
required in the following locations:
7.1. Vertical openings not exceeding three stories.
7.2. Special purpose occupancies where necessary for
manufacturing operations and direct access is provided to at least one
protected stairway.
7.3. Buildings protected throughout by an approved
automatic sprinkler system.
8. In Group H occupancies, the enclosure shall not be
required for vertical openings not exceeding three stories where necessary for
manufacturing operations and every floor level has direct access to at least
two remote enclosed stairways or other approved exits.
9. In Group M occupancies, a minimum 30-minute enclosure
shall be provided to protect all vertical openings not exceeding three stories.
This enclosure, or the enclosure specified in Section 603.4.1.1, shall not be
required in the following locations:
9.1. Openings connecting only two floor levels.
9.2. Occupancies protected throughout by an approved
automatic sprinkler system.
10. In Group R-1 occupancies, the enclosure shall not be
required for vertical openings not exceeding three stories in the following
locations:
10.1. Buildings protected throughout by an approved
automatic sprinkler system.
10.2. Buildings with less than 25 dwelling units or
sleeping units where every sleeping room above the second floor is provided with
direct access to a fire escape or other approved second exit by means of an
approved exterior door or window having a sill height of not greater than 44
inches (1118 mm) and where:
10.2.1. Any exit access corridor exceeding 8 feet (2438 mm)
in length that serves two means of egress, one of which is an unprotected
vertical opening, shall have at least one of the means of egress separated from
the vertical opening by a one-hour fire barrier; and
10.2.2. The building is protected throughout by an automatic
fire alarm system, installed and supervised in accordance with the VCC.
11. In Group R-2 occupancies, a minimum 30-minute enclosure
shall be provided to protect all vertical openings not exceeding three stories.
This enclosure, or the enclosure specified in Section 603.4.1.1, shall not be
required in the following locations:
11.1. Vertical openings not exceeding two stories with not
more than four dwelling units per floor.
11.2. Buildings protected throughout by an approved
automatic sprinkler system.
11.3. Buildings with not more than four dwelling units per
floor where every sleeping room above the second floor is provided with direct
access to a fire escape or other approved second exit by means of an approved
exterior door or window having a sill height of not greater than 44 inches
(1118 mm) and the building is protected throughout by an automatic fire alarm
system complying with Section 603.5.4.
12. One-family and two-family dwellings.
13. Group S occupancies where connecting not more than two
floor levels or where connecting not more than three floor levels and the
structure is equipped throughout with an approved automatic sprinkler system.
14. Group S occupancies where vertical opening protection
is not required for open parking garages and ramps.
603.4.1.2 Supplemental shaft and floor opening enclosure
requirements. Where the work area on any floor exceeds 50% of that floor area,
the enclosure requirements of Section 603.4.1 shall apply to vertical openings
other than stairways throughout the floor.
Exception: Vertical openings located in tenant spaces that
are entirely outside the work area.
603.4.1.3 Supplemental stairway enclosure requirements. Where
the work area on any floor exceeds 50% of that floor area, stairways that are
part of the means of egress serving the work area shall, at a minimum, be
enclosed with smoke-tight construction on the highest work area floor and all
floors below.
Exception: Where stairway enclosure is not required by the
VCC or the International Fire Code.
603.4.2 Smoke compartments. In Group I-2 occupancies where
the work area is on a story used for sleeping rooms for more than 30 patients,
the story shall be divided into not less than two compartments by smoke barrier
walls in accordance with Section 407.5 of the VCC as required for new
construction.
603.4.3 Interior finish. The interior finish of walls and
ceilings in exits and corridors in any work area shall comply with the
requirements of the VCC.
Exception: Existing interior finish materials that do not
comply with the interior finish requirements of the VCC shall be permitted to
be treated with an approved fire-retardant coating in accordance with the
manufacturer's instructions to achieve the required rating.
603.4.3.1 Supplemental interior finish requirements. Where
the work area on any floor exceeds 50% of the floor area, Section 603.4.3 shall
also apply to the interior finish in exits and corridors serving the work area
throughout the floor.
Exception: Interior finish within tenant spaces that are
entirely outside the work area.
603.4.4 Guards. The requirements of Sections 603.4.4.1 and
603.4.4.2 shall apply in all work areas.
603.4.4.1 Minimum requirement. Every portion of a floor,
such as a balcony or a loading dock, that is more than 30 inches (762 mm) above
the floor or grade below and is not provided with guards, or those in which the
existing guards are judged to be in danger of collapsing, shall be provided
with guards.
603.4.4.2 Design. Where there are no guards or where
existing guards must be replaced, the guards shall be designed and installed in
accordance with the VCC.
603.4.5 603.4 Fire-resistance ratings. Where
approved by the code official, buildings Buildings where an
automatic sprinkler system installed in accordance with Section 903.3.1.1 or
903.3.1.2 of the VCC has been added, and the building is now sprinklered
throughout, the required fire-resistance ratings of building elements and
materials shall be permitted to meet the requirements of the current building
code.
603.5 Fire protection. The requirements of Section 603.5
shall be limited to work areas in which Level 2 alterations are being
performed, and where specified they shall apply throughout the floor on which
the work areas are located or otherwise beyond the work area.
603.5.1 Corridor ratings. Where an approved automatic
sprinkler system is installed throughout the story, the required
fire-resistance rating for any corridor located on the story shall be permitted
to be reduced in accordance with the VCC. In order to be considered for a
corridor rating reduction, such system shall provide coverage for the stairway
landings serving the floor and the intermediate landings immediately below.
603.5.2 Automatic sprinkler system. Automatic sprinkler
systems shall be provided in accordance with the requirements of Sections
603.5.2.1 through 603.5.2.5. Installation requirements shall be in accordance
with the VCC.
603.5.2.1 High-rise buildings. In high-rise buildings, work
areas that have exits or corridors shared by more than one tenant or that have
exits or corridors serving an occupant load greater than 30 shall be provided
with automatic sprinkler protection in the entire work area where the work area
is located on a floor that has a sufficient sprinkler water supply system from
an existing standpipe or a sprinkler riser serving that floor.
603.5.2.1.1 Supplemental automatic sprinkler system
requirements. Where the work area on any floor exceeds 50% of that floor area,
Section 603.5.2.1 shall apply to the entire floor on which the work area is
located.
Exception: Occupied tenant spaces that are entirely outside
the work area.
603.5.2.2 Groups A, B, E, F-1, H, I, M, R-1, R-2, R-4, S-1
and S-2. In buildings with occupancies in Groups A, B, E, F-1, H, I, M, R-1,
R-2, R-4, S-1 and S-2, work areas that have exits or corridors shared by more
than one tenant or that have exits or corridors serving an occupant load
greater than 30 shall be provided with automatic sprinkler protection where all
of the following conditions occur:
1. The work area is required to be provided with automatic
sprinkler protection in accordance with the VCC as applicable to new
construction; and
2. The work area exceeds 50% of the floor area.
Exception: If the building does not have sufficient
municipal water supply for design of a fire sprinkler system available to the
floor without installation of a new fire pump, work areas shall be protected by
an automatic smoke detection system throughout all occupiable spaces other than
sleeping units or individual dwelling units that activates the occupant
notification system in accordance with Sections 907.4, 907.5 and 907.6 of the
VCC.
603.5.2.2.1 Mixed uses. In work areas containing mixed uses,
one or more of which requires automatic sprinkler protection in accordance with
Section 603.5.2.2, such protection shall not be required throughout the work
area provided that the uses requiring such protection are separated from those
not requiring protection by fire-resistance-rated construction having a minimum
two-hour rating for Group H and a minimum one-hour rating for all other
occupancy groups.
603.5.2.3 Windowless stories. Work located in a windowless
story, as determined in accordance with the VCC, shall be sprinklered where the
work area is required to be sprinklered under the provisions of the VCC for
newly constructed buildings and the building has a sufficient municipal water
supply without installation of a new fire pump.
603.5.2.4 Other required automatic sprinkler systems. In
buildings and areas listed in Table 903.2.11.6 of the VCC, work areas that have
exits or corridors shared by more than one tenant or that have exits or
corridors serving an occupant load greater than 30 shall be provided with an
automatic sprinkler system under the following conditions:
1. The work area is required to be provided with an
automatic sprinkler system in accordance with the VCC applicable to new
construction; and
2. The building has sufficient municipal water supply for
design of an automatic sprinkler system available to the floor without
installation of a new fire pump.
603.5.2.5 Supervision. Fire sprinkler systems required by
this section shall be supervised by one of the following methods:
1. Approved central station system in accordance with NFPA
72;
2. Approved proprietary system in accordance with NFPA 72;
3. Approved remote station system of the jurisdiction in
accordance with NFPA 72; or
4. When approved by the code official, approved local alarm
service that will cause the sounding of an alarm in accordance with NFPA 72.
Exception: Supervision is not required for the following:
1. Underground gate valve with roadway boxes.
2. Halogenated extinguishing systems.
3. Carbon dioxide extinguishing systems.
4. Dry-chemical and wet-chemical extinguishing systems.
5. Automatic sprinkler systems installed in accordance with
NFPA 13R where a common supply main is used to supply both domestic and
automatic sprinkler systems and a separate shutoff valve for the automatic
sprinkler system is not provided.
603.5.3 Standpipes. Where the work area includes exits or
corridors shared by more than one tenant and is located more than 50 feet
(15,240 mm) above or below the lowest level of fire department access, a
standpipe system shall be provided. Standpipes shall have an approved fire
department connection with hose connections at each floor level above or below
the lowest level of fire department access. Standpipe systems shall be
installed in accordance with the VCC.
Exceptions:
1. No pump shall be required provided that the standpipes
are capable of accepting delivery by fire department apparatus of a minimum of
250 gallons per minute (gpm) at 65 pounds per square inch (psi) (946 L/m at
448KPa) to the topmost floor in buildings equipped throughout with an automatic
sprinkler system or a minimum of 500 gpm at 65 psi (1892 L/m at 448KPa) to the
topmost floor in all other buildings. Where the standpipe terminates below the topmost
floor, the standpipe shall be designed to meet (gpm/psi) (L/m/KPa) requirements
of this exception for possible future extension of the standpipe.
2. The interconnection of multiple standpipe risers shall
not be required.
603.5.4 Fire alarm and detection. An approved fire alarm
system shall be installed in accordance with Sections 603.5.4.1 through
603.5.4.3. Where automatic sprinkler protection is provided in accordance with
Section 603.5.2 and is connected to the building fire alarm system, automatic
heat detection shall not be required.
An approved automatic fire detection system shall be
installed in accordance with the provisions of this code and NFPA 72. Devices,
combinations of devices, appliances, and equipment shall be approved. The
automatic fire detectors shall be smoke detectors, except that an approved
alternative type of detector shall be installed in spaces such as boiler rooms,
where products of combustion are present during normal operation in sufficient
quantity to actuate a smoke detector.
603.5.4.1 Fire alarm requirements. A fire alarm system shall
be installed in accordance with Sections 603.5.4.1.1 through 603.5.4.1.7 and
Sections 1103.7 and 1103.8 of the IFC. Existing alarm-notification appliances
shall be automatically activated throughout the building. Where the building is
not equipped with a fire alarm system, alarm-notification appliances within the
work area shall be provided and automatically activated.
Exceptions:
1. Occupancies with an existing, previously approved fire
alarm system.
2. Where selective notification is permitted,
alarm-notification appliances shall be automatically activated in the areas
selected.
603.5.4.1.1 Group E. Work areas classified as Group E
occupancies.
603.5.4.1.2 Group I-1. Work areas classified as Group I-1
residential care/assisted living facilities.
603.5.4.1.3 Group I-2. Throughout occupancies classified as
Group I-2 occupancies.
603.5.4.1.4 Group I-3. Work areas classified as Group I-3
occupancies.
603.5.4.1.5 Group R-1. Occupancies classified as Group R-1
occupancies.
603.5.4.1.6 Group R-2. Work areas classified as Group R-2
apartment buildings.
603.5.4.1.7 Group R-4. Work areas classified as Group R-4
residential care/assisted living facilities.
603.5.4.2 Supplemental fire alarm system requirements. Where
the work area on any floor exceeds 50% of that floor area, Section 603.5.4.1
shall apply throughout the floor.
Exception: Alarm initiating and notification appliances
shall not be required to be installed in tenant spaces outside of the work
area.
603.5.4.3 Smoke alarms. Individual sleeping units and
individual dwelling units in any work area in Group R and I-1 occupancies shall
be provided with smoke alarms in accordance with the International Fire Code.
Exception: Interconnection of smoke alarms outside of the
work area shall not be required.
603.6 Means of egress. The means of egress shall comply with
the requirements of Section 603.6.
Exceptions:
1. Where the work area and the means of egress serving it
complies with NFPA 101.
2. Means of egress conforming to the requirements of the
building code under which the building was constructed shall be considered
compliant means of egress.
603.6.1 General. The requirements of this section shall be limited
to work areas that include exits or corridors shared by more than one tenant
within the work area in which Level 2 alterations are being performed, and
where specified they shall apply throughout the floor on which the work areas
are located or otherwise beyond the work area.
603.6.2 Number of exits. The number of exits shall be in
accordance with Sections 603.6.2.1 through 603.6.2.3.
603.6.2.1 Minimum number. Every story utilized for human
occupancy on which there is a work area that includes exits or corridors shared
by more than one tenant within the work area shall be provided with the minimum
number of exits based on the occupancy and the occupant load in accordance with
the VCC. In addition, the exits shall comply with Sections 603.6.2.1.1 and 303.
603.6.2.1.1 Single-exit buildings. Only one exit is required
from buildings and spaces of the following occupancies:
1. In Groups A, B, E, F, M, U, and S occupancies, a single
exit is permitted in the story at the level of exit discharge when the occupant
load of the story does not exceed 50 and the exit access travel distance does
not exceed 75 feet (22,860 mm).
2. Groups B, F-2, and S-2 occupancies not more than two
stories in height that are not greater than 3,500 square feet per floor (326 m2),
when the exit access travel distance does not exceed 75 feet (22,860 mm). The
minimum fire-resistance rating of the exit enclosure and of the opening
protection shall be one hour.
3. Open parking structures where vehicles are mechanically
parked.
4. In Group R-4 occupancies, the maximum occupant load
excluding staff is 16.
5. Groups R-1 and R-2 not more than two stories in height,
when there are not more than four dwelling units per floor and the exit access
travel distance does not exceed 50 feet (15,240 mm). The minimum
fire-resistance rating of the exit enclosure and of the opening protection
shall be one hour.
6. In multilevel dwelling units in buildings of occupancy
Group R-1 or R-2, an exit shall not be required from every level of the
dwelling unit provided that one of the following conditions is met:
6.1. The travel distance within the dwelling unit does not
exceed 75 feet (22,860 mm); or
6.2. The building is not more than three stories in height
and